Electrical Installation
4 Electrical Installation
The podis CON manual BA000372 must be taken into account for the routing and connection
of the flat cable.
• All electrical installations and connections may be performed only by trained electricians.
• The applicable safety and accident prevention regulations must be observed.
• The connectors may never be connected or disconnected under load.
• Before opening and removing the electronics cover, the entire flat cable must be de-ener-
gized.
• When routing extra-low voltage circuits together with low-voltage circuits using one line,
the line must be protected against mechanical damage in areas of risk, e.g. cable channel,
steel pipe or similar protection.
4. Connection to the podis
®
energy bus
��
��
��
�
�
�
��
Core PVC (gray, 7 x .5 mm
) EVA (black, 7 x 4 mm
)
L1
brown
1 (black)
L2
black
2 (black)
L3
gray
3 (black)
N
blue
4 (black)
PE
green/yellow
PE green/yellow
+
red
5 (black)
-
white
6 (black)
The illustrated assignment of cores in the podis flat cable must be followed for the field dis-
tributor to ensure proper operation.
The auxiliary voltage for the supply of the outputs and inputs must be taken from a safely
isolated power supply (PELV acc. to IEC 60364-4-41)!
NOTE
The podis flat cable is coded, thereby preventing an incorrect insertion.
Summary of Contents for podis MOT FP C
Page 2: ......
Page 22: ...Wieland Electric BA000349 05 2007 podis MOT FP C CM CP I IO RS485 SEW Device Description 2...
Page 24: ...3 Wieland Electric BA000349 05 2007 Mechanical Installation Assembly 3...
Page 44: ...5 Wieland Electric BA000349 05 2007 Commissioning 5...
Page 46: ...6 Wieland Electric BA000349 05 2007 Operation 6...
Page 62: ...9 6 Wieland Electric BA000349 05 2007 Appendix 9...
Page 63: ......
Page 64: ......