Diesel Gen-set Operation Instructions
51
Finally, press
manual mode button on control panel to switch to the manual
mode, and LED indicator light turns on. After the controller is in manual mode, press
start button again to start the Gen-set manually; if you want to stop the Gen-set,
press
stop button. After safety supervision delay time is over, “Gen power on”
indicator light on controller turns on, indicating that the engine is operating.
For automatic/self-switching Gen-set, the Gen-set will simulate mains power failure
after the Gen-set is switched to AUTO mode
and mains power test mode
button is pressed. After being started, the Gen-set will supply power to loads. If you
want to stop the Gen-set, press
stop button.
Note: do not start the Gen-set when being loaded, namely air switch shall be in
switching-off position when the Gen-set is started.
Note: if starting is not successful, try again approximately 20s later. If starting
does not realized continuously for 3 times, top starting and try again after
battery voltage or fuel pipe, etc. related trouble factors are eliminated.
2. Operating capacity
2.1 Operation
After the Gen-set is started successfully, operate it under rated conditions to check
operating state of the Gen-set. Main checking contents are as follows:
1) Check if speed of the Gen-set is normal or not by viewing display screen of the
module;
2) Check if oil pressure of the Gen-set is normal or not. The oil pressure shall not be
lower than 0.15Mpa;
3) Check if pipeline of fuel, lubrication and cooling system leaks or not;