Displaying and adjusting parameters flowchart
Parameter Description
Range
Minimum
Maximum
Factory
t2
Cycling time in days
1 day
7 days
1 day
t1
High temperature alarm delay
0 min
60 min
0 min
F
High temperature alarm set point
C2 + 1ºC
31º.
31ºC
29ºC
C2
Backup unit compressor start setpoint
(2nd refrigeration stage)
C1 + 1ºC
30ºC
25ºC
C1
Head unit compressor start setpoint
(1st refrigeration stage)
21ºC
29ºC
23ºC
r
Heating set point
10ºC
C1-1ºC
14ºC
Cod
Access code for parameter change
000
255
000