EN
WIKA operating instructions digital indicator, model DI32-1
33
14122699.03 03/2020 EN/DE
9.3 Select frequency range
Parameter
Description
9,999
0 ... 9.999 Hz (automatic software filter at 100 Hz/5 ms)
99.99
0 ... 99.99 Hz (automatic software filter at 500 Hz/5 ms)
999.9
0 ... 999.9 Hz
9999
0 ... 9999 Hz (approximately 10 kHz)
9.4 Selecting pulse length limiting
Debounces mechanical contacts via the filter frequency.
Parameter
Description
no
No evaluation of the pulse length.
2
2 Hz with a pulse-duty factor of 1:1 (minimum pulse length 250 ms)
5
5 Hz with a pulse-duty factor of 1:1 (minimum pulse length 100 ms)
10
10 Hz with a pulse-duty factor of 1:1 (minimum pulse length 50 ms)
20
20 Hz with a pulse-duty factor of 1:1 (minimum pulse length 25 ms)
50
50 Hz with a pulse-duty factor of 1:1 (minimum pulse length 10 ms)
100
100 Hz with a pulse-duty factor of 1:1 (minimum pulse length 5 ms)
500
500 Hz with a pulse-duty factor of 1:1 (minimum pulse length 1 ms)
TYPE
rAnG
[
▲
] [
▼
]
9.999
99.99
[
☼
]
[
▲
]
[
▼
]
[
☼
]
999.9
9999
TYPE
FILt
[
▲
] [
▼
]
no
2
[
☼
]
[
▲
]
[
▼
]
[
☼
]
500
9. Frequency measurement