3.4 Technical data
3.4.1 Approval data
EHPA, Germany
-
EHPA, Switzerland
-
Basic standards
EN 61000-3-12
(1
EN 55014-1
EN 60335-1
EN 60335-2-40
(1
Only in conjunction with three-phase system connection and a short circuit ca-
pacity of 1.32 MVA at the transfer point from the utility grid.
3.4.2 Electrical data
Supply voltage / frequency
3~ / N / PE, 400 V / 50 Hz
Total power consumption
max 15.4 A
Power consumption standby
14 W
Consumption during operation
max 10670 W
Heating circuit pump consumption
max 140 W
Domestic water feeder pump consumption
maximum 45 W
Type of protection
IPX4
External fuse
B 16 A all poles
3.4.3 Heat source and installation location
Heat source
air
Installation location
outdoors