Communication objects for EM-Sol
Object name
Object function
Data type C R W T U Actualiz.
Collector temperature Actual value
DPT9.001 X X - X -
s(≥10s)
Storage temperature
low
Actual value
DPT9.001 X X - X -
m(≥60s)
Solar yield
Total counter
Solar yield
DPT13.013 X X - X -
l(≥10min)
Solar yield
(today)
Solar yield
DPT13.013 X X - X -
m(≥60s)
Solar yield
(previous day)
Solar yield
DPT13.013 X X - X -
l(≥10min)
7.4.11
Communication objects for RF
Object name
Object function
Data type C R W T U Actualiz.
Room temperature
RF
Actual value
DPT9.001 X X - X -
m(≥60s)
7.4.12
Communication objects for RG1
Object name
Object function
Data type C R W T U Actualiz.
Room temperature
RG1
Actual value
DPT9.001 X X - X -
m(≥60s)
7.4.13
Communication objects for RG2
Object name
Object function
Data type C R W T U Actualiz.
Room temperature
RG2
Actual value
DPT9.001 X X - X -
m(≥60s)
Room humidity
RG2
Actual value
DPT9.007 X X - X -
m(≥60s)
7.4.14
Communication objects for EM-KA
Object name
Object function
Data type C R W T U Actualiz.
Temperature sensor
at connector T1
Cascade device
DPT9.001 X X - X -
m(≥60s)
Temperature sensor
at connector T2
Cascade device
DPT9.001 X X - X -
m(≥60s)
PWM signal
to circulation pump
Cascade device
DPT5.004 X X - X -
m(≥60s)