16
Installation and commissioning
704 67 020 00 _ 111
GF Robimat XL / XM
OPERATING INSTRUCTIONS
3 Installation and commissioning
3.1 Choosing the location
When you choose the location for the machine please observe the following criteria:
•
The machine may not be installed outdoors (except for Outdoor-machines and High-
Security-Variants located under a canopy).
•
Check that the ambient temperature is in accordance with the climate class of the chiller
unit!
•
The machine must not be installed in air containing salt or chlorine, such as an indoor
swimming pool.
•
In adverse weather conditions (high humidity, high outdoor temperature) the front panels on the machine may mist
up. This is a temporary occurrence and not grounds for complaint.
•
The front window of the machine must not be exposed to direct sunlight. The chiller unit is not designed for this.
•
Do not install the machine in places where water hoses or a high-pressure cleaner is used.
•
The floor must have an adequate load bearing capacity. Observe the weight.
•
Make sure that the machine is level.
3.2 Distances
A distance of 5 cm at the back of the machine must be observed. The warm
air from the chiller unit must be able to discharge.
Additional machines can be placed either side of the machine.
There must be enough space in front of the door for opening.
3.3 Suction protection
•
In order to avoid the machine taking in the hot air, which has already
been discharged, suction protection must be attached to the rear of the
machine. It must be fitted so that it is flush with the ground!
•
Avoid thermal short circuit!
•
Suction protection is not required if the machine is fitted with a rear
advertising panel.
Suction protection
204 cm (M
odell XL)
40 cm
90°
114 cm (Modell XL)
5 cm
99 cm (Modell XM)