EN
WIKA operating instructions digital indicator, model DI32-1
63
14122699.03 03/2020 EN/DE
15. Factory settings / 16. Faults
Parameter
Default
OVEr
no
PPt
1
PrES
1
Pt.SE
Pt.Lo
rAnG
9999
run
ULOC
SEC
1
SPC.A
0
Parameter
Default
SPC.F
0
tArA
0
tASt
no
tHEr
tYP.l
tIME
MIn
UnIt
°C
VolT
0 ... 10
ZErO
0
16. Faults
Faults
Causes
Measures
Permanent overrun
4 bars above
Input signal too high
Check the measuring path
Indication range or predefined
measuring range
is exceeded
Check the programmable
points, input types and signal
range
Not all programmable points are
parameterised
Check the parameters
Permanent underrun
4 bars below
Input signal too small
Check the measuring path
Indication range or predefined
measuring range
has been overrun at the low end
Check the programmable
points, input types and signal
range
Not all programmable points are
parameterised
Check the parameters
LBR is displayed
Cable break at the sensor,
incorrect connection of the
sensor (no connection to the
terminal)
Check the input type
Check the cabling
help is displayed
Error in the configuration
memory
Restore factory settings
Settings for measuring input not
available
Password protection active
Deactivating the password
protection
Err 1 is displayed
---
Return the digital indicator to the
manufacturer.