5.9
Wieland Electric | BA000349 | 05.2007
5 |
Commissioning
5.8 Preparing the MOVIMOT
®
Operating the podis MOT requires a few settings on the MOVIMOT.
Information about the individual settings can be found in the operating instructions for
MOVIMOT.
The following settings must be performed:
• Setting the RS485 slave address "1" at MOVIMOT via DIP switch S1.
• Setting the minimum frequency via potentiometer F2. The speed setpoint is preset
relative as a percentage referenced to the maximum speed adjusted by means of the
setpoint potentiometer F1.
The ramp setting at MOVIMOT via the potentiometer is not incorporated if the RS485 inter-
face is used.
5.9 Addressing the field distributor
The PROFIBUS address can be set between 1 and 126.
The address assignment is carried out by positioning the two rotary switches in the elec-
tronics cover.
Proceed as follows to address the field distributor:
1. Remove the four fastening screws of the electronics cover and remove it.
2. Set the configured PROFIBUS address at the two rotary switches.
3. Attach the electronics cover with the four fastening screws.
• Ensure that the unit is tight and that no connecting cables have been pinched.
• The field distributor is addressed.
NOTICE
The set address is read only once upon switching on the motor.Addresses greater than
"125" are recognized as "126", and a fault message is issued. The "RUN" LED flashes.
PROFIBUS
address setting
PROFIBUS
address setting
Procedure
Procedure
PROFIBUS-DP addressing switches (rotary switches) in electronics cover
1 – Unit place (BCD)
2 – Tens digit (hex)
e.g. unit place = 5 and
tens digit = Acorresponds to
address 105 dec.
Summary of Contents for podis MOT FP C
Page 2: ......
Page 22: ...Wieland Electric BA000349 05 2007 podis MOT FP C CM CP I IO RS485 SEW Device Description 2...
Page 24: ...3 Wieland Electric BA000349 05 2007 Mechanical Installation Assembly 3...
Page 44: ...5 Wieland Electric BA000349 05 2007 Commissioning 5...
Page 46: ...6 Wieland Electric BA000349 05 2007 Operation 6...
Page 62: ...9 6 Wieland Electric BA000349 05 2007 Appendix 9...
Page 63: ......
Page 64: ......