background image

Programming

Table 5.4:

Remote Commands of parameter P0682

Operation Mode

Command

P0202 = 0
Transparent

Command 1

No function.

Command 2

No function.

Command 3

No function.

P0202 = 1
Overload Relay

Command 1

No function.

Command 2

No function.

Command 3

No function.

P0202 = 2
Direct Starter

Command 1

0

1 turns off the motor.

Command 2

0

1 turns on the motor.

Command 3

No function.

P0202 = 3
Reverse Starter

Command 1

0

1 turns off the motor.

Command 2

0

1 turns on the motor in forward direction.

Command 3

0

1 turns on the motor in reverse direction.

P0202 = 4
Star-Delta Starter

Command 1

0

1 turns off the motor.

Command 2

0

1 turns on the motor.

Command 3

No function.

P0202 = 5
Dahlander Starter

Command 1

0

1 turns off the motor.

Command 2

0

1 turns on the motor with high speed.

Command 3

0

1 turns on the motor with low speed.

P0202 = 6
Pole-Changing Starter

Command 1

0

1 turns off the motor.

Command 2

0

1 turns on the motor with high speed.

Command 3

0

1 turns on the motor with low speed.

P0202 = 7
PLC Mode

Command 1

No function.

Command 2

No function.

Command 3

No function.

P0751 – ETHERNET COMMUNICATION STATUS

Range:

0 = Setup
1 = Init
2 = Wait Comm
3 = Idle
4 = Data Active
5 = Error
6 = Reserved
7 = Exception
8 = Access Error

Default:

-

Properties:

RO

Description:

It allows identifying the Ethernet communication status.

Table 5.5:

P0751 indications

Indication

Description

0 = Setup

Module identified, waiting configuration data (automatic).

1 = Init

Module performing interface initialization procedure (automatic).

2 = Wait Comm

Initialization finished, but no communication with master.

3 = Idle

Communication with master established, but in Idle mode or Program mode.

4 = Data Active

Communication with master established and performing normal I/O data handling. ”On-
line”.

5 = Error

Communication error detected.

6 = Reserved

Reserved

7 = Exception

Major fault detected by the Ethernet interface. Requires interface reinitialization.

8 = Access error

Major fault detected between device and Ethernet interface. Requires interface reinitia-
lization.

SRW01-ETH | 16

Summary of Contents for SRW01-ETH Series

Page 1: ...Motors Automation Energy Transmission Distribution Coatings Ethernet SRW01 ETH User s Guide ...

Page 2: ...Ethernet User s Guide Series SRW01 ETH Language English Document Number 10002708521 02 Build 662 Publication Date 12 2017 ...

Page 3: ...Programming 12 5 1 Symbols for the Properties Description 12 P0029 Value of Addressing Switches 12 P0313 Action in Case of Communication Error Fieldbus 12 P0680 Status Word 13 P0682 Control Word 14 P0751 Ethernet Communication Status 16 P0753 Ethernet Baud Rate 17 P0756 Modbus TCP Timeout 17 P0760 IP Address Configuration 17 P0761 IP Address 1 18 P0762 IP Address 2 18 P0763 IP Address 3 18 P0764 IP...

Page 4: ... an Ethernet Network 29 7 7 2 Configuring the Drive 29 7 7 3 Configuring the Master 29 7 7 4 Communication Status 29 7 7 5 Operation Using Process Data 30 8 PROFINET 31 8 1 IP Address Configuration 31 8 2 Station Name Configuration 31 8 3 Indication LEDs 32 8 4 Cyclic Data 32 8 5 Acyclic Data 32 8 6 XML File GSDML 32 8 7 Modbus TCP Connections 33 8 8 Startup Guide 33 8 8 1 Installing the Product on an...

Page 5: ...ABOUT THE MANUAL This manual supplies the necessary information for the operation of the SRW01 ETH smart relay using the Ethernet interface This manual must be used together with the SRW01 ETH user s manual SRW01 ETH 5 ...

Page 6: ...eed of cross over cables The interface also makes available a Web server HTTP 1 1 MODBUS TCP SPECIFIC CHARACTERISTICS Operates as Modbus TCP server The server provides up to 4 simultaneous Modbus TCP connections Allows data communication for equipment operation and parameterization as well as markers and data used for SRW01 ETH ladder programming 1 2 ETHERNET IP SPECIFIC CHARACTERISTICS It is supp...

Page 7: ...on Ethernet multiple protocols and higher level services were specified and developed in order to perform desired activities over a network such as packet routing connection establishment sending and receiving files etc Several of these protocols have also been widely disseminated and employed such as IP TCP UDP FTP HTTP Widely used to interconnect computers in the office environment the Ethernet tec...

Page 8: ...ed of cross over cables The housings of the Ethernet connectors which are normally connected to the cable shield have connections between themselves and to the protective earth X NOTE When the equipment is turned off the built in switch is also deactivated 3 2 INDICATION LEDS The smart relay SRW01 ETH has LEDs in the each Ethernet port connector PORT1 and PORT2 besides a bicolor diagnostics LED NE...

Page 9: ... Ethernet link established but without activity Flashing Green Ethernet link established and with activity Table 3 3 LED 2 amber Link Activity 10Mbps Status Description Off Without link or device turned OFF Amber Ethernet link established but without activity Flashing Amber Ethernet link established and with activity SRW01 ETH 9 ...

Page 10: ...ATION RATE The Ethernet interfaces of the SRW01 ETH smart relay can communicate using the 10 or 100 Mbps rates in half or full duplex mode The baud rate is programmed at P0753 X NOTE It is important that for each Ethernet connection made between two points the baud rate and the duplex mode are set to the same option If the option AUTO is used in one of the points you must set the other point also ...

Page 11: ...ING The correct connection with the ground decreases problems caused by interference in an industrial environment The following are some recommendations about grounding and cable routing Always use shielded twisted pair Ethernet cables and connectors with metallic housing Connect the equipment grounding via grounding terminal Avoid the cable connection on multiple grounding points especially where...

Page 12: ...t is controlled via network and a communication error is detected Table 5 1 P0313 options Option Description 0 Only Fault Indication Fault indication only with no action taken The indication of fault will be automatically removed if the fault condition is cleared and the relay status are not either Trip or Error If the relay status is Trip or Error it is mandatory to perform error reset in order t...

Page 13: ...ed via the used network interface This programming is achieved by means of parameters P0220 to P0232 P0680 STATUS WORD Range 0000h FFFFh Default Properties RO Description It allows the device status monitoring Each bit represents a specific status Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function Reserved Digital Output O4 Status Digital Output O3 Status Digital Output O2 Status Digital Output O1 ...

Page 14: ...ital input is deactivated 1 I15 digital input is activated Bit 10 Digital Input I16 Status 0 I16 digital input is deactivated 1 I16 digital input is activated Bit 11 Digital Output O1 Status 0 O1 digital output is deactivated 1 O1 digital output is activated Bit 12 Digital Output O2 Status 0 O2 digital output is deactivated 1 O2 digital output is activated Bit 13 Digital Output O3 Status 0 O3 digi...

Page 15: ...put 1 activates the O4 digital output Bit 9 Digital Output O5 Value 0 deactivates the O5 digital output 1 activates the O5 digital output Bit 10 Digital Output O6 Value 0 deactivates the O6 digital output 1 activates the O6 digital output Bit 11 Digital Output O7 Value 0 deactivates the O7 digital output 1 activates the O7 digital output Bit 12 Digital Output O8 Value 0 deactivates the O8 digital ...

Page 16: ... on the motor with high speed Command 3 0 1 turns on the motor with low speed P0202 7 PLC Mode Command 1 No function Command 2 No function Command 3 No function P0751 ETHERNET COMMUNICATION STATUS Range 0 Setup 1 Init 2 Wait Comm 3 Idle 4 Data Active 5 Error 6 Reserved 7 Exception 8 Access Error Default Properties RO Description It allows identifying the Ethernet communication status Table 5 5 P07...

Page 17: ... TIMEOUT Range 0 0 to 65 5 s Default 0 0 Properties RW Sys Description It allows programming a time limit for the detection of Ethernet offline error for Modbus TCP protocol If the SRW01 ETH remains without receiving valid telegrams longer than the time programmed in this parameter it will be considered that a communication error has occurred the alarm E0131 will be showed on the HMI and the option...

Page 18: ...92 168 0 10 Properties RW Sys Description If P0760 0 parameters these parameters allow you to program the IP address of the Ethernet interface For other option of P0760 these parameters have no function Each parameter programs one octet of the IP address where the P0761 is the most significant octet The program med IP address then has the format P0761 P0762 P0763 P0764 X NOTE For the changes in thi...

Page 19: ... 255 255 255 254 16 255 255 0 0 X NOTE For the changes in this parameter be effective the equipment must be powered off and on again or an update must be performed by P0899 X NOTE For Modbus TCP and EtherNet IP protocols this parameter is only used if the addressing switches on the product for IP address setting are set to 0 P0766 GATEWAY 1 P0767 GATEWAY 2 P0768 GATEWAY 3 P0769 GATEWAY 4 Range 0 2...

Page 20: ... different from zero The first parameter set to zero disables the use of itself and the other parameters in the sequence For example if you set P0800 680 P0680 status P0801 3 P0003 current P0802 0 disabled Only two read words state and current will be communicated with the master The same number of words pro grammed into the equipment must be programmed in the master when configuring the network Mod...

Page 21: ...d into the equipment must be programmed in the master when configuring the network Modbus TCP protocol allows to access each parameter directly and do not distinguish cyclic and acyclic data X NOTE For the changes in these parameters be effective the equipment must be powered off and on again or an update must be performed by P0899 P0899 UPDATE ETHERNET CONFIGURATION Range 0 Normal Operation 1 Upda...

Page 22: ...760 P0769 01h FEh The combination of switches 1 and 2 form the value to configure the last digit of the IP address 192 168 0 x with subnet mask 255 255 255 0 gateway and DHCP disabled FFh Reserved X NOTE For the changes in this parameter be effective the equipment must be powered off and on again or an update must be performed by P0899 6 2 INDICATION LEDS In addition to the LEDs next to the Etherne...

Page 23: ...e device model 6 4 MEMORY MAP The smart relay SRW01 ETH has different types of data accessible through the Modbus communication These data are mapped at data addresses and access functions as described in the following items 6 4 1 Parameters The SRW01 ETH Modbus communication is based on the reading writing of the equipment parameters All the drive parameters list is made available as 16 bit holdi...

Page 24: ... addresses via Modbus 6 5 COMMUNICATION ERRORS Communication errors may occur in the transmission of telegrams as well as in the contents of the transmitted telegrams Transmission and connection errors are directly processed by the Ethernet interface and by the TCP IP protocol In the event of a successful reception during the treatment of the telegram the server may detect problems and send an err...

Page 25: ...o control the device we can mention P0680 Status Word P0682 Control Word 6 If necessary restart the Ethernet interface using P0899 6 6 3 Configuring the Master The way you do the network setup is highly dependent on the network master and the network configuration tool It is important to know the tools used to perform this activity In general the following steps are required to perform the network c...

Page 26: ...ed data is written and read by the Modbus TCP network master automatically Using these parameters the master is able to control the equipment and monitor its operation It is important to know the device parameters to program the master as desired for the application SRW01 ETH 26 ...

Page 27: ...f switches 1 and 2 form the value to configure the last digit of the IP address 192 168 0 x with subnet mask 255 255 255 0 gateway and DHCP disabled FFh Reserved X NOTE For the changes in this parameter be effective the equipment must be powered off and on again or an update must be performed by P0899 7 2 INDICATION LEDS In addition to the LEDs next to the Ethernet connectors the smart relay SRW01 ...

Page 28: ...00 162 A2h 400 5 The data is transmitted as an integer value without the indication of the decimal places 7 5 EDS FILE Each device on an EtherNet IP network has an EDS configuration file which contains information about the device functions on the network This file is used by a master or configuration software to program devices present at EtherNet IP network The EDS file is available from WEG website ...

Page 29: ...n the network configuration tool 2 Select SRW01 ETH smart relay from the available list of devices on the network configuration tool This can be done manually or automatically if allowed by the tool 3 For the master configuration in addition to the IP address used by the EtherNet IP module you must indicate the number of instances of I O and the amount of data exchanged with the master in each instan...

Page 30: ... in the I O area is automatically updated between master and slave Among the main parameters that can be used to control the device we can mention P0680 Status Word read P0682 Control Word write It is important to know these parameters to program the master as desired for the application SRW01 ETH 30 ...

Page 31: ...u to program how to configure the Station Name where the switch Ê represents the most significant digit and the switch Ë represents the less significant digit Figure 8 1 Addressing Switches Table 8 1 Addressing switches configuration for PROFINET IO Values for switches 1 and 2 Configuration 00h Station Name do not program the Station Name and this configuration must be done via network using the DCP pro...

Page 32: ...n addition to the cyclic data the PROFINET protocol also provides acyclic data mainly used to communicate diag noses and parameterization data For the SRW01 ETH smart relay the parameter list is available using this commu nication method The PROFINET protocol defines the following structure to address the components for network configuration AR Application Relation API Application Process Identifier ...

Page 33: ...lated to device settings motor parameters desired functions for I O signs etc 2 Program command sources as desired for application 3 Program communication parameters such as Station Name etc 4 Set the desired action for communication errors through the P0313 5 Set number of I O words as well as the contents of each word using parameters P0800 to P0819 and P0850 to P0869 6 If necessary restart the ...

Page 34: ...f the interface and communication The parameter P0751 indicates the status of communication between the device and the network master The network master must also provide information about the communication with slave 8 8 5 Operation Using Process Data Once the communication is established the data mapped in the I O area is automatically updated between master and slave Among the main parameters t...

Page 35: ...ss bar and it will present a web page with links to interface settings and device data Figure 9 1 WEB page for interface configuration In the interface settings it presents several fields for programming the IP address subnet DHCP among others The parameter list of the equipment can also be accessed through the WEB browser via Parameter Data link This list is presented in a simplified format with onl...

Page 36: ...contact in the communication cables Verify the entire network installation cable laying grounding E0130 ETHERNET INTERFACE ACCESS ERROR Description Indicates internal error in data exchange between SRW01 ETH smart relay and Ethernet interface Actuation It occurs when the control board can not exchange data with the Ethernet interface or when the Ethernet interface identifies some internal error In ...

Page 37: ...f the first valid telegram After the communication timeout has been identified the E0131 message will be showed on the HMI When the communication is reestablished the error indication will be removed from the HMI Possible Causes Correction Check network installation broken cable or fault poor contact on the connections with the network grounding Make sure that the Modbus TCP client sends telegrams t...

Page 38: ...WEG Drives Controls Automação LTDA Jaraguá do Sul SC Brazil Phone 55 47 3276 4000 Fax 55 47 3276 4020 São Paulo SP Brazil Phone 55 11 5053 2300 Fax 55 11 5052 4212 automacao weg net www weg net ...

Reviews: