Maximum Natural Gas Delivery Capacity
– Length of Black Iron Pipe (Sch. 40 Metallic) in Feet
Pipe Size
Cubic Feet per Hour (0.60 Specific Gravity, 0.5 WC Pressure Drop)
10
20
30
40
50
60
80
100
150
200
½”
172
118
95
81
72
65
56
50
40
34
¾”
360
247
199
170
151
137
117
104
83
71
1”
678
466
374
320
284
257
220
195
157
134
1 ¼”
1390
957
768
657
583
528
452
400
322
275
1 ½”
2090
1430
1150
985
873
791
677
600
482
412
2”
4020
2760
2220
1900
1680
1520
1300
1160
928
794
Table 14
– Natural Gas Delivery Capacity – Black Iron Pipe – Refer to ANSI Z223.1 – National Fuel Gas Code, Latest Edition
3. LP (Liquid Propane) Gas Pipe Sizing
The following is intended for use for piping between a Single or Second Stage (Low Pressure) Regulator and the water heater. The
following tables list maximum capacity of pipe in cubic feet of gas per hour for an inlet pressure of 11 inches water column and specific
pressure drop of 0.5 inches water column based on 1.5 specific gravity for liquid propane.
Maximum Liquid Propane Delivery Capacity
– Length of Corrugated Stainless Steel Pipe in Feet
Pipe Size
Cubic Feet per Hour (0.60 Specific Gravity, 0.5 WC Pressure Drop)
10
20
30
40
50
60
80
100
150
200
½”
129
91
74
64
58
53
45
41
31
28
¾”
303
216
177
153
137
126
109
98
75
69
1”
605
425
344
297
265
241
208
186
143
129
1 ¼”
971
661
528
449
397
359
307
270
217
183
1 ½”
1990
1400
1140
988
884
805
696
621
506
438
2”
4640
3290
2680
2330
2080
1900
1650
1480
1210
1050
Table 15
– Liquid Propane Delivery Capacity – Corrugated Stainless Steel Pipe – Refer to ANSI Z223.1 – National Fuel Gas
Code, Latest Edition
Maximum Liquid Propane Delivery Capacity
– Length of Black Iron Pipe (Sch. 40 Metallic) in Feet
Pipe Size
Cubic Feet per Hour (0.60 Specific Gravity, 0.5 WC Pressure Drop)
10
20
30
40
50
60
80
100
150
200
½”
291
200
160
137
122
110
101
94
84
67
¾”
608
418
336
287
255
231
212
197
175
140
1”
1150
787
632
541
480
434
400
372
330
265
1 ¼”
2350
1620
1300
1110
985
892
821
763
677
543
1 ½”
3520
2420
1940
1660
1480
1340
1230
1140
1010
814
2”
6790
4660
3750
3210
2840
2570
2370
2200
1950
1570
Table 16
– Liquid Propane Delivery Capacity – Black Iron Pipe – Refer to ANSI Z223.1 – National Fuel Gas Code, Latest Edition
B. GAS CONNECTION REQUIREMENTS
1. The gas connection fitting on the water heater
is ¾” female NPT.
NOTE:
The p
ipe size must not be less than ¾”.
2. The supply line must be sized for the maximum output of the water heater being installed. If there are additional gas appliances from
the main supply line, measure the size of the supply line according to the COMBINED total maximum BTUH draw for the appliances as
if they were operating at the same time.
3. Measure the length of the gas supply line from the gas meter to the water heater. Water heater must be installed downstream of the
gas meter to ensure adequate gas supply. Use the tables
in this manual or refer to the gas line manufacturer’s sizing information to
determine the correct supply pipe size.
4. A manual gas shut-off valve should be installed in the gas supply line close to the water heater. See Figure 15 for detail.
5. To facilitate any future maintenance, it is also recommended that an approved gas union fitting be installed in the supply line between
the shut-off valv
e and the ¾” female NPT connection on the water heater.