TYPES CA- 16 AND CA-26
imum spring deflection for this value of current may
be found. Then lock the core screw in place. Next,
adj ust the de- energized po sition of the p l unger by
raising the Micarta disc until the p lunger just p icks
up electrically at the 0. 15 amp ere value.
E l e c tr i c a l C h e c k p o i n t s
Figures 1 2 and 13 will aid i n trouble shooting
either the C A- 16 or the CA-26 relays. These curves
show the operating c urrent to trip the relay for dif-
TEI!MIMAL AIID
MOUMTIIG DElli
LS
ferent re straint currents for one restraint element as
well as for six restraint elements connected in series.
R E N E W A L P A R T S
Rep air work can be done most satisfactorily at
the factory. However, interchangeable p arts can be
furnished to c ustomers who are e quipped for doing
repair work. When ordering p arts , always give the
complete nameplate data.
PAICEL CUTOUT & O�ILLIMG
FO� SEl41 FLUSH NTG.
PIIEL DIU LLIIG
OR
CUTOUT FOil PltO.IECTIDI MTG.
(FRDIT VIEW)
57-D-7903
Fig. 14. Outline and Dri l l ing for the CA- 1 6 and CA-26 Relays in FT -32 Case,