background image

Safety 

Precautions

Page 

8

 

8.

Repair to intrinsically safe components

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will
not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe
components are the only types that can be worked on while live in the presence of a flammable
atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts
specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere
from a leak.

9.

Cabling

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or
any other adverse environmental effects. The check shall also take into account the effects of aging or
continual vibration from sources such as compressors or fans.

10.

Detection of flammable refrigerants

Under no circumstances shall potential sources of ignition be used in the searching for or detection
of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

11.

Leak detection methods

The following leak detection methods are deemed acceptable for systems containing flammable
refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity
may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a
refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for

 

the

refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant

 

 

and

shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 %maximum) is 

confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of

 

detergents 

containing chlorine shall be avoided as the chlorine may react with the refrigerant and

 

corrode the 

copper pipe-work. If a leak is suspected, all naked flames shall be removed/ extinguished.

 

If a leakage of 

refrigerant is found which requires brazing, all of the refrigerant shall be recovered from

 

the system, or 

isolated (by means of shut off valves) in a part of the system remote from the leak.

 

Oxygen free nitrogen 

(OFN) shall then be purged through the system both before and during the

 

brazing process.

12.

Removal and evacuation

When breaking into the refrigerant circuit to make repairs or for any other purpose conventional
procedures shall be used. However, it is important that best practice is followed since flammability is a
consideration. The following procedure shall be adhered to:
Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge again with inert gas; Open the
circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed
with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or

being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an 
electrical supply to equipment during servicing, then a permanently operating form of leak detection 
shall be located at the most critical point to warn of a potentially hazardous situation. 
2)Particular attention shall be paid to the following to ensure that by working on electrical components,
the casing is not altered in such a way that the level of protection is affected. This shall include damage
to cables, excessive number of connections, terminals not made to original specification, damage to
seals, incorrect fitting of glands, etc.  Ensure that apparatus is mounted securely. Ensure that seals or
sealing materials have not degraded such that they no longer serve the purpose of preventing the
ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer's
specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection
equipment. Intrinsically safe components do not have to be isolated prior to working on them.

Summary of Contents for ARC-148MS

Page 1: ...IONER Congratulations on your new Whynter product To ensure proper operation please read this Instruction Manual carefully before using this product Keep this manual in a safe place for future referen...

Page 2: ...cautions Air Filter Cleaning Unit Cleaning Store the unit when not in use Preparation Design Notice Energy Rating Information Ambient Temperature Range For Unit Operating Exhaust Hose Installation Cho...

Page 3: ...the nameplate located on unit have a qualified electrician install the proper receptacle Install the unit on a flat sturdy surface Failure to do so could result in damage or excessive noise and vibra...

Page 4: ...e the appliance must be disconnected from the supply mains Do not remove any fixed covers Never use this appliance if it is not working properly or if it has been dropped or damaged Do not run cord un...

Page 5: ...uction The appliance shall be stored so as to prevent mechanical damage from occurring A warning that the appliance shall be stored in a well ventilated area where the room size corresponds to the roo...

Page 6: ...rk on the system 2 Work procedure Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being present while the work is being performed 3 General...

Page 7: ...th the room size within which the refrigerant containing parts are installed The ventilation machinery and outlets are operating adequately and are not obstructed If an indirect refrigerating circuit...

Page 8: ...the copper pipe work If a leak is suspected all naked flames shall be removed extinguished If a leakage of refrigerant is found which requires brazing all of the refrigerant shall be recovered from th...

Page 9: ...that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It is...

Page 10: ...re that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant The evacuation process shall be carried out prior to returning t...

Page 11: ...ll to ensure proper air conditioning The horizontal louver blade should be at least 20 away from obstacles DO NOT cover the Intakes Outlets or Remote Signal Receptor of the unit as this could cause da...

Page 12: ...on older units Federal regulations require manufacturers to calculate cooling capacity based on a specific test procedure which was changed just this year Models manufactured before 2017 were tested...

Page 13: ...ION QUANTITY 1 piece 1 piece 1 piece Window Slider Kit 1 set Clear plastic plug plug is in the upper corner of the plastic bag that holds the user manual 1 piece Foam seal A Adhesive Foam seal B Adhes...

Page 14: ...emperature 1 C 2 F increments or timer hours 0 24 hours This unit is capable of displaying set temperature in Fahrenheit or in Celsius To convert from one to the other press and hold the Up and Down b...

Page 15: ...ssory sold separately under the drain area of the lower drain port Remove the bottom drain plug and let the water drain Replace the drain plug and plug in to resume operation Continuous drainage Fig 1...

Page 16: ...to the necessary length keeping it as short and straight as possible WINDOW KIT INSTALLATION The window kit has been designed to fit most standard vertical and horizontal windows However it may be ne...

Page 17: ...type Security bracket Screws Foam seal C non adhesive type Foam seal A adhesive type Foam seal B adhesive type Security bracket Screws Foam seal C non adhesive type EXHAUST AND INTAKE HOSE INSTALLATI...

Page 18: ...s function mode press the MODE button until the DRY indicator light is displayed Please note that when switching function mode there will be an approxi mately 3 minute transition time In dehumidifying...

Page 19: ...comes on AUTO RESTART In the event of a power outage the air conditioner restarts at the previously set function mode and settings when power is restored CONTROLLING THE AIR FLOW DIRECTION The louvers...

Page 20: ...ays when remote sends signal to unit 3 ON OFF Display Displays when the unit is turned on and disappears when it is turned off 4 Timer On Indicator Displays when TIMER ON is set 5 Timer Off Indicator...

Page 21: ...e washable pre This unit has three air filters the washable pre filter activated carbon filter and lower filter Switch off the air conditioner and remove the washable pre filter and activated carbon f...

Page 22: ...yet because of its time delay The set temperature is too high The internal water reservoir is full and P1 appears on display This unit is designed to work in ambient temperatures of 63 F to 90 F Pres...

Page 23: ...y The unit is not level The surface underneath the unit is uneven Low power voltage Make sure the unit is on hard level and stable surface Move the unit to a location with a level and hard floor Make...

Page 24: ...Use in commercial or industrial applications Damage accidental or otherwise to the product while in the possession of a consumernot caused by a defect in material or workmanship Damage caused by cons...

Reviews: