Exhaust fans and other air-using devices:

 Size air 

openings large enough to supply all air-using devices 
in addition to the minimum size required for combustion 
air. If there is any possibility of the equipment room 
developing a negative pressure due to exhaust fans, 
clothes dryers, etc., either pipe combustion air directly to 
the burner or provide a sealed enclosure for the burner 
and supply it with its own combustion air supply.

Safety Shutoff for Direct Vent System

The direct vent blocked 

fl

 ue safety shut off system, refer 

to Figure 3,  shuts down the burner if the exhaust 

fl

 ue is 

blocked and/or if the air inlet is blocked.  It recognizes 
a blocked 

fl

 ue by sensing excessive pressure in the 

combustion chamber.  It recognizes a blocked inlet by 
sensing excessive vacuum in the air inlet adapter.
This system meets the requirements for a blocked 

fl

 ue or 

blocked combustion air inlet per CSA Standard B140.0.  
It is designed to interrupt the cad cell circuit and allow 
the control to shut down the burner. 

Direct/Sidewall Venting Application 

For direct vent installations, follow instructions provided 
with appliance and direct vent system.  Outside 
combustion air is required for direct venting.
When installing an NX outside air adapter (Beckett Part 
Number 52018U), refer to the instruction sheet supplied 
with the adapter. This kit allows combustion air to be 

Figure 3. Pressure Switch Installation

piped directly to the burner. The NX outside air adapter  
kit may also be used for chimney vent applications that 
require outside combustion air.

Mounting dimensions

When using the Beckett universal adjustable 

fl

 ange, 

mount the air tube at a 2° downward pitch unless 
otherwise speci

fi

 ed by the appliance manufacturer.

Verify that the air tube installed on the burner 
provides the correct insertion depth. See Figure 4.

1.

2.

Figure 4. – Mounting Burner in Appliance

SK8745

Tilt down 2°

If space between burner 

air tube and opening 

exceeds 1/2 inch, pack 

burner opening with 

ceramic fiber refractory.

Connect Outside Air Duct 
to NX Adapter

The outside air adapter must be installed by strictly 
following the kit installation instructions. 
DO NOT attempt to install outside air piping without 
using the outside air adapter and instructions 
provided. 
Abundant fresh air is required for proper combustion.

y

y

y

Failure to install adapter properly could 

result in impaired combustion, appliance 

soot-up, puffback of smoke, and fi re or 

asphyxiation hazards.

Do not attempt to install outside air piping to 
the burner without using the outside air kit and 
instructions.

y

Failure to comply could result in impaired 

combustion, appliance soot-up, puffback of smoke, 

and fi re or asphyxiation hazards.

Follow the Outside Air Kit 
Instructions Exactly

Section: Inspect/Prepare Installation SIte

Summary of Contents for UO-3 CV

Page 1: ...or service work Save this manual for future reference Incorrect installation adjustment or misuse of this burner could result in death severe personal injury or substantial property damage To the Pro...

Page 2: ...2...

Page 3: ...especially during the summer in order to prevent condensation of moisture on the inside surface of the tank y y y y y Remainder of manual to be used ONLY BY QUALIFIED SERVICE TECHNICIANS Weil McLain B...

Page 4: ...t the air inlet openings to the burner or the combustion air ventilation openings in the room y y y y y Please read and understand the manual supplied with this equipment This equipment must be instal...

Page 5: ...3 See Note 2 1 00 NX70LC 1 3 4 0 75 X 60 B Hago 0 75 X 60 B Delavan 175 2 50 UO 4 DV WL6504 See Note 2 1 20 NX90LB 3 1 2 0 85 X 60 W Delavan 0 85 X 60 W Hago 190 4 00 UO 5 DV WL6505 See Note 2 1 40 NX...

Page 6: ...NX90LB 0 40 1 35 6 Slot NX50LC NX70LC NX90LC 1 10 1 75 9 Slot NX50LD NX70LD NX90LD 1 10 1 75 6 Slot NX50LF NX70LF NX90LF Inspect Prepare Installation Site Clearances to Burner and Appliance Provide s...

Page 7: ...ded that an approved insulated stainless steel liner be installed 3 4 5 6 7 For those installations not requiring a chimney such as through the wall vented appliances follow the instructions given by...

Page 8: ...truction sheet supplied with the adapter This kit allows combustion air to be Figure 3 Pressure Switch Installation piped directly to the burner The NX outside air adapter kit may also be used for chi...

Page 9: ...e the bypass plug is NOT installed in the fuel unit Manual bleeding of the fuel unit is required on initial start up If connecting a two pipe fuel supply install the fuel unit bypass plug Oil Leak and...

Page 10: ...rer s wiring diagram prior to connecting the burner wiring All wiring must be in accordance with the latest revision of national Electric Code NFPA 70 and all local codes and regulations In Canada all...

Page 11: ...inals as shown in Figures 7a and 7b Refer to the label on the underside of the control for wiring details Motor off delay on a 7505P will be disabled if the safety and operating limits as shown in Fig...

Page 12: ...on sequence The control will continue to Recycle each time the flame is lost until it reaches a pre set time allotment The control will then go into Hard Lockout instead of recycle This feature preven...

Page 13: ...as the button is held Enables Pump Priming After the reset button has been held for 15 seconds the button can then be clicked during the next ignition sequence to enter Pump Prime mode Run igniter is...

Page 14: ...The fuel valve is opened A flame should be established within the 15 second lockout time LOCKOUT If flame is not sensed by the end of the TFI the control shuts down on safety lockout and must be manu...

Page 15: ...until the retention head engages the fixed stops in the retention ring at the end of the air tube Refer to Figure 10 Tighten the zero setting locking nut The rear door must be closed The adjustment sc...

Page 16: ...Head Retention Head Head Support Legs Head Support Legs Electrode Tips Electrode Tips Electrode Clamp Electrode Clamp Electrode Bracket Electrode Bracket Electrode Insulator Electrode Insulator Elect...

Page 17: ...lint or foreign material Use a clean soft cloth with a degreaser to clean any accumulated soot or oil stains from the throttle cup sight windows Check motor current The amp draw should not exceed the...

Page 18: ...utilizes pressures higher than 100 psig so the actual nozzle flow rate will be greater than the gph stamped on the nozzle body Example A 1 00 gph nozzle 140 psig 1 18 gph For typical nozzle flow rates...

Page 19: ...92 0 99 1 06 0 85 0 95 1 01 1 04 1 13 1 20 0 90 1 01 1 07 1 10 1 19 1 27 1 00 1 12 1 18 1 23 1 32 1 41 1 10 1 23 1 30 1 35 1 46 1 56 1 20 1 34 1 42 1 47 1 59 1 70 1 25 1 39 1 48 1 53 1 65 1 77 1 35 1...

Page 20: ...he splined nut and the lower acorn nut 1 2 3 Turn the air adjustment screw clockwise to adjust the plate with the pointer to the zero position Referring to Figure 10 slide the nozzle line assembly for...

Page 21: ...21 Weil McLain Ultra Oil NX Burner Manual Figure 13 Retention Head Throttle Cup Alignment Figure 14 Blower wheel assembly SK9670 Section Trained Service Technician s Regular Maintenance...

Page 22: ...22 4 22 19 9 17 16 23 10 1 24 6 7 2 15 11a 11c 11b 25 21 26 20 11d 8 5 Section Replacement Parts For best performance specify genuine Beckett replacement parts Replacement Parts...

Page 23: ...et air louvers 1013U 19 Nozzle Line Electrode and Head Assembly Specify 20 PSC Motor Requires Mounting screws 20 x 7 8 21805U 4189 21 Primary control 7505P 22 Retention head assembly 6 slot 51785U 23...

Page 24: ...e choose one of the following options Visit our website at www beckettcorp com warranty Email your request to rwb customer service beckettcorp com Write to R W Beckett Corporation P O Box 1289 Elyria...

Reviews: