1. Network Wiring Diagram
Connect a cMT-SVR to a router via an Ethernet cable as the diagram shows below.
The default IP address of LAN 1 is DHCP. The default IP address of LAN 2 is static IP 192.168.100.1. The
IP addresses of LAN 1 and LAN 2 must be configured to different subnets.
cMT-SVR LAN Ports:
cMT-SVR HMI is equipped with two independent Ethernet ports which isolate the device network
from the company/factory network. LAN1 is a WAN (Wide Area Network) port which is allowed to
connect to a public network or another network via a gateway. LAN2 is a LAN (Local Area Network)
port.