background image

TYP ES  CA- 1 6  AND CA-26 

SOIJICE 

FEEDER 

......._..., 

TO 

BIE.U:EI 

TRIP 
COILS 

DEVICE  IIUNBEII  CIIAiT 

... 

87  - PERCEIHAIE  OlfFEREMTIAL  IEUY,  TYPE  CA•l6 

ICS - IMDICATIIIG  COITACTOfl  SWITCH 

OP  - OPERATUIG  COIL 

{BOTTOM 

L.M.ELEMUl) 

R - PAIREO RESTUIIIT COIL 

(IOTTOM I . I$ . ElENt:Jil) 

S  •  Pot. IRED  RESTUIIT  COIL 

(TOP 

L.M. flEMUr) 

T - PAIIED RESTUIIIT COIL 

(TOP  t.K. ELEMEIIT) 

TTPE 
CA-ll 
t[lAf 

81 - AUlllllln  TIIPP'IIG  IEUT,  TYPE 

wt. 

187A425 

Fig. 

9 .  

External  Schematic  of  the  Type  CA- 1 6   Relays  for 

Protection  of  a  Six  Circuit  Bus  with  Three  Feeder 

Groups 

prim ary  circuit  as  either  a  " source"  or  " feeder " .   As 

defined  here ,  a  feeder  contributes  only  a  small  por­

tion  of  the  total  fault-current  contribution  for  a  bus 
fault .  Otherwis e ,   the  circuit  is  a  source.  Next  lump  a 

number  of  feeders  into  a  "feeder  group"  by  parallel­
ing  feeder  CT ' s,  taking  the  precaution  that  each 
feeder  group  has  less  than  14  amperes  load  c urrent 
(re straint  coil  continuous  rating ).  Also  e ach  feeder 
group  should  not  contribute  more  than 

10% 

of  the 

total  phase  or  ground-fault  current  for  a  bus  fault  if 

figure  9  is  to  be  use d .  

Connect  p e r   Fig.  8  with  three  o r   four  bus  " c ir ­

c uit. "  The  term  "circuit"  refers  t o   a  source  or  t o  a 

feeder  group .  F or  e x ample ,  assume  a  bus c onsisting 
of  2  sources  and  6  feeders.  Further ,  assume  that  the 
feeders are  lumped  into  2  feeder  groups.  The  bus  now 
reduces to  four  circuits . 

If  the  bus  reduces  to  more  than  four  circ uits , 

p arallel source-circ uit CT's  or  source- and  feeder-cir ­
CT' s   until  only  four  circuits  rem ain.  Then  connect 
these  four  sets  of  CT's  to  the  rel ays p er  Fig. 

8. 

The 

exception  to  this  rule  occurs  when  the  application 

consists  of  three feeder  groups. Then,  Fig.  9  applies. 

With 

feeder  group s  and  more  than 

sources, 

p arallel  source  CT' s  until  the  applic ation reduces 
to  6  circuits;  then,  connect  to  the  relays  per Fig. 

9. 

Fig .  1 0   shows  th e  C A-26  relay  conne ctions  for  a 

circuit  bus .  Where  additional  circuits  are  pr esent 

use  the  Fig.  9  connections ;  where  there  are  more 
than  three  sources  the  source  CT's  should  be  par­
alle lled  to  reduce  the  effective  number  of  source  con­
nections  to  three .  The  "four-circuit  bus "  connec­
tions  of  Fig.  8  are  not  recommended  to  be  used  for 

bus  protection  with  the  CA-26  since  it  may  have  too 
much  restraint  when  e nergizing  the  bus  on  fault. 

Otherwise  the  connection  considerations  are  as 

described  above  for  the  C A- 1 6 .  

S E T T I N G 

C A L C U L A T I O N S  

No  calcul ations  are  re quired  to  set  the  CA- 1 6  and 

CA- 26  rel ays. 

S E T T I N G  T H E   R E L A Y  

No  settings  are  required  o n   either  the  CA- 1 6   or 

the CA- 26 main units. 

I nd i c a t i ng  C o nta c t o r   S w i t c h   ( I C S ) 

No  setting  is  required  on  the  ICS  unit  except  the 

selection  of  the  0 . 2   or  2. 0  ampere  tap  setting.  This 

selection  is  made  by  connecting  the  le ad  located  i n  

front  of  the  tap  block to  the desired  setting  by m e ans 
of  the  connecting  screw.  When the relay e nergizes  a 

125  or  250  volt  d-e  WL  relay  switch  o r   e quiva­

lent ,   use the 0 .  2  ampere  tap ;  for  48  volt  d-e  applic a ­
tions  set relay  i n  2  tap  and  use  W L  relay  c oil  Slt304-
C 209G0 1  or  e quivalent. 

I n d i c at i n g   I n s t a n t a n e o u s   T r i p   ( l i T )  

Since  the  minimum  and  maximum  markings  o n  the 

scale  only  indicate  the  working  range  of  the  core 

screw  must  be  adjusted  to  the  value  of p ick-up d e ­
sired.  It  is  recommended  that  the  liT  be  s et  to  pick 

up  at  a  value  of  current  that  is  equal  to  the  max ­

imum  rms  symmetrical  e xternal  fault  current  to the 

relay. 

I N S T A L L A T I O N  

The  relays  should  be  mounted  on  a  switchboard 

p anel  or  their  e quivalent  in  a  location  free  from  dirt , 

moisture ,  excessive  vibration ,   and  heat.  Mount  the 

relay  vertically  by  m eans  of  the  four mounting  hol e s  
on the  flange  for  semi-flush  mounting o r  by  m e an s   of 

the  rear  mounting  stud  or  studs  for  projection mount­

ing.  Either  a  mounting  stud  or  the  mounting  screws 
may  be  utilized  for  grounding  the  relay.  The  elec­

trical  connections  may  be  made  directly  to  the  t er ­

minals  b y   means  of  screws  for  steel p anel mounting 
or  to  the  terminal  studs  furnished  with the relay  fo r 

thick  p anel  mounting.  The  terminal  studs may  be 
easily  removed  or  inserted  by  locking two  nuts on the 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for KAB

Page 1: ...t s is not recommend ed If this cannot be avoided the additional impedance from the auxiliary ct s and the high voltage which transformed by the auxiliary ct should be checked SUPERSEDES I L 41 337 4...

Page 2: ...pring adj uster is also held in place by a spring ty pe clamp With the contacts closed the electrical connec tion is made through the stationary contact housing 2 clamp to the mo ving contact through...

Page 3: ...overstress the insula tion A varistor is connected internally to reduce this voltage Figure 2 shows the electrical char acteristics of this device The overvoltage unit is a high speed device and will...

Page 4: ...ce Rs 0 93 n and one way l ead resistance to junction point RL 1 07D A SETTING OF VOL TAGE UNIT 4 a for 3 phase fault condition Rs t RL _l_r I VK 0 93 1 07 N from Fig 3 K 0 76 60000 l I 375 400 0 9 V...

Page 5: ...g enough to trip a breaker I L 41 337 4A BU R D E N The relay burden is approximately 2600 ohms in the tuned circuit However this burden is not seen by any of the CTS during normal operation or during...

Page 6: ...y be necessary to re adjust the overvoltage unit spring for the desired operate voltage 6 Overvoltage Unit V 1 The upper bearing screw should be screwed down until there is approximately 025 clear anc...

Page 7: ...he voltage should measure 175 volts ac 10 A high resistance voltmeter should be used R E N EWAL PAR T S Repair work can be done most satisfactorily at the factory However interchangeable parts can be...

Page 8: ...vv _ I _ _ _H t 0 0 LO ID t 0 0 0 0 q ci PEAK CURRENT AMPERES Fig 2a Typical Volt Ampere Characteristic of Varistor in Type KAB Relay Peak Value I I I I 0 I I II 349 7A22 Ol 1 c Vl 1J om o mOl O t m z...

Page 9: ...300 200 100 01 o V 0 1 AMPERES RMS Fig 2b Typical Volt Ampere Characteristic of Varistor in Type KAB Relay RMS I I v 10 Curve 619414 OJ l c V om n Tl mOJ O r m zC1 l r r3 l om mo r z r w w m w E l e...

Page 10: ...75 0 50 0 25 10 20 30 40 so 60 70 so 90 1 00 1 10 1 20 1 30 VR MARGIN FACTOR K IRs RLI t Fig 3 Margin Factor for V Unit Setting 1 40 1 50 I CJ j C tl om l I mCJ Oz m zc I j I r om I m e r Z n m 1 60...

Page 11: ...2 3 1 I 4 5 6 8 1 0 IJ I j I J 4U 3U zn I 7 1 J ll J I I I I I R S R L 5 0 I v r vy P As RL 0 75 1 0 1 j J t 1 5 6 7 8 10 15 20 30 40 50 60 70 80 100 IT UNIT SETTING AMPERES AMSl Fig 4 IT Unit Setting...

Page 12: ...L LOCKOUT RELAY 52 BREAKERS NOTE RELAY TERMINALS 8 9 810 SHOULD BE OPEN WHEN CLRCUIT BREAKER OR BREAKERS IS TO BE BYPASSED FOR MAINTENANCE OR WHEN ANY OTHER ABNORMAL SETUP IS TO BE MADE I T y_ I 8 _7_...

Page 13: ...DANCE BUS DlFFE R ENT lA L R ELAY L 4 1 3 _ 3 7 4A Gl t 0 IL Gl 01 0 I L E lz 0 J I 0 0 Gl E 0 0 Gi a 0 c u a N o o 0 Gi co t 0 0 u __ N S3l A 3VIIIl E Nil f 3d0 13 w w w E l e c t r i c a l P a r t M...

Page 14: ...SCIEW II FOR THICK fiAIIEL USE 6 TERNIMAL AIID IQINTING DETAILS li 18 STUD _ 190 32 SCREW FOR THICK PANEL USE 190 32 STUO 3 DIA IO IIOL S Olt CUT OUT J1 e 1 _DIA IJ KOU S flll 2 1 _ 1 110 12 m aaBrl...

Page 15: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 16: ...WESTINGHOUSE ELECTRIC CORPORATION RELAY INSTRUMENT DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 17: ...ed for transformer differential applications since it is too sensitive for overriding the inrush Likewise the CA 26 relay should not be used for bus protection with the four circuit bus connections of...

Page 18: ...T Y P ES CA 1 6 AND CA 26 R ELAYS ________________________ 2 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 19: ...uncing A Micarta disc is fastened to the bottom of the guide rod by 30TT OM RI HT AliD Elf Mfn F V l lkJI ATING ONTACTO SWITCH TOPLHTII 0 LE E T F 1 OTE WITH flATIH I SUN TAN OUS POLA ITI S AS h IIN T...

Page 20: ...I ao Ht 40 f t 0 20 0 60 80 100 120 140 160 OPERATING CURRENT IN AMPERES Curve 537956 Fig 6 Typical Time Curves of the CA 1 6 and CA 26 dif ferential Relays polarity as indicated above their effect w...

Page 21: ...amperes at 250 volts d e and will c arry this current long enough to trip breaker The indicating contactor switch has two tap s that provide a pick up setting of 0 2 or 2 amperes To change taps requi...

Page 22: ...9 connections where there are more than three sources the source CT s should be par allelled to reduce the effective number of source con nections to three The four circuit bus connec tions of Fig 8...

Page 23: ...N D M AI N T E N A N C E The proper adjustments to insure correct operatio n of this relay have been made at the factory Upon receipt of the relay no customer adjustments other than those covered und...

Page 24: ...it has no t arg et F Sens itive F a u lt Detec tor w h ere s upp l ied Apply current to terminals 14 and 15 of the re l ay The fault detector should operate between the limits of 0 14 2 to 0 158 amper...

Page 25: ...t clo se in the following times CA 16 52 5 milliseconds CA 26 72 5 milliseconds These times should be the average of 5 readings 5 lnd icating C o ntactor S w i t c h IC S Close the main relay contacts...

Page 26: ...e operating current to trip the relay for dif ferent restraint current for one restraint element as 1 0 well as for six restraint elements connected in series R E N E W A L P A R T S Rep air work c an...

Page 27: ...RENT CAN EXCEED TWICE TttE EXTERNAL FAUlT CURRENT SET P ICK UP EQUAL TO MAXIMUM EXTERNAL FAULT CURRENT 1 3 A c AUX CURREMT BALAMCE CURRENT TRAitS 87 i9 7 87 87 8 12 PHASE 2 SAME AS PH H o 15 POS r 1 I...

Page 28: ...25 16 q DIA HOLES FOR s ff r 32 Uftn J oo f 4_ PANEL CUTOUT DRI LLIJG FOI SEMI FLUSH MTG PAREL DRI LLIIIG OR CUTOUT FOR PRQJECTJOII MTG FROIIT Y I EW 57 D 7903 6 f Fig 15 Outline and Drilling for the...

Page 29: ...ed i ssue T _ h e CA 6 re lay sho o be u _ til zed for tra s form er differential appllcat iiJ i_ since It IS too se nsitive for overriding the i nrus h _ Likewise the C A 26 relay shoul d not be us e...

Page 30: ...T T YP ES CA 16 AND CA 26 R ELAYS _ ___________ _ _ _ _ _ _ __ _____ i c Ill a u Ill Cl 1 IJ 2 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 31: ...evented from causing contact bouncing A Mic arta disc is fastened to the bottom of the guide rod by BOTTOM R I GHT II I IID ELEMEIH F V IHD ICATIMG CONTA CTOR SWITCH CA U 00 CA 26 TOP LEFT ltAIID ELEM...

Page 32: ...2 CA 6 ll 00 40 20 40 60 80 100 120 160 OPERATING CURRENT IN AMPERES j_ _ _ _ _ _ _ _ _ _ Curve 537956 Fig 6 Typ ical Time Curves of the CA 1 6 and CA 26 dif ferential Relays polarity as indicated abo...

Page 33: ...reaker The indicating instantaneous trip contacts will safely close 30 amperes at 250 volts d e and will carry this current long enough to trip breaker The indicating contactor switch has two taps tha...

Page 34: ...s the source CT s should be par allelled to reduce the effective number of source con nections to three The four circuit bus connec tions of Fig 8 are not recommended to be used for bus protection wit...

Page 35: ...rrect operation of this relay have been made at the factory Upon receipt of the rel ay no customer adjustments other than those covered under SETTINGS should be required Ac ceptance C h ec k The follo...

Page 36: ...y suf ficient current to operate the liT F Sen s i t i ve F au l t D etec to r w here s u pp l ied Apply current to terminals 14 and 15 of the re lay The fault detector should operate between the limi...

Page 37: ...A 26 72 5 milliseconds These times should be the average of 5 readings 5 lnd icating C o n tactor Sw itc h IC S Close the main rela y contacts and pass sufficient d e current through the trip circuit...

Page 38: ...the operating current to trip the relay for dif ferent restraint current for one restraint element as 10 well as for six restraint elements connected in series R E N E W A L P A R T S Rep air work ca...

Page 39: ...SCREW 6 FOR THICK PMIEL USE t 18 STUD r r r I I I I I TEIMIIAL MD MOLI IITIIIG DETAILS TERMIUL MI BE 25 q Oi l IJ HOLES FOI 5 9 ff r I PANEL CUTOUT DRI LLI G FOR SEMI FUJSH MTG PAIEL DRI LLIRG OR CUTO...

Page 40: ...AESTUIIT COI L 6 TOP R H ELEM I CS I I D I CATIRG COlT SW l i T liD liST TRIP 86 AUX TRIPPIRG RELAY TYPE WL t USE WIIERE INTERNAL CURREKT CAM EXCEED TWICE TltE EXTERNAL FAULT CURRENT SET P I CK UP EQ...

Page 41: ...se the two way lead burden CON T E N T S This instruction leaflet plies to the following SUPERSEDES I L 41 337 26 Denotes change from superseded i ssue typ es of relays CA 16 Bus Differential Relay CA...

Page 42: ...TYPES CA 1 6 AND CA 26 R ELAYS 41 1 0 a 0 lJ Ill 41 Q 1 o i i 2 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 43: ...plunger BOTTOM R I GHT HAMO HEMEIIT F V INTERNAL SCHEMATIC I N O I CATIMG COMTACTOR SWITCH 1m ICS CA 16 IC l iT c u l_ TOP LEFT IIAIID ELEMEMT F V NOTE WITH RELATIVE INSTAN TANEOUS POLAR I T I ES AS S...

Page 44: ...14 I6C OPERATING CURRENT IN AMPERES Curve 537956 Fig 6 Typical Time Curves of the CA 1 6 and CA 26 dif ferential Relays rent transformers connected to the bus and the operating circuit is energized i...

Page 45: ...unit when a current transformer is severely satur ated by the d e component of an asymmetrical external fault current T r i p C ir c u it The main contacts will safely close 30 ampere s ElTEIIINAL SCH...

Page 46: ...these four sets of CT s to the rel ays p er Fig 8 The exception to this rule occurs when the application consists of three feeder groups Then Fig 9 applies With 3 feeder group s and more than 3 sourc...

Page 47: ...ench For detailed FT case information refer to L L 4 1 076 A D J U S T M E N T S A N D M Al N T E N A N C E The proper adjustments to insure correct operation of this relay have been made at the facto...

Page 48: ...0 The making of the contacts and target indic ation should occur at approximately the same instant Position the stationary contact for a minimum of 1 3 2 inch wipe The bridging moving contact should t...

Page 49: ...keep er of the permanent magnet until the contacts just clo se in the following times CA 16 52 5 milliseconds CA 26 72 5 milliseconds These times should be the average of 5 readings 5 lnd icating C o...

Page 50: ...relay for dif TEI MIMAL AIID MOUMTIIG DElliLS ferent restraint currents for one restraint element as well as for six restraint elements connected in series R E N E W A L P A R T S Rep air work can be...

Page 51: ...l t USE WHERE I NTERNAL CURRENT CAN EXCEED TlfiCE THE EXTERNAL FAULT CURRENT SET P I CX UP EQUAL TO MAX I EXTERUL FAULT CURRENT A A AUX CURREMT BALAMCE CURRENT TRAU POS I C S AUK CURRENT 2 R S T Ill I...

Page 52: ...WESTIN G H O USE E L E C T R I C C O R P O R ATI O N RELAY INSTRUMENT DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 53: ...N FOUR EQUIVALENT CIRCUITS DC TIME CONSTANT OF 0 6 CYCLES 0 01 Sec OR MORE The same requirements as in A apply How S UPERSEDES I L 41 337 1C Denotes ch ange from superseded i ssue ever consideration m...

Page 54: ...pper type device A magnetic armature to which 2 TOP FKOtH El f 4ENT F INTERNAL SCHEMATIC TOP REAR ELEMENT F Y J J 1NO I CAf l MG COnfACTOR Sifil fCH IMOICATING ICS J I C I l l IMSTAn TArtEO JS TRIP Ai...

Page 55: ...unt of restraining w _J 0 0 w _J 0 0 r 20 I I I l s l i It _ 0 o 20 40 60 80 NET TORQUE IN CENTIMETER GRAMS Curve 235496 Fig 4 Typical Differential Unit Time Curve torque as indicated in Fig 3 Similar...

Page 56: ...rmers will be much greater than would ever be e xpected from a consideration of the usual ratio curves of the current transformers involved CHARACT E RISTICS There are no taps inside the relay case Ta...

Page 57: ...S POs DEV I CE NUMBER CHART PH 1 87 PERCENTAGE D IFFERENTIAL RELAY TYPE CA 6 r r y TO BREAKER TR I P CO I LS NEG _ _ _ _ _ _ _ _ _ _ _ _ ICS I ND I CATING COMTACTOR SWI TCH OP OPERATI NG CO I L R PA I...

Page 58: ...PH 3 87 PERCENTAGE DtFFERENTIAL RELAY TYPE CA 6 ICS I ND I CA T I N G CONTACTOR SWI TCH OP OPERATING COI L R PA I RED RESTRA I NT COI L TOP FRONT ELENENT S PA I RED RESTRA INT CO I L BOTTOM REAR ELEM...

Page 59: ...O I LS 87 PERCENTAGE D I FFERENT IAL RELAY TYPE CA 6 ICS I ND I CAT I NG CONTACTOR SW I TCK OP OPERATING CO I L R PA I RED RESTRA INT CO I L TOP FRONT ELEMENT S PA I RED RESTRA I NT CO I L 80T TOI4 RE...

Page 60: ...SW I TCH OP OPERATINu CO I L R PA I RED R ESTRA INT CO I L TOP FRONT ELEMENT s PA I RED RESTRA I N T CO I L BOTTOM REAR ELEMENT T PA I RED RESTRA I NT CO I L BOTTOM FRONT ELEMENT PH 1 TYPE CA 6 IN TY...

Page 61: ...der that the relay maybe given a higher minimum trip setting as noted under Ad justments and Maintenance TRIP CIRCUIT The main contact will safely close 30 amperes at 250 volts d e and the seal in con...

Page 62: ...ed 5 of the total phase or ground fault cur rent with normal bus connections In paralleling current transformers for the feeder group or groups the load current distribution should be examined to insu...

Page 63: ...rces if there are less than 8 equivalent circuits 3 Avoid pairing the two largest sources 4 If feasible parallel matched current trans formers In case IV with two feeder groups one of the restraint el...

Page 64: ...12 of pick up desired It is recommended that a pickup of 100 amperes be used I N S TA L L A T I O N Th e relays should be mounted o n switchboard panels or their equivalent in a location free from dir...

Page 65: ...ommended for this purpose The use of abrasive material for clean ing contacts is not recommend ed because of the danger of embedding small particles in the face of the soft silver and thus impairing t...

Page 66: ...W FOR T H I C K PA N E L U S 1 90 U STUD T E R M I N A L AN D M O U N T I N G D ETA I LS N OTE ALL OIME N SIONS Ito I N C I IE I t D I A 4 H O L E S O R I S 2 2 MT S C R Ew5 PA N E L C UT O UT D R I L...

Page 67: ...6 Relay Without Case Rear View J Top Rear Operating Element 2 Stationary Contact 3 Moving Contact 4 Control Element 2 Bottom Rear Restraining Element Spring Assembly 5 Bottom Front Restraining Element...

Page 68: ...W E S T I N G H O U S E E L E C T R I C C O R P O R A T I O N R E LAY D E PA RTM E N T N EWA R K N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 69: ...l 337 3A Denotes change from superseded i ssue The CA l relay should not be utilized for transformer differential applications Likewise the O A 26 relay should not be used for bus p rotection with the...

Page 70: ...N Fig 1 Types CA 1 6 Relay front view Fig 2 Typ s CA 1 6 Relay rear view t m n I 0 z 0 n p 0 tl m r E l e c t r i c a l P a r t M a n u a l s c...

Page 71: ...remain s stationary Thus a c vibrations of the plunger are prevented from c ausing contact bouncing A Micarta disc is fastened to the bottom of the guide rod by BOTTOf I RIGHT IIA ND HEMEMT F V TOP L...

Page 72: ...60 80 100 120 140 160 OPERATING CURRENT IN AMPERES Curve 537956 Fig 6 Typical Time Curves of the CA 1 6 and CA 26 dif ferential Relays polarity as indicated above their effect will be addi tive and th...

Page 73: ...stantaneous trip contacts will safely close 30 amperes at 250 volts d e and will carry this current long enough to trip breaker The indic ating contactor switch has two taps that provide a pick up set...

Page 74: ...Fig 9 connections where there are more than three sources the source CT s should be par alleled to reduce the effective number of source con nections to three The four circuit bus connec tions of Fig...

Page 75: ...ion of this relay have been made at the factory Upon receipt of the relay no customer adjustments other than those covered under SETTINGS should be required Ac ceptance C h ec k The following check is...

Page 76: ...RESTRA INT COH IM TOP L EL 11 PE T PAIRED RESTUIIT COI L n 26 TOP R M EL 11 I CS I I D I CATIIG COlT SW I IT IIO liST TR I P 116 AUX TI IPPIIG RELAY TYPE Wl t USE wrtERE IMTEINAL CURRENT CAM EXCEED T...

Page 77: ...AN FOUR EQUIVALENT CIRCUITS DC TIME CONSTANT OF 0 6 CYCLES 0 01 Sec OR MORE The same requirements as in A apply How S UPERSEDES I L 41 337 1C Denotes ch ange from superseded i ssue ever consideration...

Page 78: ...ntact is made thru the spiral spring to the spring adjuster INDICATING CONTACTOR SWITCH UNIT ICS The d e indicating contactor switch is a small clapper type device A magnetic armature to which 2 INTER...

Page 79: ...Curve 235496 Fig 4 Typical Differential Unit Time Curve torque as indicated in Fig 3 Similarly a current of 5 amperes flowing in at termiRal 16 and out of terminal 17 will produce an equal amount of...

Page 80: ...al ratio curves of the current transformers involved CHARACT E RISTICS There are no taps inside the relay case Taps 4 controlling the sensitivity of the relay are incorpor ated in the external current...

Page 81: ...CENTAGE D I FFERENTIAl REl AY TYPE CA 6 r r y TO BREAKER TR I P CO I LS NEG _ ICS I ND I CATI NG COKTACTOR SWI TCH OP OPERATING CO I L R PA I RED RESTRAI NT CO I L TOP FRON T El ENENT S PAI RED RESTRA...

Page 82: ...NUMBER CHART 87 PERCENTAGE DtFFERENTIAL RELAY TYPE CA 6 ICS I ND I CATING CONTACTOR SWI TCH OP OPERATING COI L R PA I RED RESTRA I NT COI L TOP FRONT ELEMENT S PA I RED RESTRA I NT COI L BOTTOM REAR...

Page 83: ...ER TRIP COILS 87 PERCENTAGE DIFFERENTIAL RELAY TYPE CA 6 ICS INDICATING CONTACTOR S ITCii OP OPERATING COIL R PAIRED RESTRAINT COIL TOP FRONT ELEMENT S PAIRED RESTRAINT COIL BOTTOM REAR ELEMENT T PAIR...

Page 84: ...R SW I TCH OP OPERA T I N G CO I L R PA I RED R ESTRA I N T CO I L TOP FRONT ELEMENT S PA I RED RESTRA I N T CO I L BOTTOM REAR ELEMENT T PA I RED RESTRA I N T CO I L BOTTOM FRONT ELEMENT lM TYPE CA 6...

Page 85: ...t the relay maybe given a higher minimum trip setting as noted under Ad justments and Maintenance TRIP CIRCUIT The main contactE will safely close 30 amperes at 250 volts d e and the seal in contacts...

Page 86: ...eed 5 of the total phase or ground fault cur rent with normal bus connections In paralleling current transformers for the feeder group or groups the load current distribution should be examined to ins...

Page 87: ...there are less than 8 equivalent circuits 3 Avoid pairing the two largest sources 4 If feasible parallel matched current trans formers In case IV with two feeder groups one of the restraint elements...

Page 88: ...12 of pick up desired It is recommended that a pickup of 100 amperes be used I N S T A L L AT I O N The relays should be mounted on switchboard panels or their equivalent in a location free from dirt...

Page 89: ...commended for this purpose The use of abrasive material for clean ing contacts is not recommend ed because of the danger of embedding small particl es in the face of the soft silver and thus impairing...

Page 90: ...I C K PA N E L U S 1 90 32 5TUD T E R M I N AL i _ N D 1 0 U NT I N C D ETA I LS NOTE Al L DIME N SIONS IH I N C I E t D I A 1 H O L E S FOR 1 s MTE S C R Ew S PA N E L C Ut O UT DR I L L tNC1 F O R S...

Page 91: ...y Without Case Rear Vie Element 2 Stationary Contact 3 Moving Contact 4 Control Spring A ssembly 5 Bottom Front Restraining Element 6 Indicating Contactor Switch ICS E lement 2 Bottom Rear Restra in i...

Page 92: ...WEST I NGHOUSE ELECTRIC CORPORATION RELAY INSTRUMENT DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Reviews: