Page 14
15628-0-0903
DELAYED IGNITION RESET SWITCH
Attach black wire from REMOTE/OFF/ON switch to the front
1/4" male tab on the reset switch. Attachment of black wire
onto the reset switch is done in conjunction with the preceding
steps for Wire Channel Installation. Attach black wire on the
back of the reset switch to the TH/TP terminal on gas valve.
The reset switch can be activated if the main burner has a delayed
ignition. The right, relief door is connected by a metal wire to a
cotter pin that is inserted into the reset switch. When a delayed
ignition occurs the right, relief door pivots upward, the metal wire
pulls the cotter pin out of the reset switch and the main burner is
shut OFF.
Whenever the delayed ignition reset switch is activated you
must contact a qualified service person to determine the cause
for the delayed ignition reset switch to be activated.
Replacement of cotter pin into delayed ignition reset switch
assembly by a qualified service person.
1. Lower valve cover.
2. The reset switch is located behind the right side of the valve
cover.
3. Verify the metal cable with attached cotter pin has free
movement.
4. Depress the metal lever arm located on the front of the reset
switch.
5. With the metal lever arm depressed, insert cotter pin into the
clearance hole on the right side of the bracket and into the
clearance hole on the left side of the bracket.
Attention: The tip of the cotter pin must remain flat. The
tip of the cotter pin must never be bent-over. If the tip of the
cotter pin is bent-over it could prevent the delayed ignition
reset switch from functioning during a delayed ignition.
6. Replacement of cotter pin into delayed ignition reset switch
assembly is completed.
Reassembly and Resealing Gas Accumulation Relief System
(Relief Doors) and Combustion Chamber
Whenever the relief doors are pivoted open by a delayed ignition
in the main burner, the relief door gaskets and combustion chamber
must be examined by a qualified service person for damage. All
damaged gaskets on the relief doors and combustion chamber
must be replaced by a qualified service person. If damage occurs
to the combustion chamber, it must be replaced by a qualified
service person. Contact Empire Comfort Systems, Inc. for
replacement parts.
Figure 15
Figure 14
DVKA-1 VENT ELBOW INSTALLATION
Attention: A tube of furnace cement is provided in the
Owner's Envelope. Apply furnace cement to the top, exterior
edge on the cast iron flue outlet.
Place the DVKA-1, vent elbow onto the flue outlet as you
align the clearance holes on the vent elbow with the clearance
holes on the vent elbow gasket.
Install the vent elbow onto the flue outlet with (4) hex-head
screws provided in hardware package. The vent elbow can
be installed in the vertical position or horizontal position.
All vent runs must have a minimum vertical rise of two
feet. If the vent elbow is installed in the horizontal position
and the vent run is directly behind the fireplace, you must
use Simpson Dura-Vent 36" snorkel, part number, SD-981
on exterior of the structure.