3.4.9 Operating pressure
Refrigerant high pressure side
max 42 bar
Refrigerant low pressure side
max 19 bar
3.4.10 Contents
Hydraulic unit and outdoor unit
Refrigerant R410A
3.9 kg
(1
(1
If more than 3 kg, an annual leakage test of the refrigerant circuit is mandatory.
3.4.11 Dimensions
900 mm
1365 mm
150 mm
600 mm
150 mm
365 mm
400 mm
320 mm
30 mm
85 mm
45 mm
60 mm
430 mm
1
Condensate outlet opening
3.4.12 Weight
Weight empty: ca. 100 kg