Programming
X
NOTE!
For the product with Modbus TCP protocol, it will indicate status 4 (Data Active) from the receipt of
the first valid TCP Modbus telegram, and does not change state if the Modbus TCP communication
timeout occurs.
P0753 – ETHERNET BAUD RATE
Range:
0 = Auto
1 = 10Mbit/s, half duplex
2 = 10Mbit/s, full duplex
3 = 100Mbit/s, half duplex
4 = 100Mbit/s, full duplex
Default:
0
Properties:
RW, Sys
Description:
It allows to set the desired baud rate for the Ethernet interface.
X
NOTE!
For the changes in this parameter be effective, the equipment must be powered off and on again,
or an update must be performed by P0899.
For PROFINET interface, the baud is locked to 100Mbit/s as required by the protocol.
P0756 – MODBUS TCP TIMEOUT
Range:
0.0 to 65.5 s
Default:
0.0
Properties:
RW, Sys
Description:
It allows programming a time limit for the detection of Ethernet offline error, for Modbus TCP protocol. If the SRW01-
ETH remains without receiving valid telegrams longer than the time programmed in this parameter, it will be considered
that a communication error has occurred, the alarm E0131 will be showed on the HMI and the option programmed
in P0313 will be executed.
After being powered up, the SRW01-ETH starts counting this time from the first received valid telegram. The value
0.0 disables this function.
X
NOTE!
For the changes in this parameter be effective, the equipment must be powered off and on again, or
an update must be performed by P0899.
P0760 – IP ADDRESS CONFIGURATION
Range:
0 = Parameters
1 = DHCP
2 = DCP
Default:
1
Properties:
RW, Sys
Description:
It allows to choose how to set the IP address for the Ethernet interface.
SRW01-ETH | 17