iR-COP
33
Analog I/O
iR-AQ04-VI
55mA/0.275w
--
iR-AI04-VI
70mA/0.35W
--
iR-AM06-VI
70mA/0.35W
--
iR-AI04-TR
65mA/0.325w
--
Note:
The coupler is the only power supply for the modules in this system. Please consider power requirements
when connecting multiple modules.
Example:
Device
Name
Consumption
Power Supply
Coupler
iR-COP
170mA/0.85w
2A/10w
Module
iR-DQ08-R *8
220mA*8=1.76A
X
System
Power consumption ∶ 170mA + 1.76A = 1.93 A
Power supply: 2A > 1.93A
8
Connecting Remote I/O using CODESYS