Weil-McLain UO-3 CV Instruction Manual Download Page 13

13

Weil-McLain Ultra Oil NX

 Burner Manual

Table 5 - Status Lights

Light Color

On Continuously

Flashing

Red

Restricted (Hard) Lockout

Soft Lockout

Green

Flame Sensed during normal operation 
(Could be stray light during standby)

Recycle

Yellow

Control is in Pump Prime mode 

or

Reset button currently held for 15+ seconds.

N/A

Table 4 - Reset Button Operation

If the burner is in the 

below state:

Pushing the reset button will:

Button Click

(press < 1 second)

Button Hold

(press > 1 second)

Button Hold 

(press 15+ seconds)

Lockout

Reset from Soft Lockout

Reset from Restricted (Hard) 
Lockout

Valve-on Delay, Trial for 
Ignition, Ignition Carryover

Go to Pump Prime (see “Priming 
the Pump” above)

Disable the Burner:
Any time the burner is running, 
press and hold the reset but-
ton to disable the burner.  The 
burner will remain off as long as 
the button is held.

Enables Pump Priming: 
After the reset button has been 
held for 15 seconds, the button 
can then be clicked during the 
next ignition sequence to enter 
Pump Prime mode.

Run (igniter is shut off)

No action

Motor-Off Delay, Standby

No action

Pump Prime

No action

Exit Pump Prime mode and return to Standby

Reset Button Operation

The table below explains what action the control will take when the reset button is pressed for different lengths of time during the 
various burner operating states.

Figure 8.  GeniSys Model 7505 Control

Section: Burner Control

Display Module:

Permanent device for programming 
and diagnostics

Alarm Module:

For adding isolated low voltage alarm 
contacts to the base control. See Alarm 
Module Instructions for speci

fi

 cations.

Contractor’s Tool:

Hand-held device for 
programming and diagnostics

Cad Cell
Connections

Wiring 
Connections

Communication Port 2

Reset Button with Red Light

Communication Port 1

Thermostat Terminals

Green Light

Yellow Light

Optional Components

:

Summary of Contents for UO-3 CV

Page 1: ...or service work Save this manual for future reference Incorrect installation adjustment or misuse of this burner could result in death severe personal injury or substantial property damage To the Pro...

Page 2: ...2...

Page 3: ...especially during the summer in order to prevent condensation of moisture on the inside surface of the tank y y y y y Remainder of manual to be used ONLY BY QUALIFIED SERVICE TECHNICIANS Weil McLain B...

Page 4: ...t the air inlet openings to the burner or the combustion air ventilation openings in the room y y y y y Please read and understand the manual supplied with this equipment This equipment must be instal...

Page 5: ...3 See Note 2 1 00 NX70LC 1 3 4 0 75 X 60 B Hago 0 75 X 60 B Delavan 175 2 50 UO 4 DV WL6504 See Note 2 1 20 NX90LB 3 1 2 0 85 X 60 W Delavan 0 85 X 60 W Hago 190 4 00 UO 5 DV WL6505 See Note 2 1 40 NX...

Page 6: ...NX90LB 0 40 1 35 6 Slot NX50LC NX70LC NX90LC 1 10 1 75 9 Slot NX50LD NX70LD NX90LD 1 10 1 75 6 Slot NX50LF NX70LF NX90LF Inspect Prepare Installation Site Clearances to Burner and Appliance Provide s...

Page 7: ...ded that an approved insulated stainless steel liner be installed 3 4 5 6 7 For those installations not requiring a chimney such as through the wall vented appliances follow the instructions given by...

Page 8: ...truction sheet supplied with the adapter This kit allows combustion air to be Figure 3 Pressure Switch Installation piped directly to the burner The NX outside air adapter kit may also be used for chi...

Page 9: ...e the bypass plug is NOT installed in the fuel unit Manual bleeding of the fuel unit is required on initial start up If connecting a two pipe fuel supply install the fuel unit bypass plug Oil Leak and...

Page 10: ...rer s wiring diagram prior to connecting the burner wiring All wiring must be in accordance with the latest revision of national Electric Code NFPA 70 and all local codes and regulations In Canada all...

Page 11: ...inals as shown in Figures 7a and 7b Refer to the label on the underside of the control for wiring details Motor off delay on a 7505P will be disabled if the safety and operating limits as shown in Fig...

Page 12: ...on sequence The control will continue to Recycle each time the flame is lost until it reaches a pre set time allotment The control will then go into Hard Lockout instead of recycle This feature preven...

Page 13: ...as the button is held Enables Pump Priming After the reset button has been held for 15 seconds the button can then be clicked during the next ignition sequence to enter Pump Prime mode Run igniter is...

Page 14: ...The fuel valve is opened A flame should be established within the 15 second lockout time LOCKOUT If flame is not sensed by the end of the TFI the control shuts down on safety lockout and must be manu...

Page 15: ...until the retention head engages the fixed stops in the retention ring at the end of the air tube Refer to Figure 10 Tighten the zero setting locking nut The rear door must be closed The adjustment sc...

Page 16: ...Head Retention Head Head Support Legs Head Support Legs Electrode Tips Electrode Tips Electrode Clamp Electrode Clamp Electrode Bracket Electrode Bracket Electrode Insulator Electrode Insulator Elect...

Page 17: ...lint or foreign material Use a clean soft cloth with a degreaser to clean any accumulated soot or oil stains from the throttle cup sight windows Check motor current The amp draw should not exceed the...

Page 18: ...utilizes pressures higher than 100 psig so the actual nozzle flow rate will be greater than the gph stamped on the nozzle body Example A 1 00 gph nozzle 140 psig 1 18 gph For typical nozzle flow rates...

Page 19: ...92 0 99 1 06 0 85 0 95 1 01 1 04 1 13 1 20 0 90 1 01 1 07 1 10 1 19 1 27 1 00 1 12 1 18 1 23 1 32 1 41 1 10 1 23 1 30 1 35 1 46 1 56 1 20 1 34 1 42 1 47 1 59 1 70 1 25 1 39 1 48 1 53 1 65 1 77 1 35 1...

Page 20: ...he splined nut and the lower acorn nut 1 2 3 Turn the air adjustment screw clockwise to adjust the plate with the pointer to the zero position Referring to Figure 10 slide the nozzle line assembly for...

Page 21: ...21 Weil McLain Ultra Oil NX Burner Manual Figure 13 Retention Head Throttle Cup Alignment Figure 14 Blower wheel assembly SK9670 Section Trained Service Technician s Regular Maintenance...

Page 22: ...22 4 22 19 9 17 16 23 10 1 24 6 7 2 15 11a 11c 11b 25 21 26 20 11d 8 5 Section Replacement Parts For best performance specify genuine Beckett replacement parts Replacement Parts...

Page 23: ...et air louvers 1013U 19 Nozzle Line Electrode and Head Assembly Specify 20 PSC Motor Requires Mounting screws 20 x 7 8 21805U 4189 21 Primary control 7505P 22 Retention head assembly 6 slot 51785U 23...

Page 24: ...e choose one of the following options Visit our website at www beckettcorp com warranty Email your request to rwb customer service beckettcorp com Write to R W Beckett Corporation P O Box 1289 Elyria...

Reviews: