TYP E
S E T T I N G S
P h a s e O v e rc u r r e n t U n i t ( 1 1
& l3 )
The pickup current setting is made by means of
the connecto r screw lo cated on the tap plate. By
placing the connector screw in the de sired tap , the
relay will just close its contacts at the tap value
current.
C AU T 10 N
Since the tap block connector screw carries
operating current, be sure that the ·screw is turned
tight.
In order to avoid opening the current transformer
circuits when changing tap s under lo ad , connect the
spare tap screw in the de sired tap position before
removing the ot her tap screw from the original tap
position.
G ro un d O v e rc urrent U n i t ( I a )
The core screw must be adjusted to the v alue of
pickup current desired.
A u x i l i a ry R e l a y
( X)
With the 1 25/ 250 volt relays the tapped resistor
in series with the auxiliary relay
( X)
is shipped from
the factory for operation on 1 25 volts d . c . For 250
volt operation move the lead connection from th e tap
position to the full resistanc e connection. The re
sistor in the 48 volt relay is not tapped.
I n d i c a t i n g C o n t a c to r S w i t c h ( I C S - 1 and I C S - 2)
Connect the lead lo cated in front of the tap block
to the de sired setting by means of the connecting
screw. When the relay e nergize s a 1 25-or 250-volt
d-e type WL relay switch or equivalent, use the 0. 2
ampere tap ; fo� 48-volt d-e applications set in 2 tap
and use WL c oil Stt304C 209GO 1 .
I N S T A L L A T I O N
The relays should be mounted o n switchboard
panels or t heir equivalent in a location free from
dirt , moisture , excessive vibration, and heat . Mount
the relay vertically by means of the four mounting
holes on the flang e for semi-flush mounting or by
means of the rear mounting stud or studs for projec
tion mounting. Either a mounting stud or the mounting
screws may be utilized for grounding the relay. The
electrical connections may b e made directly to the
terminals by means of screws for steel p anel mount
ing or the terminal studs furnished with the relay for
thick panel mounting. The t ermin al studs may be
e asily removed or inserted by locking two nuts on
the stud and then turning the proper nut with a wrench.
For detailed information, refer to I . L . 4 1-076 .
A D J U S T M E N T S A N D M A I N T E N A N C E
The proper adjustments to insure correct opera
tion of this relay have been made at the factory. Upon
receipt of the rel ay, no customer adj ustments, other
than those covered under "SETTINGS, " should be
required.
A c c e p t a n c e C h e c k
The following check is recommended to insure
that the relay is in proper working order:
Phase Overcurrent Unit 0 1
&
I3)
1. Contact Gap - The gap b etween the station
ary and moving contacts with the relay in the de
energized po sition should be approximately . 0 20. "
2. Minimum Trip Current - The pick-up of the
overcurrent unit can be checked by inserting the tap
screw in the de sired tap hole and applying rated tap
value current. The contact should close within
±
5%
of tap value current.
Ground Overcurrent Unit ( I0)
The core screw which is adj ustable from the top
of the trip unit determines the pickup value. The trip
unit has a nominal r atio of adjustment of 1 to 4 and
an accuracy within the limits of 10%.
The contact gap should be approximately 5/64"
between the bridging moving contact and the adj ust
able stationary contacts. The bridging moving contact
should touch both stationary contacts simultaneously.
Indicating Contactor Switch ( ICS- 1 and ICS-2)
Close the auxiliary telephone relay contacts and
p ass sufficient d-e current through the trip circuit to
close the contacts of the ICS. This v alue of current
should not be greater than the particular
res
tap set
ting being used. The i ndicator target should drop
freely.
The contact g ap should be approximately . 047"
between the bridging m oving contact and the adjust
able stationary contacts. The bridging moving contact
should touch both stationary contacts simultaneously.
1 1
www
. ElectricalPartManuals
. com
Summary of Contents for KC-4
Page 2: ...TYP E K C 4 R ELA Y 2 ai 0 lJ w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 22: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 23: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 39: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 63: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 66: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 84: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 86: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 113: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 148: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 149: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 176: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 177: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...