![Westinghouse KC-4 Installation, Operation & Maintenance Instructions Manual Download Page 6](http://html.mh-extra.com/html/westinghouse/kc-4/kc-4_installation-operation-and-maintenance-instructions-manual_965511006.webp)
T Y P E
breakers on the bus.
The TRB-1 rectifier in the primary - protection
circuits of Fig. 4 blocks the flow of red-light super
vision current through the 62X coil.
An MG-6 relay performs the 62X function in Fig.
4. Actually an S G will suffice unless a directional
comparison blocking system provides the primary
protection. With this system two MG-6 contacts seal
around the RRG and RRP contacts. (Refer to drawing
540054 2 for the details of this arrangeme nt. )
Breaker-and-a-Half Arrangement
Typical trip and control circuits for breaker
failure back-up protection for the breaker-and-a-half
bus arrangement are shown in Fig. 5. The trip cir
circuits for line A and bus L are shown . Similar cir
cuits would exist for breaker
3 .
line B and bus R.
cuits would exist for breaker
3.
line B and bus R.
Protection against break er 2 failure for line A faults
and breaker 1 failure for line A or bus L faults is
discussed below. All other breaker failure fault com
binations are equivalent to one of these three
combinations . For example, protection against a
breaker
3
failure for bus R faults is similar to the
protection against a breaker 1 failure for bus L faults.
Assuming a failure of breaker 2 for a fault
on line A, the breaker-failure timer 6 2 associated
with breaker 2 is energized by 62X or 62Y from
line A. Since the KC-4 current detector 50-2 which
is supplied by breaker 2 current does not
drop out, 62 of breaker 2 operates 86LN of
br eaker 2. One 86LN contact trip s break e r
3 .
Another 86LN contact stops the transmission of a
blocking signal on line B. allowing the remote pilot
relays to trip the remote line B breaker. if they de
tect the fault. Thus, the fault on line A is now
cleared. Another 86LN contact blocks high-sp eed re
closing of breaker
3.
Note that the timer is associa
ted with the middle breaker. which is the breaker
that has failed. The timer causes tripping of both
outside breakers , which is the same approach used
for ring bus protection, to be described later.
An essential function, the selection of the faulty
breaker, is performed by the KC-4 . Relays 6 2X and
and 62Y indicate that the fault has not been cleared.
but they are unable to define for a line A fault
whether breaker
1
or breaker 2 is still feeding current
to the fault. The 50-1 or 50-2 KC-4 performs this
job.
If breaker 1 fails for a fault on line A, bus
L
is
cleared. This is accomplished by the bus L breaker
failure timer which is energized by the line A relay
6
detector 50-1 selects the faulty breaker. Note that
the line A part of the bus L timer circuit in Fig. 5
is the same as that used with the single bus/ single
breaker arrangement in Fig . 4
If breaker 1 fails for a fault on bus L it is de
sirable to trip breaker 2 and stop the transmission
of blocking carrier on line A. This is accomplished
.by the 86Z device which is energized through 62ZL.
50-1 and 6 2L contacts and a six ohm resistor. as
shown in Fig. 5. One 86Z contact trips breaker 2.
Other 86Z contacts stop blocking carrier on line A
and block reclosing of breaker 2. The six ohm re
sistor and the 86Z coil are both low impedance
compared to the 62L circuit re sistance. Therefor e,
the 86Z coil will not affect the 6 2L timing, and the
62L timing circuit current will not be enough to pick
up the 86Z device. The six ohm circuit maintains
approximately half-voltage on the 62L device after
the timing is completed. The purpose of this seem
ingly involved circuitry is to permit a single current
detector. device 50-1, to supervise 62L timing ,
86BL tripping and 86Z tripping.
Ri n g B us A rra n g e m e n t
The circuits for the ring bus are shown i n Fig. 6
with trip and control circuits outlined for breaker 2.
together with line-B primary and back-up protection
circuits. As with the breaker-and-a-half scheme. the
primary protection uses tripping rectifiers, and the
backup us es an auxiliary relay to trip two breakers.
As before, the 6 2X and 62Y relays are operated by
the primary and back-up relays , respectively .
Assume a failure of breaker 2 for a fault on line
B. Line-B relay 62X or 62Y is operated and energizes
breaker-2 timer . Since current detector 50 for breaker
2 remains energized by the breaker-2 current. 62
operates to energize relay 86LN. Relay 86LN trips
breakers 1 and
3 ,
blocks reclosing on breakers 1 , 2,
and
3 ,
and stops carrier on lines A and B. The trip
ping of breaker
3
.and the stopping of carrier of line
B is unnecessary. since it is assumed that the pro
tective relays have already accomplished these
results. Although unnecessary, these functions do no
harm and simplify the circuitry by permitting the
86LN relay to trip breakers and stop carrier symmetri
cally, without regard to whether the fault is on line
A or line B.
The purpose of stopping carrier on line A is to
remove carrier blocking to permit remote carrier relay
relay tripping. Otherwise , line A continue s to feed
the fault through breaker 2 until a back-up relay
operates or until the fault burns clear.
www
. ElectricalPartManuals
. com
Summary of Contents for KC-4
Page 2: ...TYP E K C 4 R ELA Y 2 ai 0 lJ w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 22: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 23: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 39: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 63: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 66: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 84: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 86: ... w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 113: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 148: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 149: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 176: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 177: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...