Sequence of Operation - GeniSys 7505

Refer to the appliance manufacturer’s wiring diagram for 
actual specifi cations.

Standby

: The burner is idle, waiting for a call for 

heat. 

Valve-On Delay

: The igniter and motor are on while 

the control delays turning on the oil solenoid valve 
for the programmed time.

Trial For Ignition

: The oil solenoid valve is 

energized.  A 

fl

 ame should be established within the 

factory set trial for ignition time (lockout time).

Lockout

: The control has shut down for one of the 

following safety reasons:

The trial for ignition (lockout) time expired 
without 

fl

 ame being established.

The cad cell detected 

fl

 ame at the end of the 

Valve On Delay state.
To reset the control from lockout click the button 
1-second.

NOTE: 

A recurrence of the above failure 

modes or a failed welded relay check 
could cause the control to enter a 

Hard 

Lockout

 state that must be reset only 

by a quali

fi

 ed service technician.  

To reset from Hard Lockout, hold the 
reset button for 15 seconds until the 
yellow light turns on.

Ignition Carryover

: Once 

fl

 ame is 

established, the igniter remains on for 10 
additional seconds to ensure 

fl

 ame stability.  

Run

: The 

fl

 ame is sustained until the call for 

heat is satis

fi

 ed.  The burner is then sent to 

Motor-Off Delay, if applicable, or it is shut 
down and sent to Standby.

Recycle

: If the 

fl

 ame is lost while the 

burner is 

fi

 ring, the control shuts down the 

burner, enters a 60 second recycle delay, 

1.

2.

3.

4.

a.

b.

5.

6.

7.

and repeats the ignition sequence.  The control will 
continue to Recycle each time the 

fl

 ame is lost, until 

it reaches a pre-set time allotment.  The control will 
then go into Hard Lockout instead of recycle.  This 
feature prevents excessive accumulation of oil in 
the appliance 

fi

 ring chamber.

Motor-Off Delay

: If applicable, the oil solenoid 

valve is turned off and the control delays turning the 
motor off for the set motor-off delay time before the 
control returns to standby.

Pump Prime: 

The igniter and motor are on with the 

oil solenoid valve energized for 4 minutes.  During 
Pump Prime mode, the cad cell is disregarded, 
allowing the technician to prime the pump without 
having to jumper the cad cell.

Cad Cell Resistance Indicator: 

 If the Beckett 

7505 control is equipped with the GeniSys Display 
Module, part 52067U, the cad cell resistance can 
be selected and read on the LCD screen. Also, the 
GeniSys Contractor Tool, part 52082U, can be used 
for 

this 

purpose. 

    

 

 

 

 

 

 

 

If these are not available, the cad cell leads can 
be unplugged from the control and the resistance 
measured with a meter in the conventional way. 
Conduct these tests with 

fl

 ame present.

Flame Detection Range

Normal = 0 to 1600 ohms

Limited = 1600 ohms to lockout

8.

9.

10.

2

1

3

5

6

8

4

7

Standby

Motor-off delay

Valve-on delay

Trial for
ignition

Ignition carryover

Run

Lockout

Recycle

9

Pump
prime

Burner Control

The control can malfunction if it gets wet, leading to 
accumulation of oil or explosive oil vapors.
Never install where water can 

fl

 ood, drip or 

condense on the control.
Never use a control that has been wet - replace it.

y

y

y

Can cause severe injury, death, or property damage.

Fire or Explosion Hazard

Section: Burner Control

Summary of Contents for UO-3 CV

Page 1: ...or service work Save this manual for future reference Incorrect installation adjustment or misuse of this burner could result in death severe personal injury or substantial property damage To the Pro...

Page 2: ...2...

Page 3: ...especially during the summer in order to prevent condensation of moisture on the inside surface of the tank y y y y y Remainder of manual to be used ONLY BY QUALIFIED SERVICE TECHNICIANS Weil McLain B...

Page 4: ...t the air inlet openings to the burner or the combustion air ventilation openings in the room y y y y y Please read and understand the manual supplied with this equipment This equipment must be instal...

Page 5: ...3 See Note 2 1 00 NX70LC 1 3 4 0 75 X 60 B Hago 0 75 X 60 B Delavan 175 2 50 UO 4 DV WL6504 See Note 2 1 20 NX90LB 3 1 2 0 85 X 60 W Delavan 0 85 X 60 W Hago 190 4 00 UO 5 DV WL6505 See Note 2 1 40 NX...

Page 6: ...NX90LB 0 40 1 35 6 Slot NX50LC NX70LC NX90LC 1 10 1 75 9 Slot NX50LD NX70LD NX90LD 1 10 1 75 6 Slot NX50LF NX70LF NX90LF Inspect Prepare Installation Site Clearances to Burner and Appliance Provide s...

Page 7: ...ded that an approved insulated stainless steel liner be installed 3 4 5 6 7 For those installations not requiring a chimney such as through the wall vented appliances follow the instructions given by...

Page 8: ...truction sheet supplied with the adapter This kit allows combustion air to be Figure 3 Pressure Switch Installation piped directly to the burner The NX outside air adapter kit may also be used for chi...

Page 9: ...e the bypass plug is NOT installed in the fuel unit Manual bleeding of the fuel unit is required on initial start up If connecting a two pipe fuel supply install the fuel unit bypass plug Oil Leak and...

Page 10: ...rer s wiring diagram prior to connecting the burner wiring All wiring must be in accordance with the latest revision of national Electric Code NFPA 70 and all local codes and regulations In Canada all...

Page 11: ...inals as shown in Figures 7a and 7b Refer to the label on the underside of the control for wiring details Motor off delay on a 7505P will be disabled if the safety and operating limits as shown in Fig...

Page 12: ...on sequence The control will continue to Recycle each time the flame is lost until it reaches a pre set time allotment The control will then go into Hard Lockout instead of recycle This feature preven...

Page 13: ...as the button is held Enables Pump Priming After the reset button has been held for 15 seconds the button can then be clicked during the next ignition sequence to enter Pump Prime mode Run igniter is...

Page 14: ...The fuel valve is opened A flame should be established within the 15 second lockout time LOCKOUT If flame is not sensed by the end of the TFI the control shuts down on safety lockout and must be manu...

Page 15: ...until the retention head engages the fixed stops in the retention ring at the end of the air tube Refer to Figure 10 Tighten the zero setting locking nut The rear door must be closed The adjustment sc...

Page 16: ...Head Retention Head Head Support Legs Head Support Legs Electrode Tips Electrode Tips Electrode Clamp Electrode Clamp Electrode Bracket Electrode Bracket Electrode Insulator Electrode Insulator Elect...

Page 17: ...lint or foreign material Use a clean soft cloth with a degreaser to clean any accumulated soot or oil stains from the throttle cup sight windows Check motor current The amp draw should not exceed the...

Page 18: ...utilizes pressures higher than 100 psig so the actual nozzle flow rate will be greater than the gph stamped on the nozzle body Example A 1 00 gph nozzle 140 psig 1 18 gph For typical nozzle flow rates...

Page 19: ...92 0 99 1 06 0 85 0 95 1 01 1 04 1 13 1 20 0 90 1 01 1 07 1 10 1 19 1 27 1 00 1 12 1 18 1 23 1 32 1 41 1 10 1 23 1 30 1 35 1 46 1 56 1 20 1 34 1 42 1 47 1 59 1 70 1 25 1 39 1 48 1 53 1 65 1 77 1 35 1...

Page 20: ...he splined nut and the lower acorn nut 1 2 3 Turn the air adjustment screw clockwise to adjust the plate with the pointer to the zero position Referring to Figure 10 slide the nozzle line assembly for...

Page 21: ...21 Weil McLain Ultra Oil NX Burner Manual Figure 13 Retention Head Throttle Cup Alignment Figure 14 Blower wheel assembly SK9670 Section Trained Service Technician s Regular Maintenance...

Page 22: ...22 4 22 19 9 17 16 23 10 1 24 6 7 2 15 11a 11c 11b 25 21 26 20 11d 8 5 Section Replacement Parts For best performance specify genuine Beckett replacement parts Replacement Parts...

Page 23: ...et air louvers 1013U 19 Nozzle Line Electrode and Head Assembly Specify 20 PSC Motor Requires Mounting screws 20 x 7 8 21805U 4189 21 Primary control 7505P 22 Retention head assembly 6 slot 51785U 23...

Page 24: ...e choose one of the following options Visit our website at www beckettcorp com warranty Email your request to rwb customer service beckettcorp com Write to R W Beckett Corporation P O Box 1289 Elyria...

Reviews: