Weil-McLain UO-3 CV Instruction Manual Download Page 6

6

Certifi cations/approvals

Underwriters Laboratories has certi

fi

 ed this burner 

to comply with ANSI/UL 296 and CSA-B139. 

Low 

sulfur #1 and #2 fuel oils reduce heat exchanger 
deposits with all burners compared to the standard 
fuels. Reduced deposits extend the service 
interval for cleaning and improve the effi ciency of 
the appliance over time. Low sulfur fuels reduce 
particulate and oxides of nitrogen emissions as 
well. The Oilheat Manufacturers’ Association 
recommends these fuels as the preferred fuels for 
this burner.

Notice Special Requirements

THE INSTALLATION OF A BURNER SHALL BE IN 
ACCORDANCE WITH THE REGULATIONS OF 
AUTHORITIES HAVING JURISDICTION.
For recommended installation practices in the U.S. 
refer to the latest edition of NFPA 31. (CSA-B139 
and CSA-B140 in Canada.
Concealed damage — If you discover damage to 
the burner or controls during unpacking, notify the 
carrier at once and 

fi

 le the appropriate claim.

When contacting Beckett for service information 
— Please record the burner serial number (and have 
available when calling or writing). You will 

fi

 nd the 

serial number on the silver label located on the left 
rear of the burner. Refer to Figure 1.

Starting with minimum gph 

fi

 ring rate, the minimum 

size recommended is 6” 

fl

 ue pipe with 8” X 8” 

inside chimney, unless speci

fi

 ed otherwise by the 

appliance manufacturer.
A chimney 

fl

 ue shall extend at least 3 feet above 

the highest point at which the chimney comes in 
contact with the roof, and not less than 2 feet above 
the highest roof surface or structure within 10 feet 
horizontally of the chimney.  Refer to  Figure 2.

1.

2.

Table 3. – Air Tube Combinations (ATC)

Firing rate 

(gph)

Head

ATC codes for usable air tube 

lengths:

(min-max)

5”

7”

9”

0.40-1.35

9-Slot

NX50LB

NX70LB

NX90LB

0.40-1.35

6-Slot

NX50LC

NX70LC

NX90LC

1.10-1.75

9-Slot

NX50LD

NX70LD

NX90LD

1.10-1.75

6-Slot

NX50LF

NX70LF

NX90LF

Inspect/Prepare 

Installation Site

Clearances to Burner and Appliance

Provide space around burner and appliance for ease 
of service and maintenance. Check the minimum 
clearances against those shown by the appliance 
manufacturer and by applicable building codes.

Inspect Chimney or Direct Vent System

General Information

Table 2. – Burner Specifi cations

Capacity
LB & LC

Firing rate:  0.40 – 1.35 GPH 
Input:  56,000 – 189,000 Btu

Capacity
LD & LF

Firing rate:  1.10 - 1.75 GPH 
Input:  154,000 – 245,000 Btu/h

Fuels

U. S.

 No. 1 or No. 2 heating oil only (ASTM D396)

Canada

 No. 1 stove oil or No. 2 furnace oil only

Electrical

Power supply:

  120 VAC, 60 Hz,  single phase

Operating load:

    5.8 Amps max

Motor:

    1/7 hp, 3450 rpm, NEMA 48M frame 

PSC rotation CCW when facing shaft end

Ignition:

    Continuous duty solid-state igniter

Fuel pump

Outlet pressure - See Note 1

Air tube

ATC code - See Table 3

Dimensions
(with cover)

Height (maximum):   12-1/2 inches
Width (maximum):   .15 inches
Depth: 9-1/4 inches
Air tube diameter:   3-1/4 inches

*

Note 1.  See appliance manufacturer’s burner specifi cations for recom-

mended outlet pressure.

DO NOT USE GASOLINE, CRANKCASE 

OIL, OR ANY OIL CONTAINING GASOLINE.

Carefully inspect the chimney or exhaust vent 
system.
Make sure it is properly sized and in good working 
condition. 
Follow the instructions supplied by the appliance 
manufacturer.
The installation must strictly comply with all 
applicable codes, authorities having jurisdiction and 
the latest revision of the National Fire Protection 
Association Standard  NFPA 31 for the installation of 
chimneys and vent sizing, (or CSA-B139 and CSA-
B140 in Canada).
Regulation by these authorities take precedence 
over the general instructions provided in this 
installation manual.

y

y

y

y

y

Fire, Smoke & Asphyxiation 
Hazard

Section: General Information & Inspect/Prepare Installation SIte

Summary of Contents for UO-3 CV

Page 1: ...or service work Save this manual for future reference Incorrect installation adjustment or misuse of this burner could result in death severe personal injury or substantial property damage To the Pro...

Page 2: ...2...

Page 3: ...especially during the summer in order to prevent condensation of moisture on the inside surface of the tank y y y y y Remainder of manual to be used ONLY BY QUALIFIED SERVICE TECHNICIANS Weil McLain B...

Page 4: ...t the air inlet openings to the burner or the combustion air ventilation openings in the room y y y y y Please read and understand the manual supplied with this equipment This equipment must be instal...

Page 5: ...3 See Note 2 1 00 NX70LC 1 3 4 0 75 X 60 B Hago 0 75 X 60 B Delavan 175 2 50 UO 4 DV WL6504 See Note 2 1 20 NX90LB 3 1 2 0 85 X 60 W Delavan 0 85 X 60 W Hago 190 4 00 UO 5 DV WL6505 See Note 2 1 40 NX...

Page 6: ...NX90LB 0 40 1 35 6 Slot NX50LC NX70LC NX90LC 1 10 1 75 9 Slot NX50LD NX70LD NX90LD 1 10 1 75 6 Slot NX50LF NX70LF NX90LF Inspect Prepare Installation Site Clearances to Burner and Appliance Provide s...

Page 7: ...ded that an approved insulated stainless steel liner be installed 3 4 5 6 7 For those installations not requiring a chimney such as through the wall vented appliances follow the instructions given by...

Page 8: ...truction sheet supplied with the adapter This kit allows combustion air to be Figure 3 Pressure Switch Installation piped directly to the burner The NX outside air adapter kit may also be used for chi...

Page 9: ...e the bypass plug is NOT installed in the fuel unit Manual bleeding of the fuel unit is required on initial start up If connecting a two pipe fuel supply install the fuel unit bypass plug Oil Leak and...

Page 10: ...rer s wiring diagram prior to connecting the burner wiring All wiring must be in accordance with the latest revision of national Electric Code NFPA 70 and all local codes and regulations In Canada all...

Page 11: ...inals as shown in Figures 7a and 7b Refer to the label on the underside of the control for wiring details Motor off delay on a 7505P will be disabled if the safety and operating limits as shown in Fig...

Page 12: ...on sequence The control will continue to Recycle each time the flame is lost until it reaches a pre set time allotment The control will then go into Hard Lockout instead of recycle This feature preven...

Page 13: ...as the button is held Enables Pump Priming After the reset button has been held for 15 seconds the button can then be clicked during the next ignition sequence to enter Pump Prime mode Run igniter is...

Page 14: ...The fuel valve is opened A flame should be established within the 15 second lockout time LOCKOUT If flame is not sensed by the end of the TFI the control shuts down on safety lockout and must be manu...

Page 15: ...until the retention head engages the fixed stops in the retention ring at the end of the air tube Refer to Figure 10 Tighten the zero setting locking nut The rear door must be closed The adjustment sc...

Page 16: ...Head Retention Head Head Support Legs Head Support Legs Electrode Tips Electrode Tips Electrode Clamp Electrode Clamp Electrode Bracket Electrode Bracket Electrode Insulator Electrode Insulator Elect...

Page 17: ...lint or foreign material Use a clean soft cloth with a degreaser to clean any accumulated soot or oil stains from the throttle cup sight windows Check motor current The amp draw should not exceed the...

Page 18: ...utilizes pressures higher than 100 psig so the actual nozzle flow rate will be greater than the gph stamped on the nozzle body Example A 1 00 gph nozzle 140 psig 1 18 gph For typical nozzle flow rates...

Page 19: ...92 0 99 1 06 0 85 0 95 1 01 1 04 1 13 1 20 0 90 1 01 1 07 1 10 1 19 1 27 1 00 1 12 1 18 1 23 1 32 1 41 1 10 1 23 1 30 1 35 1 46 1 56 1 20 1 34 1 42 1 47 1 59 1 70 1 25 1 39 1 48 1 53 1 65 1 77 1 35 1...

Page 20: ...he splined nut and the lower acorn nut 1 2 3 Turn the air adjustment screw clockwise to adjust the plate with the pointer to the zero position Referring to Figure 10 slide the nozzle line assembly for...

Page 21: ...21 Weil McLain Ultra Oil NX Burner Manual Figure 13 Retention Head Throttle Cup Alignment Figure 14 Blower wheel assembly SK9670 Section Trained Service Technician s Regular Maintenance...

Page 22: ...22 4 22 19 9 17 16 23 10 1 24 6 7 2 15 11a 11c 11b 25 21 26 20 11d 8 5 Section Replacement Parts For best performance specify genuine Beckett replacement parts Replacement Parts...

Page 23: ...et air louvers 1013U 19 Nozzle Line Electrode and Head Assembly Specify 20 PSC Motor Requires Mounting screws 20 x 7 8 21805U 4189 21 Primary control 7505P 22 Retention head assembly 6 slot 51785U 23...

Page 24: ...e choose one of the following options Visit our website at www beckettcorp com warranty Email your request to rwb customer service beckettcorp com Write to R W Beckett Corporation P O Box 1289 Elyria...

Reviews: