Programming
Table 5.3:
P0682 bits function
Bit
Value/Description
Bit 0
Command 1*
Varies according to the chosen operation mode (P0202).
Bit 1
Command 2*
Varies according to the chosen operation mode (P0202).
Bit 2
Command 3*
Varies according to the chosen operation mode (P0202).
Bit 3
Reset
0
→
1
: when faulted (trip), it executes the relay reset.
Bit 4
Remote**
0
: changes to local mode.
1
: changes to remote mode.
Bit 5
Digital Output O1 Value***
0
: deactivates the O1 digital output.
1
: activates the O1 digital output.
Bit 6
Digital Output O2 Value***
0
: deactivates the O2 digital output.
1
: activates the O2 digital output.
Bit 7
Digital Output O3 Value***
0
: deactivates the O3 digital output.
1
: activates the O3 digital output.
Bit 8
Digital Output O4 Value***
0
: deactivates the O4 digital output.
1
: activates the O4 digital output.
Bit 9
Digital Output O5 Value***
0
: deactivates the O5 digital output.
1
: activates the O5 digital output.
Bit 10
Digital Output O6 Value***
0
: deactivates the O6 digital output.
1
: activates the O6 digital output.
Bit 11
Digital Output O7 Value***
0
: deactivates the O7 digital output.
1
: activates the O7 digital output.
Bit 12
Digital Output O8 Value***
0
: deactivates the O8 digital output.
1
: activates the O8 digital output.
Bit 13...15
Reserved.
*In order to have those commands executed, it is necessary that the smart relay be in remote mode. Remote
Commands are equivalent to the commands via digital inputs I11, I12 and I13 and are used to drive the motor
depending on the operating mode selected in P0202.
**For the Local/Remote selection, it is necessary to program the parameter P0220 with the Fieldbus option.
***For the control of the digital outputs, it is necessary to program the parameters P0277 to P0284 with the Fieldbus
option.
SRW01-ETH | 15