background image

TYPE  KAB  HIGH  IMP EDAN C E  
B U S  DIFFE R E NTIAL  R E L AY 

O P E R AT I ON 

The  relay  is  connected  as  shown  in  external 

connection  figure 

5. 

In  normal  operation  the  voltage 

at  the  relay  terminals  is  approximately  zero.  In 
the  case  of  an  external  fault,  the  ct  in  the  faulted 

feeder  will  produce  a  secondary  voltage  necessary 
to  force  the  total  secondary  fault  current  through 
its  windings.  Neglecting  the  effect  of  load  current, 
the  unfaulted  ct's  will  produce  no  secondary  voltage. 

If  both  the  source  ct's  and  the  faulted  feeder  ct's 
are  not  saturated,  the  voltage  at  the  relay  remains 

approximately  zero. 

However, during  severe  external  faults  the  feeder 

ct  may  saturate.  The  source  ct's  would  then,  have 
to  produce  enough  voltage  to  force  their  currents, 
through  their  own  windings  and  through  the  winding 
and  leads  of  the  faulted  ct.  In  this  case  a  voltage 
would  appear  across  the  junction  point  equal  to 
the  total  secondary  currents  of  the  source  ct's 
multiplied  by  the  resistance  of  the  faulted  ct 
secondary  winding  plus  its  leads  to  the  junction 
point.  The  relay  is  usually  set  to  operate  at  some 

voltage  higher  than  the  anticipated  voltage  expected 
for  this  condition.  This  faint  voltage  will  be  lower 
than  the  calculated  voltage  since  the  fault  ct  will 
always  produce  some  voltage  and  also  the  source 
ct  will  tend  to  saturate.  The  de  offset  component 

of  this  voltage  does  not  affect  the  relay  operation 

by  reason  of  the  series  tuned  circuit  as  well  as  the 

insensitivity  of  the  voltage  unit  to  de. 

In  the  case  of  an  internal  fault,  the  feeder  ct's 

have  in  effect  open  circuited  primaries  and  therefore 

secondary  impedances  equal  to  the  magnetizing 
impedance  which  is  high.  The  source  ct 's  will 
produce  high  voltages  to  drive  the  fault  current 

through 

the 

fe eder 

ct  secondaries. 

This  high 

voltage  will  appear  at  the  relay  terminals  and  will 

be  well  above  the  pickup  setting. 

During  severe  internal  faults  the  source  ct 

will  saturate  to  limit  the  RMS  value  of  secondary 

voltage.  However,  the  peak  voltages  of  the  wave 

form  could  be  quite  high  and  overstress  the  insula­

tion.  A  varistor  is  connected  internally  to  reduce 
this  voltage.  Figure  2  shows  the  electrical  char­

acteristics  of  this device. 

The  overvoltage  unit  is  a  high  speed  device 

and  will  operate  in 

cycles  at  twice  pickup  using 

a  sine  wave  test  voltage.  Under  fault  condition,  the 
crest  voltage  is  rather  high  for  the  first  few  cycles, 

the  operating  speed  of  the  V-unit  would  be  faster, 

Figure 

shows  the  operating  speed  of  1. 

cycles 

I.L. 

41-337.4A 

from  the  typical  staged  faults.  However,  an  over­
current  unit  is  provided  which  may  be  connected 
in  series  with  the  varistor  and  will  operate  on 
current  flow  during  severe  internal  faults  when  the 
varistor  conducts  current  to  limit  the  secondary 
voltage.  The  application  of  overcurrent  unit  has  no 

effect  on  the  operating  speed  of  the  voltage  unit. 

C HARAC T E R I S T I C S  

Overvoltage  Unit  (V) 

The  range  of  pickup  of  the  overvoltage  unit  is 

adjustable  from 

75 

to 300  volts. The  pickup  is  obtain­

ed  by  means  of  adjusting  the  spring  windup. 

Speed  of  operation  is  2  cycles  at  twice  pickup. 

(sine  wave  test  voltage). 

Over current  Unit  (IT) 

The  range  of  the  overcurrent  unit  is  3  to 

48 

am­

peres .  A  tap  is  used  to  obtain  this  by  use  of  two 
settings  (Hi  and  Lo ).  The  Lo  setting  permits  the 
core  screw  to  be  adjusted  over  a  3  to 

12 

ampere 

range.  The  Hi  setting  permits  a  12  to 

48 

ampere 

range  of  adjustment.  The  scale  plate  is  calibrated 
in  multiples  of  minimum  pickup.  The  pickup  should 

be  within 

± 

10%  of  the  setting. 

Indicating  Contactor  Switch (ICS) 

The  indicating  contactor  switch  has  two  taps 

that  provide  a  pickup setting  of  0.2 or 

amperes.  To 

change  taps  requires  connecting  the  lead  located  in 

front  of  the  tap block  to  the  desired  setting  by  means 

of  a  screw  connection. 

Trip  Circuit  Constants 

Contactor  Switch-

0. 2  ampere  tap 

6 . 5  

ohms  d-e· resistance 

2.0 

ampere  tap 

0.15 

ohms  d-e  re sistance 

* S ET T I NG  C A L C U LAT I O N S 

1 .  

SETTING  VOLTAGE  UNIT 
The  setting  of  the  voltage  unit  can  be  expressed 

as  follows: 

IF 

VR 

CRs 

RL)  -

where  VR  =pick  up  setting  of  the  V-unit,  (RMS, 

volts.) 

Rs 

de  resistance  of  ct  secondary  wind­
ing,  including  internal  leads  to  bush­

ing  terminals. 

RL 

resistance  of  lead  from  junction 
points  to  the  most  distance  ct.  (One-

www 

. ElectricalPartManuals 

. com 

Summary of Contents for KAB

Page 1: ...t s is not recommend ed If this cannot be avoided the additional impedance from the auxiliary ct s and the high voltage which transformed by the auxiliary ct should be checked SUPERSEDES I L 41 337 4...

Page 2: ...pring adj uster is also held in place by a spring ty pe clamp With the contacts closed the electrical connec tion is made through the stationary contact housing 2 clamp to the mo ving contact through...

Page 3: ...overstress the insula tion A varistor is connected internally to reduce this voltage Figure 2 shows the electrical char acteristics of this device The overvoltage unit is a high speed device and will...

Page 4: ...ce Rs 0 93 n and one way l ead resistance to junction point RL 1 07D A SETTING OF VOL TAGE UNIT 4 a for 3 phase fault condition Rs t RL _l_r I VK 0 93 1 07 N from Fig 3 K 0 76 60000 l I 375 400 0 9 V...

Page 5: ...g enough to trip a breaker I L 41 337 4A BU R D E N The relay burden is approximately 2600 ohms in the tuned circuit However this burden is not seen by any of the CTS during normal operation or during...

Page 6: ...y be necessary to re adjust the overvoltage unit spring for the desired operate voltage 6 Overvoltage Unit V 1 The upper bearing screw should be screwed down until there is approximately 025 clear anc...

Page 7: ...he voltage should measure 175 volts ac 10 A high resistance voltmeter should be used R E N EWAL PAR T S Repair work can be done most satisfactorily at the factory However interchangeable parts can be...

Page 8: ...vv _ I _ _ _H t 0 0 LO ID t 0 0 0 0 q ci PEAK CURRENT AMPERES Fig 2a Typical Volt Ampere Characteristic of Varistor in Type KAB Relay Peak Value I I I I 0 I I II 349 7A22 Ol 1 c Vl 1J om o mOl O t m z...

Page 9: ...300 200 100 01 o V 0 1 AMPERES RMS Fig 2b Typical Volt Ampere Characteristic of Varistor in Type KAB Relay RMS I I v 10 Curve 619414 OJ l c V om n Tl mOJ O r m zC1 l r r3 l om mo r z r w w m w E l e...

Page 10: ...75 0 50 0 25 10 20 30 40 so 60 70 so 90 1 00 1 10 1 20 1 30 VR MARGIN FACTOR K IRs RLI t Fig 3 Margin Factor for V Unit Setting 1 40 1 50 I CJ j C tl om l I mCJ Oz m zc I j I r om I m e r Z n m 1 60...

Page 11: ...2 3 1 I 4 5 6 8 1 0 IJ I j I J 4U 3U zn I 7 1 J ll J I I I I I R S R L 5 0 I v r vy P As RL 0 75 1 0 1 j J t 1 5 6 7 8 10 15 20 30 40 50 60 70 80 100 IT UNIT SETTING AMPERES AMSl Fig 4 IT Unit Setting...

Page 12: ...L LOCKOUT RELAY 52 BREAKERS NOTE RELAY TERMINALS 8 9 810 SHOULD BE OPEN WHEN CLRCUIT BREAKER OR BREAKERS IS TO BE BYPASSED FOR MAINTENANCE OR WHEN ANY OTHER ABNORMAL SETUP IS TO BE MADE I T y_ I 8 _7_...

Page 13: ...DANCE BUS DlFFE R ENT lA L R ELAY L 4 1 3 _ 3 7 4A Gl t 0 IL Gl 01 0 I L E lz 0 J I 0 0 Gl E 0 0 Gi a 0 c u a N o o 0 Gi co t 0 0 u __ N S3l A 3VIIIl E Nil f 3d0 13 w w w E l e c t r i c a l P a r t M...

Page 14: ...SCIEW II FOR THICK fiAIIEL USE 6 TERNIMAL AIID IQINTING DETAILS li 18 STUD _ 190 32 SCREW FOR THICK PANEL USE 190 32 STUO 3 DIA IO IIOL S Olt CUT OUT J1 e 1 _DIA IJ KOU S flll 2 1 _ 1 110 12 m aaBrl...

Page 15: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 16: ...WESTINGHOUSE ELECTRIC CORPORATION RELAY INSTRUMENT DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 17: ...ed for transformer differential applications since it is too sensitive for overriding the inrush Likewise the CA 26 relay should not be used for bus protection with the four circuit bus connections of...

Page 18: ...T Y P ES CA 1 6 AND CA 26 R ELAYS ________________________ 2 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 19: ...uncing A Micarta disc is fastened to the bottom of the guide rod by 30TT OM RI HT AliD Elf Mfn F V l lkJI ATING ONTACTO SWITCH TOPLHTII 0 LE E T F 1 OTE WITH flATIH I SUN TAN OUS POLA ITI S AS h IIN T...

Page 20: ...I ao Ht 40 f t 0 20 0 60 80 100 120 140 160 OPERATING CURRENT IN AMPERES Curve 537956 Fig 6 Typical Time Curves of the CA 1 6 and CA 26 dif ferential Relays polarity as indicated above their effect w...

Page 21: ...amperes at 250 volts d e and will c arry this current long enough to trip breaker The indicating contactor switch has two tap s that provide a pick up setting of 0 2 or 2 amperes To change taps requi...

Page 22: ...9 connections where there are more than three sources the source CT s should be par allelled to reduce the effective number of source con nections to three The four circuit bus connec tions of Fig 8...

Page 23: ...N D M AI N T E N A N C E The proper adjustments to insure correct operatio n of this relay have been made at the factory Upon receipt of the relay no customer adjustments other than those covered und...

Page 24: ...it has no t arg et F Sens itive F a u lt Detec tor w h ere s upp l ied Apply current to terminals 14 and 15 of the re l ay The fault detector should operate between the limits of 0 14 2 to 0 158 amper...

Page 25: ...t clo se in the following times CA 16 52 5 milliseconds CA 26 72 5 milliseconds These times should be the average of 5 readings 5 lnd icating C o ntactor S w i t c h IC S Close the main relay contacts...

Page 26: ...e operating current to trip the relay for dif ferent restraint current for one restraint element as 1 0 well as for six restraint elements connected in series R E N E W A L P A R T S Rep air work c an...

Page 27: ...RENT CAN EXCEED TWICE TttE EXTERNAL FAUlT CURRENT SET P ICK UP EQUAL TO MAXIMUM EXTERNAL FAULT CURRENT 1 3 A c AUX CURREMT BALAMCE CURRENT TRAitS 87 i9 7 87 87 8 12 PHASE 2 SAME AS PH H o 15 POS r 1 I...

Page 28: ...25 16 q DIA HOLES FOR s ff r 32 Uftn J oo f 4_ PANEL CUTOUT DRI LLIJG FOI SEMI FLUSH MTG PAREL DRI LLIIIG OR CUTOUT FOR PRQJECTJOII MTG FROIIT Y I EW 57 D 7903 6 f Fig 15 Outline and Drilling for the...

Page 29: ...ed i ssue T _ h e CA 6 re lay sho o be u _ til zed for tra s form er differential appllcat iiJ i_ since It IS too se nsitive for overriding the i nrus h _ Likewise the C A 26 relay shoul d not be us e...

Page 30: ...T T YP ES CA 16 AND CA 26 R ELAYS _ ___________ _ _ _ _ _ _ __ _____ i c Ill a u Ill Cl 1 IJ 2 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 31: ...evented from causing contact bouncing A Mic arta disc is fastened to the bottom of the guide rod by BOTTOM R I GHT II I IID ELEMEIH F V IHD ICATIMG CONTA CTOR SWITCH CA U 00 CA 26 TOP LEFT ltAIID ELEM...

Page 32: ...2 CA 6 ll 00 40 20 40 60 80 100 120 160 OPERATING CURRENT IN AMPERES j_ _ _ _ _ _ _ _ _ _ Curve 537956 Fig 6 Typ ical Time Curves of the CA 1 6 and CA 26 dif ferential Relays polarity as indicated abo...

Page 33: ...reaker The indicating instantaneous trip contacts will safely close 30 amperes at 250 volts d e and will carry this current long enough to trip breaker The indicating contactor switch has two taps tha...

Page 34: ...s the source CT s should be par allelled to reduce the effective number of source con nections to three The four circuit bus connec tions of Fig 8 are not recommended to be used for bus protection wit...

Page 35: ...rrect operation of this relay have been made at the factory Upon receipt of the rel ay no customer adjustments other than those covered under SETTINGS should be required Ac ceptance C h ec k The follo...

Page 36: ...y suf ficient current to operate the liT F Sen s i t i ve F au l t D etec to r w here s u pp l ied Apply current to terminals 14 and 15 of the re lay The fault detector should operate between the limi...

Page 37: ...A 26 72 5 milliseconds These times should be the average of 5 readings 5 lnd icating C o n tactor Sw itc h IC S Close the main rela y contacts and pass sufficient d e current through the trip circuit...

Page 38: ...the operating current to trip the relay for dif ferent restraint current for one restraint element as 10 well as for six restraint elements connected in series R E N E W A L P A R T S Rep air work ca...

Page 39: ...SCREW 6 FOR THICK PMIEL USE t 18 STUD r r r I I I I I TEIMIIAL MD MOLI IITIIIG DETAILS TERMIUL MI BE 25 q Oi l IJ HOLES FOI 5 9 ff r I PANEL CUTOUT DRI LLI G FOR SEMI FUJSH MTG PAIEL DRI LLIRG OR CUTO...

Page 40: ...AESTUIIT COI L 6 TOP R H ELEM I CS I I D I CATIRG COlT SW l i T liD liST TRIP 86 AUX TRIPPIRG RELAY TYPE WL t USE WIIERE INTERNAL CURREKT CAM EXCEED TWICE TltE EXTERNAL FAULT CURRENT SET P I CK UP EQ...

Page 41: ...se the two way lead burden CON T E N T S This instruction leaflet plies to the following SUPERSEDES I L 41 337 26 Denotes change from superseded i ssue typ es of relays CA 16 Bus Differential Relay CA...

Page 42: ...TYPES CA 1 6 AND CA 26 R ELAYS 41 1 0 a 0 lJ Ill 41 Q 1 o i i 2 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 43: ...plunger BOTTOM R I GHT HAMO HEMEIIT F V INTERNAL SCHEMATIC I N O I CATIMG COMTACTOR SWITCH 1m ICS CA 16 IC l iT c u l_ TOP LEFT IIAIID ELEMEMT F V NOTE WITH RELATIVE INSTAN TANEOUS POLAR I T I ES AS S...

Page 44: ...14 I6C OPERATING CURRENT IN AMPERES Curve 537956 Fig 6 Typical Time Curves of the CA 1 6 and CA 26 dif ferential Relays rent transformers connected to the bus and the operating circuit is energized i...

Page 45: ...unit when a current transformer is severely satur ated by the d e component of an asymmetrical external fault current T r i p C ir c u it The main contacts will safely close 30 ampere s ElTEIIINAL SCH...

Page 46: ...these four sets of CT s to the rel ays p er Fig 8 The exception to this rule occurs when the application consists of three feeder groups Then Fig 9 applies With 3 feeder group s and more than 3 sourc...

Page 47: ...ench For detailed FT case information refer to L L 4 1 076 A D J U S T M E N T S A N D M Al N T E N A N C E The proper adjustments to insure correct operation of this relay have been made at the facto...

Page 48: ...0 The making of the contacts and target indic ation should occur at approximately the same instant Position the stationary contact for a minimum of 1 3 2 inch wipe The bridging moving contact should t...

Page 49: ...keep er of the permanent magnet until the contacts just clo se in the following times CA 16 52 5 milliseconds CA 26 72 5 milliseconds These times should be the average of 5 readings 5 lnd icating C o...

Page 50: ...relay for dif TEI MIMAL AIID MOUMTIIG DElliLS ferent restraint currents for one restraint element as well as for six restraint elements connected in series R E N E W A L P A R T S Rep air work can be...

Page 51: ...l t USE WHERE I NTERNAL CURRENT CAN EXCEED TlfiCE THE EXTERNAL FAULT CURRENT SET P I CX UP EQUAL TO MAX I EXTERUL FAULT CURRENT A A AUX CURREMT BALAMCE CURRENT TRAU POS I C S AUK CURRENT 2 R S T Ill I...

Page 52: ...WESTIN G H O USE E L E C T R I C C O R P O R ATI O N RELAY INSTRUMENT DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 53: ...N FOUR EQUIVALENT CIRCUITS DC TIME CONSTANT OF 0 6 CYCLES 0 01 Sec OR MORE The same requirements as in A apply How S UPERSEDES I L 41 337 1C Denotes ch ange from superseded i ssue ever consideration m...

Page 54: ...pper type device A magnetic armature to which 2 TOP FKOtH El f 4ENT F INTERNAL SCHEMATIC TOP REAR ELEMENT F Y J J 1NO I CAf l MG COnfACTOR Sifil fCH IMOICATING ICS J I C I l l IMSTAn TArtEO JS TRIP Ai...

Page 55: ...unt of restraining w _J 0 0 w _J 0 0 r 20 I I I l s l i It _ 0 o 20 40 60 80 NET TORQUE IN CENTIMETER GRAMS Curve 235496 Fig 4 Typical Differential Unit Time Curve torque as indicated in Fig 3 Similar...

Page 56: ...rmers will be much greater than would ever be e xpected from a consideration of the usual ratio curves of the current transformers involved CHARACT E RISTICS There are no taps inside the relay case Ta...

Page 57: ...S POs DEV I CE NUMBER CHART PH 1 87 PERCENTAGE D IFFERENTIAL RELAY TYPE CA 6 r r y TO BREAKER TR I P CO I LS NEG _ _ _ _ _ _ _ _ _ _ _ _ ICS I ND I CATING COMTACTOR SWI TCH OP OPERATI NG CO I L R PA I...

Page 58: ...PH 3 87 PERCENTAGE DtFFERENTIAL RELAY TYPE CA 6 ICS I ND I CA T I N G CONTACTOR SWI TCH OP OPERATING COI L R PA I RED RESTRA I NT COI L TOP FRONT ELENENT S PA I RED RESTRA INT CO I L BOTTOM REAR ELEM...

Page 59: ...O I LS 87 PERCENTAGE D I FFERENT IAL RELAY TYPE CA 6 ICS I ND I CAT I NG CONTACTOR SW I TCK OP OPERATING CO I L R PA I RED RESTRA INT CO I L TOP FRONT ELEMENT S PA I RED RESTRA I NT CO I L 80T TOI4 RE...

Page 60: ...SW I TCH OP OPERATINu CO I L R PA I RED R ESTRA INT CO I L TOP FRONT ELEMENT s PA I RED RESTRA I N T CO I L BOTTOM REAR ELEMENT T PA I RED RESTRA I NT CO I L BOTTOM FRONT ELEMENT PH 1 TYPE CA 6 IN TY...

Page 61: ...der that the relay maybe given a higher minimum trip setting as noted under Ad justments and Maintenance TRIP CIRCUIT The main contact will safely close 30 amperes at 250 volts d e and the seal in con...

Page 62: ...ed 5 of the total phase or ground fault cur rent with normal bus connections In paralleling current transformers for the feeder group or groups the load current distribution should be examined to insu...

Page 63: ...rces if there are less than 8 equivalent circuits 3 Avoid pairing the two largest sources 4 If feasible parallel matched current trans formers In case IV with two feeder groups one of the restraint el...

Page 64: ...12 of pick up desired It is recommended that a pickup of 100 amperes be used I N S TA L L A T I O N Th e relays should be mounted o n switchboard panels or their equivalent in a location free from dir...

Page 65: ...ommended for this purpose The use of abrasive material for clean ing contacts is not recommend ed because of the danger of embedding small particles in the face of the soft silver and thus impairing t...

Page 66: ...W FOR T H I C K PA N E L U S 1 90 U STUD T E R M I N A L AN D M O U N T I N G D ETA I LS N OTE ALL OIME N SIONS Ito I N C I IE I t D I A 4 H O L E S O R I S 2 2 MT S C R Ew5 PA N E L C UT O UT D R I L...

Page 67: ...6 Relay Without Case Rear View J Top Rear Operating Element 2 Stationary Contact 3 Moving Contact 4 Control Element 2 Bottom Rear Restraining Element Spring Assembly 5 Bottom Front Restraining Element...

Page 68: ...W E S T I N G H O U S E E L E C T R I C C O R P O R A T I O N R E LAY D E PA RTM E N T N EWA R K N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 69: ...l 337 3A Denotes change from superseded i ssue The CA l relay should not be utilized for transformer differential applications Likewise the O A 26 relay should not be used for bus p rotection with the...

Page 70: ...N Fig 1 Types CA 1 6 Relay front view Fig 2 Typ s CA 1 6 Relay rear view t m n I 0 z 0 n p 0 tl m r E l e c t r i c a l P a r t M a n u a l s c...

Page 71: ...remain s stationary Thus a c vibrations of the plunger are prevented from c ausing contact bouncing A Micarta disc is fastened to the bottom of the guide rod by BOTTOf I RIGHT IIA ND HEMEMT F V TOP L...

Page 72: ...60 80 100 120 140 160 OPERATING CURRENT IN AMPERES Curve 537956 Fig 6 Typical Time Curves of the CA 1 6 and CA 26 dif ferential Relays polarity as indicated above their effect will be addi tive and th...

Page 73: ...stantaneous trip contacts will safely close 30 amperes at 250 volts d e and will carry this current long enough to trip breaker The indic ating contactor switch has two taps that provide a pick up set...

Page 74: ...Fig 9 connections where there are more than three sources the source CT s should be par alleled to reduce the effective number of source con nections to three The four circuit bus connec tions of Fig...

Page 75: ...ion of this relay have been made at the factory Upon receipt of the relay no customer adjustments other than those covered under SETTINGS should be required Ac ceptance C h ec k The following check is...

Page 76: ...RESTRA INT COH IM TOP L EL 11 PE T PAIRED RESTUIIT COI L n 26 TOP R M EL 11 I CS I I D I CATIIG COlT SW I IT IIO liST TR I P 116 AUX TI IPPIIG RELAY TYPE Wl t USE wrtERE IMTEINAL CURRENT CAM EXCEED T...

Page 77: ...AN FOUR EQUIVALENT CIRCUITS DC TIME CONSTANT OF 0 6 CYCLES 0 01 Sec OR MORE The same requirements as in A apply How S UPERSEDES I L 41 337 1C Denotes ch ange from superseded i ssue ever consideration...

Page 78: ...ntact is made thru the spiral spring to the spring adjuster INDICATING CONTACTOR SWITCH UNIT ICS The d e indicating contactor switch is a small clapper type device A magnetic armature to which 2 INTER...

Page 79: ...Curve 235496 Fig 4 Typical Differential Unit Time Curve torque as indicated in Fig 3 Similarly a current of 5 amperes flowing in at termiRal 16 and out of terminal 17 will produce an equal amount of...

Page 80: ...al ratio curves of the current transformers involved CHARACT E RISTICS There are no taps inside the relay case Taps 4 controlling the sensitivity of the relay are incorpor ated in the external current...

Page 81: ...CENTAGE D I FFERENTIAl REl AY TYPE CA 6 r r y TO BREAKER TR I P CO I LS NEG _ ICS I ND I CATI NG COKTACTOR SWI TCH OP OPERATING CO I L R PA I RED RESTRAI NT CO I L TOP FRON T El ENENT S PAI RED RESTRA...

Page 82: ...NUMBER CHART 87 PERCENTAGE DtFFERENTIAL RELAY TYPE CA 6 ICS I ND I CATING CONTACTOR SWI TCH OP OPERATING COI L R PA I RED RESTRA I NT COI L TOP FRONT ELEMENT S PA I RED RESTRA I NT COI L BOTTOM REAR...

Page 83: ...ER TRIP COILS 87 PERCENTAGE DIFFERENTIAL RELAY TYPE CA 6 ICS INDICATING CONTACTOR S ITCii OP OPERATING COIL R PAIRED RESTRAINT COIL TOP FRONT ELEMENT S PAIRED RESTRAINT COIL BOTTOM REAR ELEMENT T PAIR...

Page 84: ...R SW I TCH OP OPERA T I N G CO I L R PA I RED R ESTRA I N T CO I L TOP FRONT ELEMENT S PA I RED RESTRA I N T CO I L BOTTOM REAR ELEMENT T PA I RED RESTRA I N T CO I L BOTTOM FRONT ELEMENT lM TYPE CA 6...

Page 85: ...t the relay maybe given a higher minimum trip setting as noted under Ad justments and Maintenance TRIP CIRCUIT The main contactE will safely close 30 amperes at 250 volts d e and the seal in contacts...

Page 86: ...eed 5 of the total phase or ground fault cur rent with normal bus connections In paralleling current transformers for the feeder group or groups the load current distribution should be examined to ins...

Page 87: ...there are less than 8 equivalent circuits 3 Avoid pairing the two largest sources 4 If feasible parallel matched current trans formers In case IV with two feeder groups one of the restraint elements...

Page 88: ...12 of pick up desired It is recommended that a pickup of 100 amperes be used I N S T A L L AT I O N The relays should be mounted on switchboard panels or their equivalent in a location free from dirt...

Page 89: ...commended for this purpose The use of abrasive material for clean ing contacts is not recommend ed because of the danger of embedding small particl es in the face of the soft silver and thus impairing...

Page 90: ...I C K PA N E L U S 1 90 32 5TUD T E R M I N AL i _ N D 1 0 U NT I N C D ETA I LS NOTE Al L DIME N SIONS IH I N C I E t D I A 1 H O L E S FOR 1 s MTE S C R Ew S PA N E L C Ut O UT DR I L L tNC1 F O R S...

Page 91: ...y Without Case Rear Vie Element 2 Stationary Contact 3 Moving Contact 4 Control Spring A ssembly 5 Bottom Front Restraining Element 6 Indicating Contactor Switch ICS E lement 2 Bottom Rear Restra in i...

Page 92: ...WEST I NGHOUSE ELECTRIC CORPORATION RELAY INSTRUMENT DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Reviews: