Whelen Engineering Company E-2010 Operation & Installation Manual Download Page 10

6

SYSTEM SETUP

Setup for system variables. Use the Up or Down arrows to move through the choices. The following
parameters are set in this section:

Area Code

3 digits. A value other than 000 must be entered.

Xmitter Up

Radio transmitter warm up time, in seconds or tenths of seconds. A 
value other than 0 must be entered.

Base ID

Base Station identification number, 0-7, for systems with more than one 
E-2010.

Ch Grant Wait

Channel grant waiting time, in seconds. For trunking radios only. The
time that the E-2010 waits until aborting a transmission, if Channel grant
is not received.

Ch Grant Delay

Channel grant delay time, in seconds. The time that the E-2010 holds off
the transmission following the receipt of Channel Grant.

AUDIO

Audio output control. Use the Up or Down arrows to move through the choices. The following functions
are set in this section:

Speaker

The speaker may be Off or set to Radio Channel 1 or 2. The speaker monitors 
any audio on the selected Channel.

Microphone

The Public Address microphone may be Off or set to Radio Channel 1 or 2.

Buzzer

The Low Battery or Intrusion Alarm Buzzer may be On or Off.

CALL KEY SETUP

Setup for all Call Keys. Refer to the Call Key Section of the Manual.

TIME  DATE

Routines for entering current time and date. Use to set the day of the week, the time and the date. Day of
week must be set for Auto Call Keys. Use the Up or Down arrows to select the day. Use the numeric
keypad to set time and date. Time is military time (24 hour time).

OPTION

Reserved for future use.

NOTE:

While in the Menu Selections portion of the keyboard, pressing
CALL KEY CANCEL will return the E-2010 to the standby
screen.

Summary of Contents for E-2010

Page 1: ...6 7 8 9 0 ALL DOWN UP MESSAGES MENU SELECTIONS ENTER WARNING TONES VOICE ROTATING DIRECTION STATUS PORT SETUP AUDIO POLLING SETUP CALL KEY TIME DATE SETUP 2 3 4 8 7 6 5 12 11 10 9 16 15 14 13 SIREN A...

Page 2: ...f a Whelen Engineering Company Inc Model E 2010 Central Control Station Prior to reading this manual or using this product you should be familiar with Whelen Engineering Company s family of High Power...

Page 3: ...e software described in this manual is supplied with the understanding that it may not be copied or otherwise redistributed without prior permission of Whelen Engineering Company Inc All materials and...

Page 4: ...us 4 Port Setup 5 Polling Setup 5 Auto Call Setup 5 System Setup 6 Audio 6 Call Key Setup 6 Time Date 6 Option 6 Call Keys 7 Call Key Programming 7 Modify a Call Key 8 Delete a Call Key 8 Finishing a...

Page 5: ...Make a Menu Selection 2 Enter the four digit Address 3 Select the Channel 4 Press the Send button The user may select from different command control status or test functions The E 2010 supports up to...

Page 6: ...assigned a unique address In order to accept a command string the remote siren must receive the proper area code and address in the proper order in a certain time span A remote siren will reject any c...

Page 7: ...ons in the Menu Selection portion of the keyboard The wildcard address entry it equals numerical entries 0 through 9 ALL A one button method for entering four signs for selecting all remote siren addr...

Page 8: ...2 MSG 3 Activates Digital Voice Message 3 MSG 4 Activates Digital Voice Message 4 MSG 5 Activates Digital Voice Message 5 MSG 6 Activates Digital Voice Message 6 MSG 7 Activates Digital Voice Message...

Page 9: ...p for the RS 232 communication port and the Printer port The RS 232 port is dedicated to a PC operating Whelen supplied software The parameters are PRINTER ON or OFF Use the Left or Right arrow to tog...

Page 10: ...AUDIO Audio output control Use the Up or Down arrows to move through the choices The following functions are set in this section Speaker The speaker may be Off or set to Radio Channel 1 or 2 The spea...

Page 11: ...remote inputs These are described in another section Call Key 61 and Call Key 62 are available as Time of Day functions These are described in another section A Call Key in progress may be canceled b...

Page 12: ...or Right arrow to toggle the Edit Mode to ON Press ENTER A new programming screen will appear as shown The cursor is at the command prompt Use the Down arrow to scroll the cursor around to the Sequenc...

Page 13: ...a Call Key To Finish use the Down arrow to scroll through to the EDIT option Use the Left or Right arrow to select Finish and press ENTER PRINTING AN INDIVIDUAL CALL KEY Call Keys may be printed indiv...

Page 14: ...Cancel 49 Voice Message 1 09 North 15 Silent Test 01 Wail 50 Voice Message 2 10 East 63 Active Status 02 Attack 51 Voice Message 3 11 South 30 Test Clear 03 Alert 52 Voice Message 4 12 West 57 Strobe...

Page 15: ...keypad as shown Enter the four digit address of the target remote siren The address is entered with the most significant bit first The sign represents a wildcard or all values 0 to 9 ALL is a quick wa...

Page 16: ...8 lines of data This buffer is printed when the printer is reconnected or turned back on The proper way to prevent printing is to select printer Off through the Port Setup function in Menu Selections...

Page 17: ...e If desired the E 2010 can interface with a personal computer IBM compatible running Windows 95 through an RS 232 Serial Communication port Software is included to allow for the following Storing dat...

Page 18: ...only Pin Signal 1 Push To Talk Output 2 Push To Talk Output 3 Audio Out Output 4 Audio Out Output 5 Squelch In Input 6 Ground 7 Channel Grant Input 8 Audio In Input 9 Audio In Input 10 Ground 4 Make a...

Page 19: ...010 on Send the CANCEL Command to siren address 0001 While the tone is transmitting adjust the level potentiometer for 2 5 KHz deviation Repeat this step as needed to adjust the level Repeat for Chann...

Page 20: ...ot maintain time SOLUTION Check AC power and DC power pack connection Security switch is off Area code is still at 000 must be set Transmitter warm up is still 0 0 must be set to a value other than 0...

Page 21: ...C Humidity 0 95 non condensing Audio 2 wire 600 transformer balanced adjustable Control Normally open relay for Push To Talk Contact rating 1 2 A 120 VAC 1 A 24 VDC Signaling DTMF format 2 of 8 Whele...