background image

KX 

TRANSFORMER 

AL  RELAY 

120 X  RELAY 

Page  9 

AR  RELAY 

!20  Y  RELAY 

Fig. 

6- CVR-1 Relay Removed from Case (Rear View) 

trol  panel)  and  follow  the  procedure  under 
"Setting  the  CVR-1  Relay  by  Applying  an 
External  Voltage".  The self-sealing circuit 
of  the  CVR-1  relay  may  be  cleared  by  mo­
mentarily  connecting  a  jumper  from  2  to  5. 

The  120  switch  performs  this  function  in 

the  tap  changer,  clearing  the  self-sealing 
network  and  applying  negative  compounding 

to  the  disk  of  the  CVR-1  relay.  If  desired, 
a  constant  voltage  may  be  applied  at  points 

6  and  9  with  the  Test  Rheostat being used  to 

obtain  a  variable  voltage.  A voltmeter con-

nected  across  9  and  14  will  indicate  the 
voltage  actually  applied  to  the voltage sens­

ing  coil. 

A  somewhat more intricate test circuit is 

indicated  in  Figure  8.  Such  a  reconnection 

following  removal  of  the  original  jumpers 
will  provide  all  switching  and indication re­
quired  to  calibrate  the  relay  and  check  its 

performance  while  removed  from  the  tap 

changer  control  panel.  Lights  Rp  and  Lp 

indicate  operations  of  contacts  90R  and 90L 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for CVR-1

Page 1: ...1 Voltage Regulating Relay Westinghouse Electric Corporation Power Transformer Division Sharon Pa I B 47 065 9A Elfecci e NoYember 1962 Supersedes I B 47 065 9 March 1961 w w w E l e c t r i c a l P...

Page 2: ...Simplified Control Schematic With CVR 1 Relay 6 CVR 1 Removed From Case Rear View 7 Closeup of CVR 1 Relay Adjustments 8 Circuit for Checking and Calibrating the CVR 1 Relay Removed From Case 9 Typic...

Page 3: ...romagnet and clean them if any foreign material is present Operate the relay to check the settings and electrical connections Operation The sensing element of the CVR 1 relay is an induction disk volt...

Page 4: ...cing contact has opened a cam operated 120 switch in the tap changer closes to energize the 120X relay which in turn takes over the sealing of the AR relay through its 120X contact and also operates t...

Page 5: ...d By thus circulating current pro portional to the load through resistance and reactance elements an impedance voltage is produced which is combined with the control voltage to match the relation betw...

Page 6: ...TT2 as shown in Figure 5 It is convenient to apply an ex ternal variable voltage source to PTT1 and PTT2 reading on the voltmeter the voltage at which the 90R and 90L contacts close If desired a const...

Page 7: ...g contact operating the tap changer in the lower direction 5 The CVR 1 relay is now set to hold regulated output between the limits of 119 and 121 volts or at a nominal 120 volt level Page 7 balance v...

Page 8: ...heostat for the de sired value of the 90L setting and again after 60 seconds set the control selector on AUTO Move the 90L stationary contact until it picks up the motor control relay 5 Refer to Time...

Page 9: ...sk of the CVR 1 relay If desired a constant voltage may be applied at points 6 and 9 with the Test Rheostat being used to obtain a variable voltage A voltmeter con nected across 9 and 14 will indicate...

Page 10: ...te closing of the raise and lower pushbuttons Ro and Lo still indicate operation ofAR and AL contacts General operating data for the relay on 60 cycles is as follows Burden of the potential circuit at...

Page 11: ...OSED Fig 8 Circuit for Checking and Calibrating the CVR 1 Relay Removed from Case of voltage For example any one of the fol lowing conditions contributes to a shorter time delay 1 A lower damping fact...

Page 12: ...wn in Figure 7 This is done by loosening the four magnet assembly mounting screws See Figure 7 and sliding the magnet assembly to its new position A magnet time multiplier scale is attached to the per...

Page 13: ...front of the relay with the cover removed The adjustments for resistance and reactance compensation the switch for reversing the polarity of the reactance compensation and the Test Rheo stat are all...

Page 14: ...ation is available only when the main current transformer is delivering a full 5 amperes to the tap changer control An auxiliary current transformer ACT steps this current down from 5 amperes to the 2...

Page 15: ...sation N c T 5 X X RL X d X n N POT Dial Setting for Reactance Compensation N 5 x C T x XL x d x n N POT Where N c T main current transformer ratio primary current secondary current N POT potential tr...

Page 16: ...e completed through the closed knife blades The case designation is type FT 32 REMOVING CHASSIS To remove the chassis first remove the cover by unscrewing the captive thumb nut at the bottom and lifti...

Page 17: ...v v L 3 4 5 6 7 8 9 10 12 EQUIVALENT CONDUCTOR SPACING FEET v v v v c 300 000 CM 5001000 CM I 0001000 CM 16 20 30 EQUIVALENT CONDUCTOR SPACING D OF UNSYMMETRICAL THREE PHASE LINES IS GIVEii BY THE EXP...

Page 18: ...ugh the current test jack jaws This circuit can be isolated by inserting an ammeter test plug S ll640 47 SWITCH BLADE JAW CLIP LEAD LUG AMMETER TEST PlUG SWITCH BLADE HINGE Fig 14 Ammeter Test Plug in...

Page 19: ...sition An internal schematic for the relay is shown in Figure 3 Maintenance The proper adjustments to insure correct operation of this relay have been made at the factory and should not be disturbed a...

Page 20: ...ounding Resistors 3000 Ohms 25 Watt 8 1202954 Resistor 6 Ohms 25 Watt S 04D1298H84 Trimming Resistor 3000 Ohms 5 Watt S 184A635H12 Resistor Self Supporting 4500 Ohms 5 Watt S 182A874H01 Thermistor Sel...

Reviews: