Operating instructions magnetostrictive level transmitter, models FLM-CA, FLM-CM
11
■
If, during mounting, the float is removed, it must be slid back onto the guide tube with
the marking “TOP” in the direction of the probe head, so that correct measurement can
be made.
5.1.1 “Screw-in body” version
The dismounting of the float is then only required if the float cannot pass
through the mounting hole in the vessel. Otherwise, only mounting steps 3, 6
and, if necessary, 7 must be carried out.
Inserting the level transmitter into the vessel:
1. Loosen both threaded pins, remove the adjusting collar
and remove the float
from
the guide tube
.
2. If necessary, slide the screw-in body
onto the guide tube.
3. Insert the level transmitter into the vessel, apply suitable sealing material to, screw in
and tighten the mounting thread
.
4. Slide the float
back onto the guide tube
.
The float must be slid back onto the guide tube with the marking “TOP” in the
direction of the probe head, so that correct measurement can be made.
5. Re-affix the adjusting collar
, position and secure the threaded pins over the groove.
6. Position the process connection to its height and tighten the union nut
finger-tight by
hand.
5. Commissioning, operation