LOWER
FLEX I TEST
PLUG
i
@
120
VOL.
T..
60
CYCL E
VOLTAGE
R
Page 11
UPPER
FLEXJTEST
PLUG
Oi
120
NORMALLY OPEN SPRING RETURN
S WITCHES
OR
PUSH- BUTTONS
RA I SE
LOWER
120
(CLOSE TO RESET RELAY)
Lp
@
0
INDICATING LIGHTS
*
Rp
•
RAISE
01
SK CONTACT
Lp
: LOWER DISK
CONTACT
Ro
•
RAISE
OPER ATE
Lo
•
LOWER OPE RATE
*
USE
1/2!5
OR
1/4
WATT NEON L AMPS WITH PROT E CTIVE RESISTORS
CAL-AUTO-MAN
3·
POSITION SELE CTOR SWITCH SEQUENCE
SWITCH POSITION
CAL.
AUTO
MAN
I
X
X
2
X
X
3
X
X=
INDICATES CONTACTS CLOSED
Fig.
8
-
Circuit for Checking and Calibrating the CVR-1 Relay Removed from Case
of voltage. For example, any one of the fol
lowing conditions contributes
to
a shorter
time delay.
1.
A lower damping factor.
2. A greater voltage deviation from the
center of the set bandwidth.
3. A lower bandwidth.
Should the conditions be reversed, a
longer time delay is indicated. It is difficult
to make a general statement about time de
lay except that itis not fixed. It can be said,
however, that for step deviations from the
band center equal to 75% of total set band
width, time delay may be varied from
11
to
60 seconds by adjustment of the damping
magnet and keeper. Correction for greater