43
926.275.1 - GB
INSTRUCTIONS FOR FITTERS
The authorised Technical Assistance Service can convert this boiler to natural gas (
G20
) or liquid gas (
G31
).
19. GAS CONVERSION
The procedure for calibrating the pressure regulator varies slightly according to the type of gas valve fitted (
HONEywEll
or
SIT
, see figure 10).
Carry out the following operations:
A) replace the main burner nozzles;
B) change the modulator voltage
C) new max. and min. calibration of the pressure regulator.
A) Replace the burner injectors
• carefully pull the main burner off its seat;
• replace the main burner injectors making sure to fully tighten them to prevent gas leaks. Injector diameters are specified
in table 2.
B) Change the modulator voltage
• set parameter
F02
according to the gas used, as described in section 21;
C) Calibrate the pressure regulator (Figure 10)
• connect the positive pressure test point of a differential pressure gauge (possibly water-operated) to the gas valve pres
-
sure test point (
Pb
). Only for models with sealed chambers, connect the negative pressure test point of the pressure
gauge to a “
T
” fitting in order to join the boiler adjustment outlet, the gas valve adjustment outlet (
Pc
) and the pressure
gauge. (The same measurement can be made by connecting the pressure gauge to the pressure test point (
Pb
) after
removing the front panel of the sealed chamber). Measuring burner pressure using methods other than those described
could lead to incorrect results as the low pressure created by the fan in the sealed chamber would not be taken into
account.
C1) Adjustment to nominal heat output:
• open the gas tap and switch the boiler to the Winter mode;
• open a hot water tap that can provide a flow rate of at least
10 litres a minute
or make sure there is maximum heat
demand;
• remove the modulator cover;
• adjust the brass screw (a) until the pressure values shown in table 1 are obtained;
• make sure that the dynamic inlet pressure of the boiler, measured at the gas valve pressure test point (Pa) is correct (37
mbar for propane or 20 mbar for natural gas).
C2) Adjustment to reduced heat output:
• disconnect the modulator power cable and unscrew the screw (
b
) until a pressure value corresponding to reduced heat
output is achieved (see tab. 1);
• reconnect the wire;
• mount the modulator cover and seal.
C3) Final checks
• attach the additional plate supplied with the transformer specifying the type of gas and the calibration performed.
Figure 10
SIT valve - mod. SIGmA 845
Honeywell valve - mod. Vk 4105 m
0901_1101
Summary of Contents for quasar D
Page 29: ......
Page 55: ......
Page 81: ......
Page 107: ......
Page 110: ...110 926 275 1 RU WE STEN 2 3 1 0805_2302 CG_2072...
Page 111: ...111 926 275 1 RU 4 5 1 3 1 1 1...
Page 112: ...112 926 275 1 RU 5 OFF 9 7 8 0 7 1 5 2 6 2 24 F 24 CG_2115 0902_0603 A B...
Page 120: ...120 926 275 1 RU 9 0712_1208 CG_2008 17 230 3 3x0 75 2 8 9 2 L N L N 1 2 18 9 1 2 1 2...
Page 125: ...125 926 275 1 RU 24 F 03 10 24 03 10 2 2 3 2 0 5 3 30 5 30 25 10 24 10 3 NTC 22...
Page 126: ...126 926 275 1 RU 23 13 9912070100 2 2 19 2 2 24 1 25 0902_0606...
Page 127: ...127 926 275 1 RU 26 Kt 2 TM Te 2 0505_3002 TM Te curbe kt 27...
Page 130: ...130 926 275 1 RU 29 24 F C N R G V B V NTC NTC CG_2113 0905_2601...
Page 131: ...131 926 275 1 RU 24 C N R G V B V NTC NTC CG_2116 0905_2602...
Page 135: ......
Page 161: ......
Page 164: ...164 926 275 1 GR 1 2 3 4 2 3 RESET 1 Reset 0805_2302 CG_2072...
Page 165: ...165 926 275 1 GR 4 5 1 3 1 1 C 1 C...
Page 166: ...166 926 275 1 GR 5 OFF 9 7 8 GPL 0 7 1 5 bar 3 6 2 24 F 24 CG_2115 0902_0603 A B...
Page 180: ...180 926 275 1 GR 23 13 9912070100 2 CO2 CO 3 cm 19 C1 2 2 CO2 CO 24 1 25 l h mH 2 O 0902_0606...
Page 181: ...181 926 275 1 GR 26 faston kt 1 TM Te 2 0505_3002 TM Te kt 27...
Page 184: ...184 926 275 1 GR 29 24 F C M N R G V B V NTC NTC CG_2113 0905_2601...
Page 185: ...185 926 275 1 GR 24 C M N R G V B V NTC NTC CG_2116 0905_2602...
Page 187: ...187 926 275 1 GR...