TYPE  CA-6  PERCENTAGE  DIFFERENTIAL  RELAY 

FOR  BUS  AND  TRANSFORMER  PROTECTION 

C A UT I 

0 H 

Before  putting  relays  into  service,  re­

move  all  blocking  which  may  have  been  inserted  for 
the  purpose  of  securing  the  parts  during  shipment, 
make  sure  that  all  moving  parts  operate  freely,  in· 

spect  the  contacts  to  see  that  they  are  clean  and 
close  properly,  and  operate  the  relay  to  check  the 

settings  and  electrical  connections . 

A P P L I CATION 

The  type  CA-6  percentage  differential  relay  is 

us ually  applied  for  the  differential  protection  of 
multi-circuit  buses. 

The  application  of  the  CA-6 

relays  for  bu s  differential  protection  may  be  divided 
into  three  categories.  (In  the  following  discussion 

an  equivalent  circuit is  defined  as  a major  source  or 
a  group  of  feeder  circuits.  The  fault  current  contri­
bution  of  all  the  paralleled  feeders  should  not  ex­
ceed 

5% 

of  the  total  phase  or  ground  fault  current , 

with  normal  bus  connections . )  

GENERATING  STATION  BUSES  - FOU R  
EQUIVALENT  CIRCUITS  O R   LESS  - DC 
TIME  CONSTANT 

0!<' 

0 . 6   CYCLES 

O R   MORE. 

If  the  following  requirements  are  met ,  the 

CA-6  may  be  satisfactorily  applied: 

1)  The 

maximum  external  fault  current 

through  the  bu s  should  not  exceed  100 

symmetrical  RMS secondary  amperes. 

2)  The  magnetizing  current  of  the  current 

transformers  carrying  a  total  external 
fault  current  of  100  symmetrical  second­

ary  amperes  should  not  exceed  one  sec­

ondary  ampere . 

B)  GENERATING  STATION  BUSES  - MORE 

THAN  FOUR  EQUIVALENT  CIRCUITS 

• 

DC 

TIME  CONSTANT  OF  0 . 6   CYCLES 

OR MORE . 

The  same  requirements  as  in  (A)  apply.  How-

S UPERSEDES I . L. 

41-337. 1C 

*Denotes  ch an ge from  superseded  i ssue. 

ever,  consideration  must  be  given  to  the  re­

straint  coil  connections. 

Where  more  than  4  e quivalent  circuits  are 

present ,  it  is  rarely  necessary  to  provide  two 

relays  per  phase.  With  little  or  no  compromise 
in  the  protection  scheme ,  one  relay  can  handle 

at  least  8  equivalent  bus  circuits.  (See  "Con ­
nections"  for  further  discussion . )  

C)  SUBSTATIOr  BUSES - DC  TIME CONSTANT 

OF  0.6  CYCLES 

O R  LESS. 

If  the  following  requirements  are  met ,   the 

CA-6  may  be  satisfactorily  applied: 

1)  The 

maximum  external  fault  current 

through  the  bus  should  not  exceed  100 
symmetrical  RMS  secondary  amperes .  

2)  The  magnetizing  current  of  the  current 

transformers  carrying  a  total  external 
fault  current  of  100  symmetrical  s econd­
ary  amperes  should  not  exceed 

ten  sec­

ondary  amperes. 

Where  more  than  4  equivalent  circuits  are 

present,  it  is  rarely  necessary  to  provide  two 

relays  per  phase.  With  little  or  no  compromise 
in  the  protection  scheme,  one  relay  can  handl e 

at  least  eight  equivalent  bus  circuits. 

(See  "Connections" for further  discussion. ) 

A  type  CA-6  transformer  relay  is  also  available 

for  3  winding  transformer  protection.  The  standard 

bus  relay  should  not  be  utilized  for  transformer  dif­

ferential  applic ations. 

CONSTRUCTION 

The  type  CA-6  relay  consists  of  three  restrain­

ing  elements  (two  restraining  windings  per  element), 
one  operating  element ,   and  an  indicating  contactor 

switch.  The  type  CA-6  transformer  relay  also  con­

tains  an  indicating  instantaneous  trip  unit. 

EFFECTI V E  SEPTEM B E R  

1960 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for KAB

Page 1: ...t s is not recommend ed If this cannot be avoided the additional impedance from the auxiliary ct s and the high voltage which transformed by the auxiliary ct should be checked SUPERSEDES I L 41 337 4...

Page 2: ...pring adj uster is also held in place by a spring ty pe clamp With the contacts closed the electrical connec tion is made through the stationary contact housing 2 clamp to the mo ving contact through...

Page 3: ...overstress the insula tion A varistor is connected internally to reduce this voltage Figure 2 shows the electrical char acteristics of this device The overvoltage unit is a high speed device and will...

Page 4: ...ce Rs 0 93 n and one way l ead resistance to junction point RL 1 07D A SETTING OF VOL TAGE UNIT 4 a for 3 phase fault condition Rs t RL _l_r I VK 0 93 1 07 N from Fig 3 K 0 76 60000 l I 375 400 0 9 V...

Page 5: ...g enough to trip a breaker I L 41 337 4A BU R D E N The relay burden is approximately 2600 ohms in the tuned circuit However this burden is not seen by any of the CTS during normal operation or during...

Page 6: ...y be necessary to re adjust the overvoltage unit spring for the desired operate voltage 6 Overvoltage Unit V 1 The upper bearing screw should be screwed down until there is approximately 025 clear anc...

Page 7: ...he voltage should measure 175 volts ac 10 A high resistance voltmeter should be used R E N EWAL PAR T S Repair work can be done most satisfactorily at the factory However interchangeable parts can be...

Page 8: ...vv _ I _ _ _H t 0 0 LO ID t 0 0 0 0 q ci PEAK CURRENT AMPERES Fig 2a Typical Volt Ampere Characteristic of Varistor in Type KAB Relay Peak Value I I I I 0 I I II 349 7A22 Ol 1 c Vl 1J om o mOl O t m z...

Page 9: ...300 200 100 01 o V 0 1 AMPERES RMS Fig 2b Typical Volt Ampere Characteristic of Varistor in Type KAB Relay RMS I I v 10 Curve 619414 OJ l c V om n Tl mOJ O r m zC1 l r r3 l om mo r z r w w m w E l e...

Page 10: ...75 0 50 0 25 10 20 30 40 so 60 70 so 90 1 00 1 10 1 20 1 30 VR MARGIN FACTOR K IRs RLI t Fig 3 Margin Factor for V Unit Setting 1 40 1 50 I CJ j C tl om l I mCJ Oz m zc I j I r om I m e r Z n m 1 60...

Page 11: ...2 3 1 I 4 5 6 8 1 0 IJ I j I J 4U 3U zn I 7 1 J ll J I I I I I R S R L 5 0 I v r vy P As RL 0 75 1 0 1 j J t 1 5 6 7 8 10 15 20 30 40 50 60 70 80 100 IT UNIT SETTING AMPERES AMSl Fig 4 IT Unit Setting...

Page 12: ...L LOCKOUT RELAY 52 BREAKERS NOTE RELAY TERMINALS 8 9 810 SHOULD BE OPEN WHEN CLRCUIT BREAKER OR BREAKERS IS TO BE BYPASSED FOR MAINTENANCE OR WHEN ANY OTHER ABNORMAL SETUP IS TO BE MADE I T y_ I 8 _7_...

Page 13: ...DANCE BUS DlFFE R ENT lA L R ELAY L 4 1 3 _ 3 7 4A Gl t 0 IL Gl 01 0 I L E lz 0 J I 0 0 Gl E 0 0 Gi a 0 c u a N o o 0 Gi co t 0 0 u __ N S3l A 3VIIIl E Nil f 3d0 13 w w w E l e c t r i c a l P a r t M...

Page 14: ...SCIEW II FOR THICK fiAIIEL USE 6 TERNIMAL AIID IQINTING DETAILS li 18 STUD _ 190 32 SCREW FOR THICK PANEL USE 190 32 STUO 3 DIA IO IIOL S Olt CUT OUT J1 e 1 _DIA IJ KOU S flll 2 1 _ 1 110 12 m aaBrl...

Page 15: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 16: ...WESTINGHOUSE ELECTRIC CORPORATION RELAY INSTRUMENT DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 17: ...ed for transformer differential applications since it is too sensitive for overriding the inrush Likewise the CA 26 relay should not be used for bus protection with the four circuit bus connections of...

Page 18: ...T Y P ES CA 1 6 AND CA 26 R ELAYS ________________________ 2 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 19: ...uncing A Micarta disc is fastened to the bottom of the guide rod by 30TT OM RI HT AliD Elf Mfn F V l lkJI ATING ONTACTO SWITCH TOPLHTII 0 LE E T F 1 OTE WITH flATIH I SUN TAN OUS POLA ITI S AS h IIN T...

Page 20: ...I ao Ht 40 f t 0 20 0 60 80 100 120 140 160 OPERATING CURRENT IN AMPERES Curve 537956 Fig 6 Typical Time Curves of the CA 1 6 and CA 26 dif ferential Relays polarity as indicated above their effect w...

Page 21: ...amperes at 250 volts d e and will c arry this current long enough to trip breaker The indicating contactor switch has two tap s that provide a pick up setting of 0 2 or 2 amperes To change taps requi...

Page 22: ...9 connections where there are more than three sources the source CT s should be par allelled to reduce the effective number of source con nections to three The four circuit bus connec tions of Fig 8...

Page 23: ...N D M AI N T E N A N C E The proper adjustments to insure correct operatio n of this relay have been made at the factory Upon receipt of the relay no customer adjustments other than those covered und...

Page 24: ...it has no t arg et F Sens itive F a u lt Detec tor w h ere s upp l ied Apply current to terminals 14 and 15 of the re l ay The fault detector should operate between the limits of 0 14 2 to 0 158 amper...

Page 25: ...t clo se in the following times CA 16 52 5 milliseconds CA 26 72 5 milliseconds These times should be the average of 5 readings 5 lnd icating C o ntactor S w i t c h IC S Close the main relay contacts...

Page 26: ...e operating current to trip the relay for dif ferent restraint current for one restraint element as 1 0 well as for six restraint elements connected in series R E N E W A L P A R T S Rep air work c an...

Page 27: ...RENT CAN EXCEED TWICE TttE EXTERNAL FAUlT CURRENT SET P ICK UP EQUAL TO MAXIMUM EXTERNAL FAULT CURRENT 1 3 A c AUX CURREMT BALAMCE CURRENT TRAitS 87 i9 7 87 87 8 12 PHASE 2 SAME AS PH H o 15 POS r 1 I...

Page 28: ...25 16 q DIA HOLES FOR s ff r 32 Uftn J oo f 4_ PANEL CUTOUT DRI LLIJG FOI SEMI FLUSH MTG PAREL DRI LLIIIG OR CUTOUT FOR PRQJECTJOII MTG FROIIT Y I EW 57 D 7903 6 f Fig 15 Outline and Drilling for the...

Page 29: ...ed i ssue T _ h e CA 6 re lay sho o be u _ til zed for tra s form er differential appllcat iiJ i_ since It IS too se nsitive for overriding the i nrus h _ Likewise the C A 26 relay shoul d not be us e...

Page 30: ...T T YP ES CA 16 AND CA 26 R ELAYS _ ___________ _ _ _ _ _ _ __ _____ i c Ill a u Ill Cl 1 IJ 2 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 31: ...evented from causing contact bouncing A Mic arta disc is fastened to the bottom of the guide rod by BOTTOM R I GHT II I IID ELEMEIH F V IHD ICATIMG CONTA CTOR SWITCH CA U 00 CA 26 TOP LEFT ltAIID ELEM...

Page 32: ...2 CA 6 ll 00 40 20 40 60 80 100 120 160 OPERATING CURRENT IN AMPERES j_ _ _ _ _ _ _ _ _ _ Curve 537956 Fig 6 Typ ical Time Curves of the CA 1 6 and CA 26 dif ferential Relays polarity as indicated abo...

Page 33: ...reaker The indicating instantaneous trip contacts will safely close 30 amperes at 250 volts d e and will carry this current long enough to trip breaker The indicating contactor switch has two taps tha...

Page 34: ...s the source CT s should be par allelled to reduce the effective number of source con nections to three The four circuit bus connec tions of Fig 8 are not recommended to be used for bus protection wit...

Page 35: ...rrect operation of this relay have been made at the factory Upon receipt of the rel ay no customer adjustments other than those covered under SETTINGS should be required Ac ceptance C h ec k The follo...

Page 36: ...y suf ficient current to operate the liT F Sen s i t i ve F au l t D etec to r w here s u pp l ied Apply current to terminals 14 and 15 of the re lay The fault detector should operate between the limi...

Page 37: ...A 26 72 5 milliseconds These times should be the average of 5 readings 5 lnd icating C o n tactor Sw itc h IC S Close the main rela y contacts and pass sufficient d e current through the trip circuit...

Page 38: ...the operating current to trip the relay for dif ferent restraint current for one restraint element as 10 well as for six restraint elements connected in series R E N E W A L P A R T S Rep air work ca...

Page 39: ...SCREW 6 FOR THICK PMIEL USE t 18 STUD r r r I I I I I TEIMIIAL MD MOLI IITIIIG DETAILS TERMIUL MI BE 25 q Oi l IJ HOLES FOI 5 9 ff r I PANEL CUTOUT DRI LLI G FOR SEMI FUJSH MTG PAIEL DRI LLIRG OR CUTO...

Page 40: ...AESTUIIT COI L 6 TOP R H ELEM I CS I I D I CATIRG COlT SW l i T liD liST TRIP 86 AUX TRIPPIRG RELAY TYPE WL t USE WIIERE INTERNAL CURREKT CAM EXCEED TWICE TltE EXTERNAL FAULT CURRENT SET P I CK UP EQ...

Page 41: ...se the two way lead burden CON T E N T S This instruction leaflet plies to the following SUPERSEDES I L 41 337 26 Denotes change from superseded i ssue typ es of relays CA 16 Bus Differential Relay CA...

Page 42: ...TYPES CA 1 6 AND CA 26 R ELAYS 41 1 0 a 0 lJ Ill 41 Q 1 o i i 2 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 43: ...plunger BOTTOM R I GHT HAMO HEMEIIT F V INTERNAL SCHEMATIC I N O I CATIMG COMTACTOR SWITCH 1m ICS CA 16 IC l iT c u l_ TOP LEFT IIAIID ELEMEMT F V NOTE WITH RELATIVE INSTAN TANEOUS POLAR I T I ES AS S...

Page 44: ...14 I6C OPERATING CURRENT IN AMPERES Curve 537956 Fig 6 Typical Time Curves of the CA 1 6 and CA 26 dif ferential Relays rent transformers connected to the bus and the operating circuit is energized i...

Page 45: ...unit when a current transformer is severely satur ated by the d e component of an asymmetrical external fault current T r i p C ir c u it The main contacts will safely close 30 ampere s ElTEIIINAL SCH...

Page 46: ...these four sets of CT s to the rel ays p er Fig 8 The exception to this rule occurs when the application consists of three feeder groups Then Fig 9 applies With 3 feeder group s and more than 3 sourc...

Page 47: ...ench For detailed FT case information refer to L L 4 1 076 A D J U S T M E N T S A N D M Al N T E N A N C E The proper adjustments to insure correct operation of this relay have been made at the facto...

Page 48: ...0 The making of the contacts and target indic ation should occur at approximately the same instant Position the stationary contact for a minimum of 1 3 2 inch wipe The bridging moving contact should t...

Page 49: ...keep er of the permanent magnet until the contacts just clo se in the following times CA 16 52 5 milliseconds CA 26 72 5 milliseconds These times should be the average of 5 readings 5 lnd icating C o...

Page 50: ...relay for dif TEI MIMAL AIID MOUMTIIG DElliLS ferent restraint currents for one restraint element as well as for six restraint elements connected in series R E N E W A L P A R T S Rep air work can be...

Page 51: ...l t USE WHERE I NTERNAL CURRENT CAN EXCEED TlfiCE THE EXTERNAL FAULT CURRENT SET P I CX UP EQUAL TO MAX I EXTERUL FAULT CURRENT A A AUX CURREMT BALAMCE CURRENT TRAU POS I C S AUK CURRENT 2 R S T Ill I...

Page 52: ...WESTIN G H O USE E L E C T R I C C O R P O R ATI O N RELAY INSTRUMENT DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 53: ...N FOUR EQUIVALENT CIRCUITS DC TIME CONSTANT OF 0 6 CYCLES 0 01 Sec OR MORE The same requirements as in A apply How S UPERSEDES I L 41 337 1C Denotes ch ange from superseded i ssue ever consideration m...

Page 54: ...pper type device A magnetic armature to which 2 TOP FKOtH El f 4ENT F INTERNAL SCHEMATIC TOP REAR ELEMENT F Y J J 1NO I CAf l MG COnfACTOR Sifil fCH IMOICATING ICS J I C I l l IMSTAn TArtEO JS TRIP Ai...

Page 55: ...unt of restraining w _J 0 0 w _J 0 0 r 20 I I I l s l i It _ 0 o 20 40 60 80 NET TORQUE IN CENTIMETER GRAMS Curve 235496 Fig 4 Typical Differential Unit Time Curve torque as indicated in Fig 3 Similar...

Page 56: ...rmers will be much greater than would ever be e xpected from a consideration of the usual ratio curves of the current transformers involved CHARACT E RISTICS There are no taps inside the relay case Ta...

Page 57: ...S POs DEV I CE NUMBER CHART PH 1 87 PERCENTAGE D IFFERENTIAL RELAY TYPE CA 6 r r y TO BREAKER TR I P CO I LS NEG _ _ _ _ _ _ _ _ _ _ _ _ ICS I ND I CATING COMTACTOR SWI TCH OP OPERATI NG CO I L R PA I...

Page 58: ...PH 3 87 PERCENTAGE DtFFERENTIAL RELAY TYPE CA 6 ICS I ND I CA T I N G CONTACTOR SWI TCH OP OPERATING COI L R PA I RED RESTRA I NT COI L TOP FRONT ELENENT S PA I RED RESTRA INT CO I L BOTTOM REAR ELEM...

Page 59: ...O I LS 87 PERCENTAGE D I FFERENT IAL RELAY TYPE CA 6 ICS I ND I CAT I NG CONTACTOR SW I TCK OP OPERATING CO I L R PA I RED RESTRA INT CO I L TOP FRONT ELEMENT S PA I RED RESTRA I NT CO I L 80T TOI4 RE...

Page 60: ...SW I TCH OP OPERATINu CO I L R PA I RED R ESTRA INT CO I L TOP FRONT ELEMENT s PA I RED RESTRA I N T CO I L BOTTOM REAR ELEMENT T PA I RED RESTRA I NT CO I L BOTTOM FRONT ELEMENT PH 1 TYPE CA 6 IN TY...

Page 61: ...der that the relay maybe given a higher minimum trip setting as noted under Ad justments and Maintenance TRIP CIRCUIT The main contact will safely close 30 amperes at 250 volts d e and the seal in con...

Page 62: ...ed 5 of the total phase or ground fault cur rent with normal bus connections In paralleling current transformers for the feeder group or groups the load current distribution should be examined to insu...

Page 63: ...rces if there are less than 8 equivalent circuits 3 Avoid pairing the two largest sources 4 If feasible parallel matched current trans formers In case IV with two feeder groups one of the restraint el...

Page 64: ...12 of pick up desired It is recommended that a pickup of 100 amperes be used I N S TA L L A T I O N Th e relays should be mounted o n switchboard panels or their equivalent in a location free from dir...

Page 65: ...ommended for this purpose The use of abrasive material for clean ing contacts is not recommend ed because of the danger of embedding small particles in the face of the soft silver and thus impairing t...

Page 66: ...W FOR T H I C K PA N E L U S 1 90 U STUD T E R M I N A L AN D M O U N T I N G D ETA I LS N OTE ALL OIME N SIONS Ito I N C I IE I t D I A 4 H O L E S O R I S 2 2 MT S C R Ew5 PA N E L C UT O UT D R I L...

Page 67: ...6 Relay Without Case Rear View J Top Rear Operating Element 2 Stationary Contact 3 Moving Contact 4 Control Element 2 Bottom Rear Restraining Element Spring Assembly 5 Bottom Front Restraining Element...

Page 68: ...W E S T I N G H O U S E E L E C T R I C C O R P O R A T I O N R E LAY D E PA RTM E N T N EWA R K N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 69: ...l 337 3A Denotes change from superseded i ssue The CA l relay should not be utilized for transformer differential applications Likewise the O A 26 relay should not be used for bus p rotection with the...

Page 70: ...N Fig 1 Types CA 1 6 Relay front view Fig 2 Typ s CA 1 6 Relay rear view t m n I 0 z 0 n p 0 tl m r E l e c t r i c a l P a r t M a n u a l s c...

Page 71: ...remain s stationary Thus a c vibrations of the plunger are prevented from c ausing contact bouncing A Micarta disc is fastened to the bottom of the guide rod by BOTTOf I RIGHT IIA ND HEMEMT F V TOP L...

Page 72: ...60 80 100 120 140 160 OPERATING CURRENT IN AMPERES Curve 537956 Fig 6 Typical Time Curves of the CA 1 6 and CA 26 dif ferential Relays polarity as indicated above their effect will be addi tive and th...

Page 73: ...stantaneous trip contacts will safely close 30 amperes at 250 volts d e and will carry this current long enough to trip breaker The indic ating contactor switch has two taps that provide a pick up set...

Page 74: ...Fig 9 connections where there are more than three sources the source CT s should be par alleled to reduce the effective number of source con nections to three The four circuit bus connec tions of Fig...

Page 75: ...ion of this relay have been made at the factory Upon receipt of the relay no customer adjustments other than those covered under SETTINGS should be required Ac ceptance C h ec k The following check is...

Page 76: ...RESTRA INT COH IM TOP L EL 11 PE T PAIRED RESTUIIT COI L n 26 TOP R M EL 11 I CS I I D I CATIIG COlT SW I IT IIO liST TR I P 116 AUX TI IPPIIG RELAY TYPE Wl t USE wrtERE IMTEINAL CURRENT CAM EXCEED T...

Page 77: ...AN FOUR EQUIVALENT CIRCUITS DC TIME CONSTANT OF 0 6 CYCLES 0 01 Sec OR MORE The same requirements as in A apply How S UPERSEDES I L 41 337 1C Denotes ch ange from superseded i ssue ever consideration...

Page 78: ...ntact is made thru the spiral spring to the spring adjuster INDICATING CONTACTOR SWITCH UNIT ICS The d e indicating contactor switch is a small clapper type device A magnetic armature to which 2 INTER...

Page 79: ...Curve 235496 Fig 4 Typical Differential Unit Time Curve torque as indicated in Fig 3 Similarly a current of 5 amperes flowing in at termiRal 16 and out of terminal 17 will produce an equal amount of...

Page 80: ...al ratio curves of the current transformers involved CHARACT E RISTICS There are no taps inside the relay case Taps 4 controlling the sensitivity of the relay are incorpor ated in the external current...

Page 81: ...CENTAGE D I FFERENTIAl REl AY TYPE CA 6 r r y TO BREAKER TR I P CO I LS NEG _ ICS I ND I CATI NG COKTACTOR SWI TCH OP OPERATING CO I L R PA I RED RESTRAI NT CO I L TOP FRON T El ENENT S PAI RED RESTRA...

Page 82: ...NUMBER CHART 87 PERCENTAGE DtFFERENTIAL RELAY TYPE CA 6 ICS I ND I CATING CONTACTOR SWI TCH OP OPERATING COI L R PA I RED RESTRA I NT COI L TOP FRONT ELEMENT S PA I RED RESTRA I NT COI L BOTTOM REAR...

Page 83: ...ER TRIP COILS 87 PERCENTAGE DIFFERENTIAL RELAY TYPE CA 6 ICS INDICATING CONTACTOR S ITCii OP OPERATING COIL R PAIRED RESTRAINT COIL TOP FRONT ELEMENT S PAIRED RESTRAINT COIL BOTTOM REAR ELEMENT T PAIR...

Page 84: ...R SW I TCH OP OPERA T I N G CO I L R PA I RED R ESTRA I N T CO I L TOP FRONT ELEMENT S PA I RED RESTRA I N T CO I L BOTTOM REAR ELEMENT T PA I RED RESTRA I N T CO I L BOTTOM FRONT ELEMENT lM TYPE CA 6...

Page 85: ...t the relay maybe given a higher minimum trip setting as noted under Ad justments and Maintenance TRIP CIRCUIT The main contactE will safely close 30 amperes at 250 volts d e and the seal in contacts...

Page 86: ...eed 5 of the total phase or ground fault cur rent with normal bus connections In paralleling current transformers for the feeder group or groups the load current distribution should be examined to ins...

Page 87: ...there are less than 8 equivalent circuits 3 Avoid pairing the two largest sources 4 If feasible parallel matched current trans formers In case IV with two feeder groups one of the restraint elements...

Page 88: ...12 of pick up desired It is recommended that a pickup of 100 amperes be used I N S T A L L AT I O N The relays should be mounted on switchboard panels or their equivalent in a location free from dirt...

Page 89: ...commended for this purpose The use of abrasive material for clean ing contacts is not recommend ed because of the danger of embedding small particl es in the face of the soft silver and thus impairing...

Page 90: ...I C K PA N E L U S 1 90 32 5TUD T E R M I N AL i _ N D 1 0 U NT I N C D ETA I LS NOTE Al L DIME N SIONS IH I N C I E t D I A 1 H O L E S FOR 1 s MTE S C R Ew S PA N E L C Ut O UT DR I L L tNC1 F O R S...

Page 91: ...y Without Case Rear Vie Element 2 Stationary Contact 3 Moving Contact 4 Control Spring A ssembly 5 Bottom Front Restraining Element 6 Indicating Contactor Switch ICS E lement 2 Bottom Rear Restra in i...

Page 92: ...WEST I NGHOUSE ELECTRIC CORPORATION RELAY INSTRUMENT DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Reviews: