background image

Safety 

Precautions

15.

Labelling

Equipment shall be labelled stating that it has been decommissioned and emptied of refrigerant. The

 

label

shall be dated and signed. Ensure that there are labels on the equipment stating the equipment

 

contains

flammable refrigerant.

16.

Recovery

When removing refrigerant from a system, either for servicing or decommissioning, it is recommended
good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders,

 

ensure

that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct

 

number of

cylinders for holding the total system charge is available. All cylinders to be used are

 

designated for the

recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the

 

recovery of refrigerant).

Cylinders shall be complete with pressure relief valve and associated shut-off

 

valves in good working

order. Empty recovery cylinders are evacuated and, if possible, cooled before

13.

Charging procedures

In addition to conventional charging procedures, the following requirements shall be followed. Ensure
that contamination of different refrigerants does not occur when using charging equipment. Hoses or
lines shall be as short as possible to minimise the amount of refrigerant contained in them.
Cylinders shall be kept upright.
Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it

 

shall

be pressure tested with OFN. The system shall be leak tested on completion of charging but prior

 

to

commissioning. A follow up leak test shall be carried out prior to leaving the site.

14.

Decommissioning

Before carrying out this procedure, it is essential that the technician is completely familiar with the
equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely.
Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is

 

required

prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before

 

the task is

commenced.

a)

Become familiar with the equipment and its operation.    b) Isolate system electrically.    c) Before

attempting the procedure ensure that: Mechanical handling equipment is available, if required, for
handling refrigerant cylinders;All personal protective equipment is available and being used correctly;
The recovery process is supervised at all times by a competent person; Recovery equipment and

 

cylinders

conform to the appropriate standards.    d) Pump down refrigerant system, if possible.    e) If a

 

vacuum is

not possible, make a manifold so that refrigerant can be removed from various parts of  the

 

system.     f)

Make sure that cylinder is situated on the scales before recovery takes place.    g) Start the

 

recovery

machine and operate in accordance with manufacturer's instructions.    h) Do not overfill

 

cylinders. (No

more than 80 % volume liquid charge).     i)  Do not exceed the maximum working

 

pressure of thecylinder,

even temporarily.     j)  When the cylinders have been filled correctly and the

 

process completed, make

sure that the cylinders and the equipment are removed from site promptly

 

and all isolation valves on the

equipment are closed off.     k) Recovered refrigerant shall not be charged

 

into another refrigeration

system unless it has been cleaned and checked.

oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system 
with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and 
finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. 
When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable 
work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take 
place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is 
ventilation available.

Page 

9

 

Summary of Contents for ARC-148MS

Page 1: ...IONER Congratulations on your new Whynter product To ensure proper operation please read this Instruction Manual carefully before using this product Keep this manual in a safe place for future referen...

Page 2: ...cautions Air Filter Cleaning Unit Cleaning Store the unit when not in use Preparation Design Notice Energy Rating Information Ambient Temperature Range For Unit Operating Exhaust Hose Installation Cho...

Page 3: ...the nameplate located on unit have a qualified electrician install the proper receptacle Install the unit on a flat sturdy surface Failure to do so could result in damage or excessive noise and vibra...

Page 4: ...e the appliance must be disconnected from the supply mains Do not remove any fixed covers Never use this appliance if it is not working properly or if it has been dropped or damaged Do not run cord un...

Page 5: ...uction The appliance shall be stored so as to prevent mechanical damage from occurring A warning that the appliance shall be stored in a well ventilated area where the room size corresponds to the roo...

Page 6: ...rk on the system 2 Work procedure Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being present while the work is being performed 3 General...

Page 7: ...th the room size within which the refrigerant containing parts are installed The ventilation machinery and outlets are operating adequately and are not obstructed If an indirect refrigerating circuit...

Page 8: ...the copper pipe work If a leak is suspected all naked flames shall be removed extinguished If a leakage of refrigerant is found which requires brazing all of the refrigerant shall be recovered from th...

Page 9: ...that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It is...

Page 10: ...re that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant The evacuation process shall be carried out prior to returning t...

Page 11: ...ll to ensure proper air conditioning The horizontal louver blade should be at least 20 away from obstacles DO NOT cover the Intakes Outlets or Remote Signal Receptor of the unit as this could cause da...

Page 12: ...on older units Federal regulations require manufacturers to calculate cooling capacity based on a specific test procedure which was changed just this year Models manufactured before 2017 were tested...

Page 13: ...ION QUANTITY 1 piece 1 piece 1 piece Window Slider Kit 1 set Clear plastic plug plug is in the upper corner of the plastic bag that holds the user manual 1 piece Foam seal A Adhesive Foam seal B Adhes...

Page 14: ...emperature 1 C 2 F increments or timer hours 0 24 hours This unit is capable of displaying set temperature in Fahrenheit or in Celsius To convert from one to the other press and hold the Up and Down b...

Page 15: ...ssory sold separately under the drain area of the lower drain port Remove the bottom drain plug and let the water drain Replace the drain plug and plug in to resume operation Continuous drainage Fig 1...

Page 16: ...to the necessary length keeping it as short and straight as possible WINDOW KIT INSTALLATION The window kit has been designed to fit most standard vertical and horizontal windows However it may be ne...

Page 17: ...type Security bracket Screws Foam seal C non adhesive type Foam seal A adhesive type Foam seal B adhesive type Security bracket Screws Foam seal C non adhesive type EXHAUST AND INTAKE HOSE INSTALLATI...

Page 18: ...s function mode press the MODE button until the DRY indicator light is displayed Please note that when switching function mode there will be an approxi mately 3 minute transition time In dehumidifying...

Page 19: ...comes on AUTO RESTART In the event of a power outage the air conditioner restarts at the previously set function mode and settings when power is restored CONTROLLING THE AIR FLOW DIRECTION The louvers...

Page 20: ...ays when remote sends signal to unit 3 ON OFF Display Displays when the unit is turned on and disappears when it is turned off 4 Timer On Indicator Displays when TIMER ON is set 5 Timer Off Indicator...

Page 21: ...e washable pre This unit has three air filters the washable pre filter activated carbon filter and lower filter Switch off the air conditioner and remove the washable pre filter and activated carbon f...

Page 22: ...yet because of its time delay The set temperature is too high The internal water reservoir is full and P1 appears on display This unit is designed to work in ambient temperatures of 63 F to 90 F Pres...

Page 23: ...y The unit is not level The surface underneath the unit is uneven Low power voltage Make sure the unit is on hard level and stable surface Move the unit to a location with a level and hard floor Make...

Page 24: ...Use in commercial or industrial applications Damage accidental or otherwise to the product while in the possession of a consumernot caused by a defect in material or workmanship Damage caused by cons...

Reviews: