Table B.3:
Conducted and radiated emission levels, and additional information
Tabla B.3:
Niveles de emisión conducida y irradiada y informaciones adicionales
Tabela B.3:
Níveis de emissão conduzida e radiada e informações adicionais
Inverter Model
(With Build-in RFI Filter)
Modelo del Convertidor de Frecuencia
(Con Filtro RFI Interno)
Modelo do Inversor
(Com Filtro RFI Interno
Conducted Emission –
Maximum Motor Cable Length
Emisión Conducida –
longitud Maxima del Cable del Motor
Emissão Conduzida –
Comprimento Máximo do Cabo do Motor
Radiated
Emission
Emisión Radiada
Emissão Radiada
Category C3
Categoría C3
Categoria C3
Category C2
Categoría C2
Categoria C2
Category
Categoría
Categoria
1
CFW501A01P0T4...C3...
6 m
-
C3
2
CFW501A01P6T4...C3...
6 m
-
C3
3
CFW501A02P6T4...C3...
6 m
-
C3
4
CFW501A04P3T4...C3...
6 m
-
C3
5
CFW501A06P1T4...C3...
6 m
-
C3
6
CFW501B02P6T4...C3...
20 m
-
C3
7
CFW501B04P3T4...C3...
20 m
-
C3
8
CFW501B06P5T4...C3...
20 m
-
C3
9
CFW501B10P0T4...C3...
20 m
-
C3
10
CFW501C14P0T4...C2...
30 m
20 m
C3
11
CFW501C16P0T4...C2...
30 m
20 m
C3
12
CFW501D24P0T4...C3...
(1)
Contact WEG
Consulte a WEG
Consulte la WEG
-
C3
13
CFW501D31P0T4...C3...
(1)
-
C3
Note:
(1)
In models 12 and 13, WEG must be consulted in order to check the inverter installations and operating conditions.
Nota:
(1)
En los modelos 12 y 13, WEG deberá ser consultada para verificar las condiciones de instalación y operación del convertidor.
Nota:
(1)
Nos modelos 12 e 13, a WEG deve ser consultada para verificar as condições de instalação e operação do inversor.
Notes:
For conducted emission category C2, the switching frequency is 5 kHz for models 10 and 11.
For conducted emission C2, in models 10 and 11, use the ferrite 12473659 on the output cables (2 turns).
For conducted emission category C3, the switching frequency is 5 kHz for models 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12 and 13.
For conducted emission category C3, in models 1, 2, 3, 4, 5, 6, 7, 8 and 9, use the ferrite 12480705 on the output cables (2
turns) and use the ferrite 12480705 on the input cables (2 turns).
For conducted emission C3, in models 10 and 11, use the ferrite 12473659 on the output cables (1 turn).
For conducted emission category C3, in models 12 and 13, use the ferrite 12983778 on the output cables (1 turn) and use the
ferrite 12983778 on the input cables (2 turns).
For Radiated Emission, in models 1, 2, 3, 4 and 5, use shielded cable up to 6 m.
For Radiated Emission, in models 6, 7, 8, 9, 12 y 13, use shielded cable up to 30 m.
For Radiated Emission, in models 10 and 11, use the ferrite 12473659 on the output cables (1 turn). Use shielded cable up to
30 m.
Notas:
Para emisión conducida categoría C2, la frecuencia de conmutación es de 5 kHz para los modelos 10 y 11.
Para emisión conducida categoría C2, en los modelos 10 y 11, utilizar ferrita 12473659 en los cables de salida (2 vueltas).
Para emisión conducida categoría C3, la frecuencia de conmutación es de 5 kHz para los modelos 1, 2, 3, 4, 5, 6, 7, 8, 9, 10,
11, 12 y 13.
Para emisión conducida categoría C3, en el modelos 1, 2, 3, 4, 5, 6, 7, 8 y 9, utilizar ferrita 12480705 en los cables de salida (2
vueltas) y utilizar ferrita 12480705 en los cables de entrada (2 vueltas).
Para emisión conducida categoría C3, en los modelos 10 y 11, utilizar ferrita 12473659 en los cables de salida (1 vuelta).
Para emision conducida categoria C3, en el modelos 12 y 13, utilizar ferrita 12983778 en los cables de salida (1 vuelta) y utilizar
ferrita 12983778 en los cables de entrada (2 vueltas).
Para Emisión Radiada, en los modelos 1, 2, 3, 4 y 5, utilizar cable blindado de hasta 6 m.
Para Emisión Radiada, en los modelos 6, 7, 8, 9, 12 y 13, utilizar cable blindado de hasta 30 m.
Para Emisión Radiada, en los modelos 10 y 11 utilizar ferrita 12473659 en los cables de salida (1 vuelta). Utilizar cable blindado
de hasta 30 m.