76-5023-05 Page 19 of 20
Built-in fixed timers
Timer function
Time
Delay in compressors start due to power failure
3 min
Compressor restart delay due to temperature change, set point, etc.
3 min
Phase shifted between compressors
5 sec
Return to the temperature display from an inactive display
1 min
Disabling the input of the access code due to repeated erroneous entry (3 times)
1 min
Alarm Identification
Message on the Display
Identification
Action
ALT
High Temperature Alarm
The display shows
ALT
and the room
temperature alternately.
The sequencer beeps
NORMAL LED goes out
The failure dry contact closes
STE
Temperature Sensor Failure Alarm
The display flashes showing
STE
The sequencer beeps
NORMAL LED goes out
All unit control outputs opens
The failure dry contact closes
BTE
Power Supply Failure Alarm
(Low voltage)
The display flashes showing
BTE
The sequencer beeps
NORMAL LED goes out
All unit control outputs opens
The failure dry contact closes
FE1,FE2
Unit Failure stop alarm (Digital
input)
The display flashes showing
FE1,
FE2
(unit 1 or 2).
The sequencer beeps
NORMAL LED goes out
All unit control outputs opens
The failure dry contact closes
FF
Emergency Stop Alarm
(Fire, phase failure, etc.)
The display flashes showing
FF
The sequencer beeps
NORMAL LED goes out
All unit control outputs opens
The failure dry contact closes