Installation and Connection
CFW-11W G2 | 3-39
3
Drive 3 - Run/Stop function with three-wire control.
Enabling of the Run/Stop function with three-wire control.
Parameters to be set:
Program DI3 to START.
P0265 = 6.
Program DI4 to STOP.
P0266 = 7.
Program P0224 = 1 (DIx) in case you wish the 3-wire control in Local mode.
Program P0227 = 1 (DIx) in case you wish the 3-wire control in Remote mode.
Program the Direction of Rotation via DI2.
Program P0223 = 4 for Local Mode or P0226 = 4 for Remote Mode.
S1 and S2 are, respectively, ON (NO contact) and OFF (NC contact) pushbuttons.
The speed reference can be via AI analog input (as in Drive 2), via HMI (as in Drive 1) or another source.
Forward/Reverse
S3 (FWD/REV)
Stop S2
Start S1
Conector XC1
1
+ REF
2
AI1+
3
AI1-
4
- REF
5
AI2+
6
AI2-
7
AO1
8
AGND (24 V)
9
AO2
10
AGND (24 V)
11
DGND*
12
COM
13
24 Vcc
14
COM
15
DI1
16
DI2
17
DI3
18
DI4
19
DI5
20
DI6
21
NF1
DO1
(RL1)
22
C1
23
NA1
24
NF2
DO2
(RL2)
25
C2
26
NA2
27
NF3
DO3
(RL3)
28
C3
29
NA3
Figure 3.46:
Connections in XC1 for Drive 3