9.9 Linearising the sensor values
Setting the number of programmable points
In addition to the lower and upper indication values, an additional 5 programmable
points can be defined. Only activated programmable point parameters will be
displayed (dIS.1 ... 5, InP.1 ... 5).
Parameter
Description
Setting range
SPC.F
Number of programmable points
0 ... 5
Setting analogue and indication values for programmable points
The value stored under “dIS” will be shown on the display, when it matches the
sensor signal defined under “InP”. The values must be parameterised in increasing
order.
Parameter
Description
Setting range
dIS.1
Indication value for programmable point 1
-1999 ... 9999
InP.1
Analogue value for programmable point 1
-1999 ... 9999
dIS.2
Indication value for programmable point 2
-1999 ... 9999
InP.2
Analogue value for programmable point 2
-1999 ... 9999
dIS.3
Indication value for programmable point 3
-1999 ... 9999
InP.3
Analogue value for programmable point 3
-1999 ... 9999
dIS.4
Indication value for programmable point 4
-1999 ... 9999
InP.4
Analogue value for programmable point 4
-1999 ... 9999
dIS.5
Indication value for programmable point 5
-1999 ... 9999
InP.5
Analogue value for programmable point 4
-1999 ... 9999
TYPE
SPC.F
[
▲
] [
▼
]
[
☼
]
[
☼
]
dIS.1
InP.1
dIS.5
[
▲
]
[
▼
]
InP.5
0
…
5
[
▲
] [
▼
]
[
☼
]
-1999
…
9999
[
☼
]
-1999
…
9999
[
☼
]
-1999
…
9999
[
☼
]
-1999
…
9999