iR-COP
23
04
h
synchronous (cyclic every 4
th
sync)
…..
…..
…..
…..
F0
h
synchronous (cyclic every 240
th
sync)
F1
h
reserved
…..
…..
…..
…..
FB
h
reserved
FC
h
RTR-only (synchronous)
FD
h
RTR-only (event-driven)
FE
h
event-driven (manufacturer-specific)
FF
h
event-driven (device profile and application profile specific)
Word index 03h: Inhibit Time
When Transmission Type of PDO is set to FEh/FFh, the inhibit time specifies the
minimum length of time in 100µs that must be allowed to elapse between the
transmissions. 0 means disabling this function.
Word index 05h: Event Timer
When Transmission Type of PDO is set to FEh/FFh, the Event Timer specifies the
minimum length of time in milliseconds that must be allowed to elapse between
the transmissions. 0 means disabling this function.
6.2.3
PDO Mapping Parameter
Index
Sub-
index
Description
Type
ro/
rw
Default
RPDO1 mapping parameter
(digital outputs)
1600h
00h
Number of mapped application objects in
RPDO1
UNSIGNED8
rw
08h
01h
1st application object
UNSIGNED32
rw
6200 01 08h
02h
2st application object
UNSIGNED32
rw
6200 02 08h
03h
3st application object
UNSIGNED32
rw
6200 03 08h
04h
4st application object
UNSIGNED32
rw
6200 04 08h
05h
5st application object
UNSIGNED32
rw
6200 05 08h
06h
6st application object
UNSIGNED32
rw
6200 06 08h
07h
7st application object
UNSIGNED32
rw
6200 07 08h
08h
8st application object
UNSIGNED32
rw
6200 08 08h
RPDO2 mapping parameter
(analog outputs
)
1601h
00h
Number of mapped application objects in
PDO
UNSIGNED8
rw
04h
01h
1st application object
UNSIGNED32
rw
6411 01 10h
02h
2st application object
UNSIGNED32
rw
6411 02 10h