background image

2

INSTALLATION REQUIREMENTS

These instructions are intended as a general guide only and do 
not supersede any national or local codes in any way. The 
installation must comply with all state, and local codes as well as 
the National Electrical Code.

The heat pump is designed and approved for outdoor use 
only.

The heat pump must be installed with no ductwork in the 
airstream. The outdoor fan is not designed to operate against 
any additional static pressure.

Tools and Parts

Gather the required tools and parts before starting installation. 
Read and follow the instructions provided with any tools listed 
here.

Tools needed

Parts needed

Check local codes and HVAC supplier. Check existing electrical 
supply, and read “Electrical Requirements,” “Location 
Requirements,” “System Requirements” and “Connect 
Refrigerant Lines.”

System Requirements

Heat pump system matches are derived from actual laboratory 
testing of matched systems. It is recommended that only 
matching equipment be used to ensure proper operation and 
efficient performance.

The designed system matches are listed in the heat pump 
unit specification sheets and on the heat pump refrigerant 
charging instructions located on the back of the service 
access panel.

Refrigerant charging instructions include a list of matching 
indoor equipment with the proper expansion device size and 
amount of refrigerant charge required.

This heat pump has been factory charged with a quantity of 
refrigerant (R22) sufficient for a matched indoor coil and a 
maximum 15 ft of refrigerant line.

Indoor System Expansion Device

Check the indoor coil expansion device to see whether it 
matches the required expansion device for the indoor coil 
and heat pump combination being installed.

Refer to the refrigerant charge label located on the inside of 
the heat pump access panel for the correct expansion device 
size required. 

Replace the expansion device with the correct size if this size 
is not already installed in the indoor coil. Instructions for 
replacing the expansion device are provided with the indoor 
coil.

Location Requirements

This heat pump is designed to be located outdoors with 
sufficient clearance for free entrance to the inlet and 
discharge air openings. The location must also allow for 
adequate service access. See “Minimum Clearances.”

Where possible, select a location for the heat pump which is 
shaded from the direct rays of the sun most of the time. North 
or east locations are usually most desirable. Position the heat 
pump to avoid direct contact with water, snow or ice from a 
roofline overhead. 

The heat pump must be installed on a solid, level mounting 
pad that will not settle or shift. Isolate the pad from the 
building structure to avoid possible transmission of sound or 
vibration from the heat pump into the conditioned space.

The heat pump foundation should be raised to a minimum of 
3" above finish grade. In areas which have prolonged periods 
of temperatures below freezing, and/or snowfall, the heat 
pump should be elevated above the average snow line. If 
heat pump is to be installed on a flat roof, it should be on a 
platform or other support which will raise the inlet air opening 
12" minimum above the surface of the flat roof.

Care should be taken to ensure free drainage of condensate 
from defrost cycles. This will prevent ice accumulation. The 
heat pump should be located away from walkways to prevent 
possible icing from defrost condensate.

Avoid placing the heat pump near areas such as sleeping 
quarters or study rooms. Normal operating sound levels may 
be objectionable if the heat pump is placed near certain 
rooms. A shift in sound type does occur during the defrost 
mode. The defrost mode generally lasts no longer than 
10 minutes.

Minimum Clearances

Torch

⁵⁄₁₆

" nut driver

¹⁄₄

" nut driver

A. Outdoor rated disconnect switch
B. NEC class 1 wiring

C. NEC class 2 wiring

D. House thermostat

E. Seal openings

48" Overhead

Clearance

(Discharge

Air)

To

Power

Supply

To

Indoor

Unit

To

Indoor

Coil

30" Service

Access Clearance

36" Clearance
         (Inlet Air)

12" Clearance Between
Unit and Building

12" Clearance
(Inlet Air)

A B

C

D

E

Summary of Contents for W2GH3

Page 1: ... you don t immediately You can be killed or seriously injured if you don t follow All safety messages will tell you what the potential hazard is tell you how to reduce the chance of injury and tell you what can happen if the instructions are not followed Your safety and the safety of others are very important We have provided many important safety messages in this manual and on your appliance Alwa...

Page 2: ...installed in the indoor coil Instructions for replacing the expansion device are provided with the indoor coil LocationRequirements This heat pump is designed to be located outdoors with sufficient clearance for free entrance to the inlet and discharge air openings The location must also allow for adequate service access See Minimum Clearances Where possible select a location for the heat pump whi...

Page 3: ...round vapor line only C Wire tie around vapor line only D Tape or wire tie E Metal sleeve F Tape or wire tie G Strap the vapor line to the floor joist or roof rafter at 8 intervals then strap the liquid line to the vapor line A Anchored heavy nylon wire tie B Strap liquid line to vapor line C Liquid line D Vapor line wrapped in armaflex E Metal sleeve F Wall stud G Automotive muffler type hanger B...

Page 4: ...ready to be completed 1 Route the suction and liquid lines from the fittings on the indoor coil to the fittings on the heat pump Run the lines in as direct a path as possible avoiding unnecessary turns and bends 2 For product efficiency be sure that the suction line is insulated over the entire exposed length and that both suction and liquid lines are not in direct contact with floors walls ductwo...

Page 5: ...re to be supplied by the installer Refer to the rating plate for the maximum over current protection minimum circuit ampacity and operating voltage See wiring diagrams later in this section Install an adequately sized branch circuit disconnect per the NEC within sight of and readily accessible from heat pump The cable or conduit and fittings connected from the disconnect to the heat pump shall be ...

Page 6: ... ground wire C 208 230 volt field supply wires WARNING Electrical Shock Hazard Disconnect power before servicing Replace all parts and panels before operating Failure to do so can result in death or electrical shock T1 T2 L1 L2 L1 L2 C A B A Do not connect C common connection between indoor unit and thermostat except when required by the indoor thermostat Refer to the thermostat installation instr...

Page 7: ...s necessary to maintain system performance The defrost control is time temperature initiated and temperature terminated with a maximum defrost time time out of 10 minutes The time between defrost cycles is preset at 60 minute intervals at the factory but can be field adjusted between 30 60 or 90 minutes To adjust the time period between defrost cycles see Adjust Time Between Defrost Cycles The def...

Page 8: ...he test pins When the jumper is placed across the Test pins for 2 seconds the control will enter the defrost mode If the jumper is removed before an additional 5 second period has elapsed 7 seconds total the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed If the jumper is not removed until after the additional 5 second period has elapsed the defrost wi...

Page 9: ...eaves and other large obstructions should be carefully removed from the heat pump surfaces without damaging the fin surface of the coil Routinely clean or change the indoor air filter Should the indoor coil become dirty thus restricting airflow call a qualified service person to carefully clean the coil surface An annual inspection by a qualified person should be performed to ensure continued qual...

Page 10: ...10 Notes ...

Page 11: ...11 ...

Page 12: ..._____________________ Address ________________________________________________________ Phone number__________________________________________________ Model number __________________________________________________ Serial number __________________________________________________ Installation date ________________________________________________ 48348M005 2005 All rights reserved Registered Trademar...

Reviews: