62
9
CODE Message Cause
Possible
fault/rectification
Sensor
30
Fault
Flow safety temp. sensor defective
• Check cable + sensor
31
Fault
Flue gas sensor defective
• Check cable + sensor
33
Warning
5
External sensor B1 defective
• Check cable + sensor
34
Warning
)
DHW sensor B3 defective
• Check cable + sensor
35
Warning
Throughpurt sensor defective,
• Check cable + sensor
version - C
38
Fault
Calorifier sensor B10 defective
• Check cable + sensor
39
Fault
Calorifier sensor B11 defective
• Check cable + sensorn
Motors
41
Fault
Gas valve proving
• Electrical connection gas valve faulty, replace
• Gas valve leaking, replace gas valve
42
Warning
No PWM control signal available
• Check cable connection PWM pump
43
Fault
Fan speed not achieved
• Check cable connection, replace fan
44
Fault
Fan standby faulty
• Replace fan
Electronics
51
Fault
System fault boiler control
• New configuration with P10
• Check all available parameters as per
Ch. 6.3.3, if necessary use WCM diagnostic
Application fault BCC plug:
• Plug in BCC
• Install BCC of version 3.X
Invalid unit configuration
• Replace WCM-CPU
52
Fault
System fault combustion control:
• Replace WCM-CPU
Invalid configuration data set
• Carry out initialisation of BCC
Application fault BCC plug:
• Check polling of BCC
• Plug in BCC and carry out initialisation
53
Fault
Voltage supply insufficient
• Check fuse
or fuse F2 (24V) defective
• Check fan
• Replace electronics
54
Fault
Faulty electronics
• Short circuit ionisation electrode - burner, check
burner fleece for fibres
• Inputs H1, H2 are defective
• Check ionisation electrode, unplug ionisation
electrode/switch control on and off
➩
Fault gone
➩
Replace electrode
• Replace WCM-CPU
55
Fault
Mains frequency is < 45 Hz
• Check mains, avoid unstable mains
or > 55 Hz
56
Fault
Ionisation current measurement faulty
• Reset, if it recurs replace WCM-CPU
Continuation of fault and warning message
5)
If the external sensor is defective, the regulation
continues in emergecy operation. This is based on an
external temperature of 5°C.