Weil-McLain UO-3 CV Instruction Manual Download Page 16

16

Allow the burner to run for approximately 5 to 10 

minutes.

1.

Step 2: 

At the trace of smoke level, measure the 

CO

2

 (or O

2

) . This is the vital reference 

point for further adjustments.  Example: 
13.5% CO

2

 (2.6% O

2

)

Step 3:

 Increase the air to reduce the CO

2

 by 1.5 to 

2 percentage points. (O

2

 will be increased 

by approximately 2.0 to 2.7 percentage 
points.)   Example: Reduce CO

2

 from 

13.5% to 11.5% (2.6% to 5.3% O

2

).  

Step 4:

 Recheck smoke level. It should be Zero.

 

This procedure provides a margin of 
reserve air to accommodate variable 
conditions.

 

If the draft level has changed, recheck the
smoke and CO

2

 levels and readjust 

burner, if necessary. 

Step 5:

 Once the combustion has been set, tighten 

the lower acorn nut and splined nut on the 
air adjustment assembly. See Figure 9.

Chimney Vent Systems:  Install the burner cover 
and repeat Steps 2 and 4 above. If CO

2

 increases 

(O

2

 decreases), remove the cover and adjust the 

air setting so the CO

2

 (O

2

) with the cover installed 

meets the requirements of Step 3.
Direct Vent Systems with outside air ducted to 
burner:  Install the burner cover.
Start and stop the burner several times to ensure 
satisfactory operation. Test the primary control 
and all other appliance safety controls to verify 
that they function according to the manufacturer’s 
speci

fi

 cations.

4.

5.

6.

Figure 10. – Nozzle Line/Head/Air Tube Assembly  (Low fi ring rate shown.) 

Retention Head

Retention Head

Head Support Legs

Head Support Legs

Electrode Tips

Electrode Tips

Electrode Clamp

Electrode Clamp

Electrode Bracket

Electrode Bracket

Electrode Insulator

Electrode Insulator

Electrode Extension Rods

Electrode Extension Rods

Nozzle Adapter

Nozzle Adapter

Nozzle

Nozzle

Stops in Retention Ring

Stops in Retention Ring

Retention Ring

Retention Ring

Throttle Ring

Throttle Ring

Throttle Cup

Throttle Cup

Nozzle Line

Nozzle Line

Bulkhead Fitting

Bulkhead Fitting

SK9666A

SK9666A

Throttle Cup Hub

Throttle Cup Hub

Set the stack or over-

fi

 re draft to the level speci

fi

 ed 

by the appliance manufacturer.

Natural Draft Applications; 

typically over-

fi

 re 

draft is -0.01” or   -0.02” w.c. 

Direct Venting

; typically may not require draft 

adjustment.

High Effi ciency/Positive Pressure Appliances

also vary from traditional appliances (see 
manufacturer’s recommendations).

Follow these 

fi

 ve steps to properly adjust the 

burner:

Step 1:

 Adjust the head/air until a trace of smoke 

is achieved.  This can be accomplished 
by turning the screw on the head/air 
adjustment plate assembly to increase air 
(CCW) or decrease air (CW).

2.

3.

The NX burner has a reduced 
diameter air tube, precision-

designed air throttle cup and combustion head 
for improved performance.  This design provides 
very accurate control of the air/fuel ratio, but the 
light reaching the cad cell through small holes in 
these components is limited.  Because of this, 

the 

average cad cell resistance may be higher than 
conventional burners

 with larger openings.

Section: Start the Burner and Set Combustion

Summary of Contents for UO-3 CV

Page 1: ...or service work Save this manual for future reference Incorrect installation adjustment or misuse of this burner could result in death severe personal injury or substantial property damage To the Pro...

Page 2: ...2...

Page 3: ...especially during the summer in order to prevent condensation of moisture on the inside surface of the tank y y y y y Remainder of manual to be used ONLY BY QUALIFIED SERVICE TECHNICIANS Weil McLain B...

Page 4: ...t the air inlet openings to the burner or the combustion air ventilation openings in the room y y y y y Please read and understand the manual supplied with this equipment This equipment must be instal...

Page 5: ...3 See Note 2 1 00 NX70LC 1 3 4 0 75 X 60 B Hago 0 75 X 60 B Delavan 175 2 50 UO 4 DV WL6504 See Note 2 1 20 NX90LB 3 1 2 0 85 X 60 W Delavan 0 85 X 60 W Hago 190 4 00 UO 5 DV WL6505 See Note 2 1 40 NX...

Page 6: ...NX90LB 0 40 1 35 6 Slot NX50LC NX70LC NX90LC 1 10 1 75 9 Slot NX50LD NX70LD NX90LD 1 10 1 75 6 Slot NX50LF NX70LF NX90LF Inspect Prepare Installation Site Clearances to Burner and Appliance Provide s...

Page 7: ...ded that an approved insulated stainless steel liner be installed 3 4 5 6 7 For those installations not requiring a chimney such as through the wall vented appliances follow the instructions given by...

Page 8: ...truction sheet supplied with the adapter This kit allows combustion air to be Figure 3 Pressure Switch Installation piped directly to the burner The NX outside air adapter kit may also be used for chi...

Page 9: ...e the bypass plug is NOT installed in the fuel unit Manual bleeding of the fuel unit is required on initial start up If connecting a two pipe fuel supply install the fuel unit bypass plug Oil Leak and...

Page 10: ...rer s wiring diagram prior to connecting the burner wiring All wiring must be in accordance with the latest revision of national Electric Code NFPA 70 and all local codes and regulations In Canada all...

Page 11: ...inals as shown in Figures 7a and 7b Refer to the label on the underside of the control for wiring details Motor off delay on a 7505P will be disabled if the safety and operating limits as shown in Fig...

Page 12: ...on sequence The control will continue to Recycle each time the flame is lost until it reaches a pre set time allotment The control will then go into Hard Lockout instead of recycle This feature preven...

Page 13: ...as the button is held Enables Pump Priming After the reset button has been held for 15 seconds the button can then be clicked during the next ignition sequence to enter Pump Prime mode Run igniter is...

Page 14: ...The fuel valve is opened A flame should be established within the 15 second lockout time LOCKOUT If flame is not sensed by the end of the TFI the control shuts down on safety lockout and must be manu...

Page 15: ...until the retention head engages the fixed stops in the retention ring at the end of the air tube Refer to Figure 10 Tighten the zero setting locking nut The rear door must be closed The adjustment sc...

Page 16: ...Head Retention Head Head Support Legs Head Support Legs Electrode Tips Electrode Tips Electrode Clamp Electrode Clamp Electrode Bracket Electrode Bracket Electrode Insulator Electrode Insulator Elect...

Page 17: ...lint or foreign material Use a clean soft cloth with a degreaser to clean any accumulated soot or oil stains from the throttle cup sight windows Check motor current The amp draw should not exceed the...

Page 18: ...utilizes pressures higher than 100 psig so the actual nozzle flow rate will be greater than the gph stamped on the nozzle body Example A 1 00 gph nozzle 140 psig 1 18 gph For typical nozzle flow rates...

Page 19: ...92 0 99 1 06 0 85 0 95 1 01 1 04 1 13 1 20 0 90 1 01 1 07 1 10 1 19 1 27 1 00 1 12 1 18 1 23 1 32 1 41 1 10 1 23 1 30 1 35 1 46 1 56 1 20 1 34 1 42 1 47 1 59 1 70 1 25 1 39 1 48 1 53 1 65 1 77 1 35 1...

Page 20: ...he splined nut and the lower acorn nut 1 2 3 Turn the air adjustment screw clockwise to adjust the plate with the pointer to the zero position Referring to Figure 10 slide the nozzle line assembly for...

Page 21: ...21 Weil McLain Ultra Oil NX Burner Manual Figure 13 Retention Head Throttle Cup Alignment Figure 14 Blower wheel assembly SK9670 Section Trained Service Technician s Regular Maintenance...

Page 22: ...22 4 22 19 9 17 16 23 10 1 24 6 7 2 15 11a 11c 11b 25 21 26 20 11d 8 5 Section Replacement Parts For best performance specify genuine Beckett replacement parts Replacement Parts...

Page 23: ...et air louvers 1013U 19 Nozzle Line Electrode and Head Assembly Specify 20 PSC Motor Requires Mounting screws 20 x 7 8 21805U 4189 21 Primary control 7505P 22 Retention head assembly 6 slot 51785U 23...

Page 24: ...e choose one of the following options Visit our website at www beckettcorp com warranty Email your request to rwb customer service beckettcorp com Write to R W Beckett Corporation P O Box 1289 Elyria...

Reviews: