background image

8

Defrost Thermostat

The defrost thermostat is located on the liquid line between the 
check/expansion valve and the distributor. When defrost 
thermostat senses 42ºF or cooler, the thermostat contacts close 
and send a signal to the defrost control board to start the defrost 
timing. It also terminates defrost when the liquid line warms up to 
70ºF.

Defrost Control

The defrost control board includes the combined functions of the 
time/temperature defrost control, defrost relay, diagnostic LEDs 
and terminal strip for field wiring connections. See "Defrost 
Control Board" illustration.

The control provides automatic switching from normal heating 
operation to defrost mode and back. During compressor cycle 
(call for defrost), the control accumulates compressor run times 
at 30, 60 or 90 minute field-adjustable intervals. If the defrost 
thermostat is closed when the selected compressor run time 
interval ends, the defrost relay is energized and defrost begins.

Defrost Control Timing Pins

Each timing pin selection provides a different accumulated 
compressor run time period during one thermostat run cycle. This 
time period must occur before a defrost cycle is initiated. The 
defrost interval can be adjusted to 30 (T1), 60 (T2) or 90 (T3) 
minutes. See "Defrost Control Board" illustration. The defrost 
timing jumper is factory-installed to provide a 60-minute defrost 
interval. If the timing selector jumper is not in place, the control 
defaults to a 90-minute defrost interval. The maximum defrost 
period is 14 minutes and cannot be adjusted.

A test option is provided for troubleshooting. The test mode may 
be started any time the unit is in the heating mode and the 
defrost thermostat is closed or jumpered. If the jumper is in the 
test position at power-up, the control will ignore the test pins. 
When the jumper is placed across the Test pins for 2 seconds, 
the control will enter the defrost mode. If the jumper is removed 
before an additional 5-second period has elapsed (7 seconds 
total), the unit will remain in defrost mode until the defrost 
thermostat opens or 14 minutes have passed. If the jumper is not 
removed until after the additional 5-second period has elapsed, 
the defrost will terminate and the test option will not function 
again until the jumper is removed and re-applied.

Pressure Switch Circuit

The defrost control incorporates a pressure switch circuit that 
allows the application of an optional high pressure switch. See 
"Defrost Control Board" illustration. During a demand cycle, the 
defrost control will lock out the unit if the optional high pressure 
switch opens. The diagnostic LEDs will display a pattern for an 
open high pressure switch. See “Diagnostic LEDs.” The unit will 
remain locked out until the switch resets or is reset.

Remove the factory-installed jumper before connecting the 
optional high pressure switch to the control board.

NOTE: If not using a pressure switch, the factory-installed jumper 
wire must be connected.

Adjusting Defrost System

Defrost Control Board

Optional high pressure switch safety circuit connections

NOTE: To add the pressure switch, remove the factory-installed 
jumper.

Adjust Time Between Defrost Cycles

1. Disconnect power.

2. Remove the control box cover.

A. Defrost interval timing pins
B. Test pins

C. Compressor delay pins
D. Reversing valve

E. Low pressure switch

F. Defrost thermostat

G. High pressure switch (optional)

H. Diagnostic LEDs

I. 24V terminal strip connections

K1 Relay

K2 Relay

FAN

DS1

L

24V

P2

P5

O-OUT

DF

Y1-OUT

HI-PS

U1

U2

DS2

K3 Relay

P6

TST PS DF C

R

O Y1

C5

LO-PS

C2

P1

30
60

90

TEST

W1

C

L

R

Y1

O

H

I

A

B

C

D

E

F

G

WARNING

Electrical Shock Hazard

Disconnect power before servicing.

Replace all parts and panels before operating.

Failure to do so can result in death or electrical shock.

Summary of Contents for W2GH3

Page 1: ... you don t immediately You can be killed or seriously injured if you don t follow All safety messages will tell you what the potential hazard is tell you how to reduce the chance of injury and tell you what can happen if the instructions are not followed Your safety and the safety of others are very important We have provided many important safety messages in this manual and on your appliance Alwa...

Page 2: ...installed in the indoor coil Instructions for replacing the expansion device are provided with the indoor coil LocationRequirements This heat pump is designed to be located outdoors with sufficient clearance for free entrance to the inlet and discharge air openings The location must also allow for adequate service access See Minimum Clearances Where possible select a location for the heat pump whi...

Page 3: ...round vapor line only C Wire tie around vapor line only D Tape or wire tie E Metal sleeve F Tape or wire tie G Strap the vapor line to the floor joist or roof rafter at 8 intervals then strap the liquid line to the vapor line A Anchored heavy nylon wire tie B Strap liquid line to vapor line C Liquid line D Vapor line wrapped in armaflex E Metal sleeve F Wall stud G Automotive muffler type hanger B...

Page 4: ...ready to be completed 1 Route the suction and liquid lines from the fittings on the indoor coil to the fittings on the heat pump Run the lines in as direct a path as possible avoiding unnecessary turns and bends 2 For product efficiency be sure that the suction line is insulated over the entire exposed length and that both suction and liquid lines are not in direct contact with floors walls ductwo...

Page 5: ...re to be supplied by the installer Refer to the rating plate for the maximum over current protection minimum circuit ampacity and operating voltage See wiring diagrams later in this section Install an adequately sized branch circuit disconnect per the NEC within sight of and readily accessible from heat pump The cable or conduit and fittings connected from the disconnect to the heat pump shall be ...

Page 6: ... ground wire C 208 230 volt field supply wires WARNING Electrical Shock Hazard Disconnect power before servicing Replace all parts and panels before operating Failure to do so can result in death or electrical shock T1 T2 L1 L2 L1 L2 C A B A Do not connect C common connection between indoor unit and thermostat except when required by the indoor thermostat Refer to the thermostat installation instr...

Page 7: ...s necessary to maintain system performance The defrost control is time temperature initiated and temperature terminated with a maximum defrost time time out of 10 minutes The time between defrost cycles is preset at 60 minute intervals at the factory but can be field adjusted between 30 60 or 90 minutes To adjust the time period between defrost cycles see Adjust Time Between Defrost Cycles The def...

Page 8: ...he test pins When the jumper is placed across the Test pins for 2 seconds the control will enter the defrost mode If the jumper is removed before an additional 5 second period has elapsed 7 seconds total the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed If the jumper is not removed until after the additional 5 second period has elapsed the defrost wi...

Page 9: ...eaves and other large obstructions should be carefully removed from the heat pump surfaces without damaging the fin surface of the coil Routinely clean or change the indoor air filter Should the indoor coil become dirty thus restricting airflow call a qualified service person to carefully clean the coil surface An annual inspection by a qualified person should be performed to ensure continued qual...

Page 10: ...10 Notes ...

Page 11: ...11 ...

Page 12: ..._____________________ Address ________________________________________________________ Phone number__________________________________________________ Model number __________________________________________________ Serial number __________________________________________________ Installation date ________________________________________________ 48348M005 2005 All rights reserved Registered Trademar...

Reviews: