Prior to installation ensure that:
▪
the bearing capacity of the floor is sufficient (see Ch. 3.4.12),
▪
the floor is even and level, if necessary concrete the foundations
(see Ch. 11.1),
▪
the bearing capacity of masonry is sufficient if mounting to the wall,
▪
the pipework path is unimpeded,
▪
condensate water can drain away unimpeded from a frost free outlet,
▪
the unit is accessible for servicing.
Minimum clearance
Do not install the unit near doors and windows. The outlet air must not blow against
windows of neighbouring buildings.
CAUTION
Problems caused by non-compliance with minimum clearances
A short circuit of the air flow can cause problems.
▶
Do not place solid objects near the air inlet and outlet area.
▶
Observe minimum clearance to buildings and sold objects:
150 mm
300 mm
300 mm
200 mm
500 mm
150 mm