background image

in  the "direct" position.  Reversed reactance 
compensation  is  obtained  by  placing it in the 
"reverse"  position,  which  reverses  the  po­
larity  of  the  reactance  element. 

"Reverse  reactance" compensation  is  a 

method  used  to  reduce  the  circulating  cur­
rent  that  might flow when two or more trans­
formers  are  paralleled.  It is a requirement 
of  ASA  Standards  C57.12-37.236.1.  Instead 
of  running  toward  opposite  extreme  posi­
tions,  tap  changers  having  "reverse  re­
actance"  compensation  tend  to  move toward 
whatever  positions  cause the least amount of 
circulating  current  to  flow.  This is accom­
plished  at  some  sacrifice  of  normal  line 

drop  compensation,  but  is  generally  satis­
factory  when  units paralleled are not located 
in  close  proximity  to  each  other,  or  where 

the  supply  is  from  different  sources. 

4.  Line 

The 

final  settings  on  the  line-drop  compensator 

are  usually  made  by  field  adjustments,  but 
if  the  data  on  the  particular  line  is  known, 
the  curves  in  Figs.  12  and  13  may  be  used, 

and  initial  values  calculated. 

The  initial  line-drop  compensator  set­

tings  can  be  derived by the use of the  follow­
ing  expressions: 

Dial  Setting for Resistance Compensation  = 

Nc  T 

• 

• 

RL 

n. 

NPOT 

Dial  Setting  for  Reactance Compensation  = 

5  x 

C.T.  x  XL  x  d  x  n. 

NPOT 

Where 

Nc. T.  =  main  current  transformer  ratio 

primary  current 

NPOT  = 

potential  transformer  ratio 

primary  voltage 

Page 15 

RL 

resistance  per  conductor  from 
unit  to  load  center,  in  ohms  per 

mile. 

inductive  reactance  per  conduc­
tor  from  unit  to  load  center,  in 
ohms  per  mile. 

miles  from  unit  to  load  center. 

120/balance  voltage  setting. 

A  typical  three-phase  example  is  as  fol­
lows: 

0

.,...__

4'

-

0

-

4'-0 

8, 

500,000  CM  copper  conductor,  with  flat 
spacing  above. 

Line  Voltage =  12000  volts 

Main  Current  Transformer  Ratio=  600/5 

Potential Transformer  Ratio =  6928/120 

Distance from unit to load center  3 .5 miles. 

Balance  voltage  setting =  117  volts. 

A  unit  energizes  a  typical  distribution 

circuit  whose  characteristics  are  given 
above.  Determining  the  constants  for  the 

circuit  on  a  per  phase  basis, 
From  Figure  12: 
R  =  0.12  ohms  per  mile. 

From  Figure  13: 
D  = 1.26x4  =  5.04  feet. 

XL =  0.64  ohms  per  mile. 

The  line  drop  compensator  resistance  set­

ting  is: 

120 

6928/120 

0.12 

3.5 

117  - 4.47 

The  line  drop  compensator  reactance  set­

ting  is: 

600/5 

120 

6928/120 

0.64 

3.5 

23.9 

These  settings  may  be  adjusted  as found 

necessary  as  shown  by  load  center  voltage 
measurements. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for CVR-1

Page 1: ...1 Voltage Regulating Relay Westinghouse Electric Corporation Power Transformer Division Sharon Pa I B 47 065 9A Elfecci e NoYember 1962 Supersedes I B 47 065 9 March 1961 w w w E l e c t r i c a l P...

Page 2: ...Simplified Control Schematic With CVR 1 Relay 6 CVR 1 Removed From Case Rear View 7 Closeup of CVR 1 Relay Adjustments 8 Circuit for Checking and Calibrating the CVR 1 Relay Removed From Case 9 Typic...

Page 3: ...romagnet and clean them if any foreign material is present Operate the relay to check the settings and electrical connections Operation The sensing element of the CVR 1 relay is an induction disk volt...

Page 4: ...cing contact has opened a cam operated 120 switch in the tap changer closes to energize the 120X relay which in turn takes over the sealing of the AR relay through its 120X contact and also operates t...

Page 5: ...d By thus circulating current pro portional to the load through resistance and reactance elements an impedance voltage is produced which is combined with the control voltage to match the relation betw...

Page 6: ...TT2 as shown in Figure 5 It is convenient to apply an ex ternal variable voltage source to PTT1 and PTT2 reading on the voltmeter the voltage at which the 90R and 90L contacts close If desired a const...

Page 7: ...g contact operating the tap changer in the lower direction 5 The CVR 1 relay is now set to hold regulated output between the limits of 119 and 121 volts or at a nominal 120 volt level Page 7 balance v...

Page 8: ...heostat for the de sired value of the 90L setting and again after 60 seconds set the control selector on AUTO Move the 90L stationary contact until it picks up the motor control relay 5 Refer to Time...

Page 9: ...sk of the CVR 1 relay If desired a constant voltage may be applied at points 6 and 9 with the Test Rheostat being used to obtain a variable voltage A voltmeter con nected across 9 and 14 will indicate...

Page 10: ...te closing of the raise and lower pushbuttons Ro and Lo still indicate operation ofAR and AL contacts General operating data for the relay on 60 cycles is as follows Burden of the potential circuit at...

Page 11: ...OSED Fig 8 Circuit for Checking and Calibrating the CVR 1 Relay Removed from Case of voltage For example any one of the fol lowing conditions contributes to a shorter time delay 1 A lower damping fact...

Page 12: ...wn in Figure 7 This is done by loosening the four magnet assembly mounting screws See Figure 7 and sliding the magnet assembly to its new position A magnet time multiplier scale is attached to the per...

Page 13: ...front of the relay with the cover removed The adjustments for resistance and reactance compensation the switch for reversing the polarity of the reactance compensation and the Test Rheo stat are all...

Page 14: ...ation is available only when the main current transformer is delivering a full 5 amperes to the tap changer control An auxiliary current transformer ACT steps this current down from 5 amperes to the 2...

Page 15: ...sation N c T 5 X X RL X d X n N POT Dial Setting for Reactance Compensation N 5 x C T x XL x d x n N POT Where N c T main current transformer ratio primary current secondary current N POT potential tr...

Page 16: ...e completed through the closed knife blades The case designation is type FT 32 REMOVING CHASSIS To remove the chassis first remove the cover by unscrewing the captive thumb nut at the bottom and lifti...

Page 17: ...v v L 3 4 5 6 7 8 9 10 12 EQUIVALENT CONDUCTOR SPACING FEET v v v v c 300 000 CM 5001000 CM I 0001000 CM 16 20 30 EQUIVALENT CONDUCTOR SPACING D OF UNSYMMETRICAL THREE PHASE LINES IS GIVEii BY THE EXP...

Page 18: ...ugh the current test jack jaws This circuit can be isolated by inserting an ammeter test plug S ll640 47 SWITCH BLADE JAW CLIP LEAD LUG AMMETER TEST PlUG SWITCH BLADE HINGE Fig 14 Ammeter Test Plug in...

Page 19: ...sition An internal schematic for the relay is shown in Figure 3 Maintenance The proper adjustments to insure correct operation of this relay have been made at the factory and should not be disturbed a...

Page 20: ...ounding Resistors 3000 Ohms 25 Watt 8 1202954 Resistor 6 Ohms 25 Watt S 04D1298H84 Trimming Resistor 3000 Ohms 5 Watt S 184A635H12 Resistor Self Supporting 4500 Ohms 5 Watt S 182A874H01 Thermistor Sel...

Reviews: