48
WHL-060 REV. 1.6.16
Table 24
– Status Mode Display Screen Descriptions
Turn the dial
counterclockwise and clockwise to scroll through the displayed parameters. To view parameter details, press the
button at the appropriate screen. Press the
or
buttons to leave the parameter.
Press the
button again to return to Operation Mode.
G. RECIRCULATION MODES
The following section details the various Recirculation Mode functions.
NOTE:
When Recirculation Mode is active and there is no hot water demand, DHW temperature is limited to 125
o
F (51
o
C). This is
intended to decrease the risk of scalding. The water heater will heat water to temperatures greater than 125
o
F (51
o
C) if the DHW set-
point is higher than 125
o
F (51
o
C) and there is a demand for hot water.
Hotter water increases the risk of scald injury. Scalding may occur within 5 seconds at a setting of 140
o
F (60
o
C). Water temperature
over 125
o
F can instantly cause severe burns, or death, from scalds. Children, disabled, and elderly are at the highest risk of being
scalded. See instruction manual before setting temperature at appliance. Feel water before bathing or showering!
NOTE:
In all Recirculation Modes but Pulse Mode: When Recirculation Mode is operational and the burner turns off, the pump will
continue to run for seven (7) minutes and stop for three (3) minutes. This cycle will repeat until the burner turns on or the recirculation
timer ends.
Display
(Main Menu)
Display
(Sub Menu)
Detail
Description
A: GA or A:LI
Flow Unit
Current Flow Unit (Li: Liters/min, GA: Gallons/min)
b: dH
DHW outlet water temperature
Current DHW outlet water temperature
C: In
DHW inlet water temperature
Current DHW inlet water temperature
d: Rt
Recirculation return water temperature
Current recirculation return water temperature
E: oP
Heat exchanger outlet water temperature
Current heat exchanger outlet water temperature
F: Eh
Exhaust temperature
Current exhaust temperature
H : oH
Overheat water temperature (HX)
Current overheat water temperature (HX)
I: Fr
FAN speed (RPM)
Current FAN speed (RPM)
L: rt
1: PH
Operation Time
Power Supply
L: rt on display on
sub menu
Time water heater has been powered in
1000 hour units
2: rh
Burner Operating Time
Time burner has operated in 1 hour
units
3: rH
Burner Operating Time
Time burner has operated in 1000 hour
units
4: It
Ignition Attempts
Number of ignition attempts: 10 times
the displayed unit
5: IH
Ignition Attempts
Number of ignition attempts: 10,000
times the displayed unit
M: CC
SELF
Percentage of self units running
N/A
ALL
Capacity for all operating cascade units
N/A
F1
– F 19
Capacity for individual
water heaters
N/A
N: TS
Auto
PULS
Default Recirculation Mode
See Table 25 for Recirculation Mode details.
NOTE:
Before setting the Recirculation Mode, go into the
Installer Mode and change
0: RC
from
oFF
to
InRC
(Internal
Recirculation Operation) or
EtRC
(External Recirculation
Operation ). Recirculation Mode will not work if this Operation
is not activated. See Table 27 to for Internal and External
Recirculation Operation details.
Pro1
04-9:30,
16-21:30
Recirculation Mode Program 1 (adjustable)
Pro2
06-7:30
18-19:30
Recirculation Mode Program 2 (adjustable)
Pro3
-
User Custom Settings
PULS
10
Recirculation Pulse Mode