Operating instructions magnetostrictive level transmitter, models FLM-CA, FLM-CM
10
5. Commissioning, operation
DANGER!
Risk of injury due to improper use
Work on containers involves the danger of intoxication and suffocation.
▶
No work is allowed to be carried out unless by taking suitable personal
protective measures (e.g. breathing apparatus, protective clothing etc.).
▶
Work on the instrument must only be carried out by trained skilled
personnel.
5.1 Mounting
■
During mounting, ensure that the guide tube is not bent and that the float is not
subjected to shock loads.
■
The installation of the level transmitter in areas with strong external magnetic fields is
not permitted, since this will impede the correct measured value determination.
■
The level transmitter can also be installed in the vessel from below. If the vessel is also
pressurised, then the maximum length of the level transmitter is 2 m.
Guide tube length
Guide tube length
Inser
tion length
Guide tube
Screw-in body
Flange
Mounting on bypass
Probe head
Probe head
Neck tube
Flange
Screw-in
body
112
112
116
Float
Float
Adjusting
collar
Adjusting
collar
Guide tube
88
5. Commissioning, operation