5
DETAILED PARAMETER DESCRIPTION
Description:
Refer to P0234 (Analog input AI1 gain (unipolar MVC4 board)).
P0725 - Minimum coasting time
Adjustable range:
0 to 300 s
Factory setting:
0 s
Acesso:
Menu
→
Configurations
→
Control
Description:
The minimum coasting time determines for how long the inverter will not be accepting the General Enable or
Start/Stop command after a coasting stop (P0232 = 1 (General disable)).
By programming 0 at this parameter the function is deactivated.
P0740 - Function of analog input AI1 MVC3
Adjustable range:
0 to 2
Factory setting:
0
Acesso:
Menu
→
Configurations
→
I/O
→
Analog inputs
Description:
It defines the function of the AI1 analog input of the MVC3 board.
Table 5.71:
Function of analog input AI1 MVC3
Function
0
Not Used
1
Torque reference
2
Limit current
P0741 - Analog input AI1 gain (bipolar MVC3 board)
Adjustable range:
0.000 to 9.999
Factory setting:
1.000
Acesso:
Menu
→
Configurations
→
I/O
→
Analog inputs
Description:
It sets the gain of analog input AI1 of the MVC3 board.
Refer to P0234 (Analog input AI1 gain (unipolar MVC4 board)).
P0742 - Analog input AI1 offset (bipolar MVC3 board)
Adjustable range:
-100.0 to 100.0 %
Factory setting:
0.0 %
Acesso:
Menu
→
Configurations
→
I/O
→
Analog inputs
Description:
It sets the offset of analog input AI1 of the MVC3 board.
Refer to P0234 (Analog input AI1 gain (unipolar MVC4 board)).
P0744 - Function of analog input AI2 MVC3
Adjustable range:
0 to 1
Factory setting:
0
Acesso:
Menu
→
Configurations
→
I/O
→
Analog inputs
MVW3000 | 5-96