Caution 

Supply Voltage 

Condition 

Do not power the MT-6050iV3 and inductive DC loads

, or input circuitry 

to the controller, with the same power supply. Note: The 24 VDC output 

from some controllers may not have enough current to power the 

MT-6050iV3. 

 

Caution  

Wire Routing 

Wire lengths should be minimized (Maximum 1600’ (500 m) shielded, 

1000’ (300 m) unshielded). 

Wires should be run in pairs with a neutral or common paired with a hot or 

signal line. 

If wiring is to be exposed to lightning or surges, use appropriate surge 

suppression devices. 

Keep AC, high energy, and rapidly switching DC wiring separate from 

signal wires. 

Equip ungrounded DC supplies with a resistor and capacitor in parallel to 

earth ground. This provides a path for static and high frequency dissipation. 

Typical values to use are 1MOhm and 4700pF. 

 

Caution  

 

To prevent the HMI from becoming damaged or having sound output issues, 

after turning the device off, please wait 10 seconds before turning the device 

on again. 

 

Connection 

To make a connection, strip about 3/8” of insulation off the end of the wire, 

turn the connector screw counterclockwise until the gap is wide open, insert 

the wire all the way in, and turn the screw clockwise until it’s tight. 

Connect positive DC line to the ‘+24V’ terminal and the DC ground to the 

‘0V‘ terminal. 

2.2.2 Grounding Requirements 

 

 

Chassis ground must be used.    DC ground is not directly coupled to Earth 

ground internally. It is preferable not to ground DC negative return to chassis 

ground as poor site earths can introduce noise into a system, but if necessary 

an earth connection should be made, from the power supply return point to 

the central star earth point. Ground conductors should be as short and as large 

in size as possible. The conductors must always be large enough to carry the 

maximum short circuit current of the path being considered. Ground 

conductors should be connected to a tree from a central star earth ground 

point. This ensures that no ground conductor carries current from any other 

branch. 

2.2.3 CE Requirements 

To make an MT-6050iV3 comply with EMC directives, and to reduce susceptibility to electrical 

interference, a separate #14 AWG ground wire should be taken to the chassis ground terminal of the 
power connector. This ground connection should be run directly to the central star earth connection 
point (as recommended in most Installation Instructions). 

2.2.4 Safety Guidelines 

This section presents recommended installation practices, and procedures. Since no two 

applications are identical, these recommendations should be considered as guidelines. 

 

Hardware 
Considerations 

WARNING! 
The system designer should be aware that devices in Controller systems could 

fail and thereby create an unsafe condition. Furthermore, electrical 

interference in an operator interface, such as an MT-6050iV3, can lead to 

equipment start-up, which could result in property damage and/or physical 

injury to the equipment operator. 
If you, or your company, use any programmable control systems that require 

an operator or attendant, you should be aware that this potential safety hazard 

exists and take appropriate precautions. Although the specific design steps 

depend on your particular application, the following precautions generally 
apply to installation of solid-state programmable control devices. In addition, 

these precautions conform to the guidelines for installation of Controllers as 

recommended in the NEMA ICS 3-304 Control Standards. 

Summary of Contents for MT-6050iV3 Series

Page 1: ...es has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Pro...

Page 2: ...are followed See Specifications z Do not operate the unit in areas subject to explosion hazards due to flammable gases vapors or dusts z The unit should not be installed where fast temperature variat...

Page 3: ...int to the central star earth point Ground conductors should be as short and as large in size as possible The conductors must always be large enough to carry the maximum short circuit current of the p...

Page 4: ...t errors that might be introduced if programs are changed while the equipment is in operation z The ICS 3 304 81 Safety Recommendations are reproduced by permission of the National Electrical Manufact...

Page 5: ...specific location Advanced 2 Check Include this location in the search and assign the path to install Weintek HMI i Series driver from C EB8000 usbdriver 3 If the USB driver successfully be installed...

Page 6: ...rked to indicate compliance with the EMC Directive The MT 6050iV3 Series has been designed to operate satisfactorily in electromagnetic noise immunity and without emitting high levels of electrical no...

Page 7: ...port N A USB USB Client port x 1 Processor 32bit RISC CPU 400MHz Flash memory 128MB SD card slot N A RTC N A General Specification Input Power 24 20 VDC Max Power Consumption 250 mA 24VDC Isolated Pow...

Page 8: ...Power Connector 128mm 5 039 102mm 4 016 119mm 4 685 93mm 3 661 R2mm R0 079 MT6050iV3 119mm 4 685 W x 93mm 3 661 H Front View 38 22mm 1 505 Reset DIP SW COM 117 73mm 4 635 91 53mm 3 603 FUSE5X20 a b c...

Reviews: