![Weishaupt WWP L 15 ARS Installation And Operating Instruction Download Page 15](http://html.mh-extra.com/html/weishaupt/wwp-l-15-ars/wwp-l-15-ars_installation-and-operating-instruction_953333015.webp)
3.4.6 Rating
Evaporator air throughput
5770 m³/h
Recommended condenser heating water throughput 2.579 m³/h / 11.56 kPa
Capacity data - heating (EN 14511)
Heating water supply temperature
+20 ... +60 °C
Air temperature application limit
-20 ... +30 °C
Heating water temperature differential
A2 / W35
5 K
Nominal heat capacity
A2 / W35
9.5 kW
Coefficient of performance (COP)
A2 / W35
3.15
Heating water temperature differential
A7 / W35
5 K
Nominal heat capacity
A7 / W35
15.0 kW
Coefficient of performance (COP)
A7 / W35
4.3
Capacity data - cooling (EN 14511)
Cooling water supply temperature
+4 ... +18 °C
Air temperature application limit
0 ... +46 °C
Cooling - temperature differential
A35 / W7
5 K
Nominal cooling capacity
A35 / W7
12.6 kW
Efficiency ratio (EER)
A35 / W7
3.17
Cooling - temperature differential
A35 / W18
5 K
Nominal cooling capacity
A35 / W18
15.8 kW
Efficiency ratio (EER)
A35 / W18
4.24
Installation and operating instruction
Outdoor unit WWP L 15 ARS
3 Product description
83292002 • 1/2014-05 • La
15-55